GENPAD HURRICANE PADS FOR KOHLER GENERATORS

SOUTH FLORIDA (MIAMI DADE, BROWARD, PALM BEACH COUNTIES)


5523 WEST CYPRESS STREET CLIENT: DIVERSITECH
SUITE 200 PROJECT: WIND ANALYSIS HURRICANE PADS MAX. WIND SPEED 175 MPH
TAMPA, FLORIDA 33607 CODES: FLORIDA BUILDING CODE 2010
ASCE 7-10
EB: 8426 RISK CATEGORY = II
MIAMI DADE COUNTY BASIC WIND SPEED = 175 MPH
BROWARD COUNTY BASIC WIND SPEED = 170 MPH
USE A BASIC WIND SPEED OF 175 MPH
JAMES R. MEHLTRETTER, P.E.
FL # 33860 Kz= 0.85 Exposure C ; Table 28.3-1
Kd= 0.85 Table 26.6-1
March 5, 2012 Kzt= 1.00 Figure 26.8-1

Wind Speed V= 175.00

qz= 0.00256*Kz*Kzt*Kd*V^2*I 56.57 PSF (4) 3/8" DIA 1 1/2" LONG ZINC COATED SET IN 4" SOLID CONCRETE
F= qz*G*Cf*Af (Eq. 6-28)
G= 0.85 PULLOUT = 3899# ULT PER TEST (ASTM E-488-96 SEE NOTE 6)
Cf= (Figure 6-21)ASCE 1.30 PULLOUT = 974# SERVICE (FS=4.0)
NOTES:
INSTALL BOLTS THROUGH UNIT BASE PER 1 LOAD COMBINATION ASD PER 2.4.1 ASCE 7-10
MANUFACTURE'S SPECIFICATIONS 0.6 x DEAD + 0.6 x WIND (ASCE 7-10; 2.4.1)
Wind Pressure 62.51 PSF 2 DESIGN IS BASED ON SECTION 29.5 OF ASCE 7-10 "OTHER STRUCTURES"
F= Wind Pressure *Af See Tables UNITS ARE TO BE LOCATED ON THE GROUND.
Af = L x H 3 ALL OTHER UNITS NOT SHOWN MUST BE DESIGNED ON A
CASE BY CASE BASIS.
4 LARGER HURRICANE PAD USED IN SOME COMBINATIONS TO SATISFY
DESIGN CHECK.
5 WIND PRESSURE ON UNITS IN ACCORDANCE WITH ASCE 7-10 FIGURE 29.5-1
GENPAD HURRICANE PAD 4" THICK 6 ANCHOR TEST DATA BASED ON ARCHITECTURAL TESTING REPORT
MODEL # WEIGHT L W NUMBER A7207.01-106-31 DATED 03/04/2011.
WIND SPEED Pressure
175.00 62.51 PSF FG3154-4K 275 54 31

PAD .6(UNIT + PAD)


MAXIMUM UNIT DIMENSIONS MINIMUM WEIGHT PAD WEIGHT WEIGHT .6xDEAD .6xWIND REMARKS
ASD DEAD ASD DESIGN Allowable Allowable
LOAD WIND Pressure Wind
W L H POUNDS MODEL # MOMENT F MOMENT SF DESIGN qz Speed V
NUMBER FT-# # FT-# OVERTURN CHECK PSF MPH
KOHLER UNITS MODEL NUMBER
14 kw 14 RES 26.200 48.000 29.000 410 FG3154-4K 275 411 530.88 604.27 438.10 1.21 OK OK FOR 175 MPH 75.7 193
20 kw 20 RES 26.200 48.000 29.000 500 FG3154-4K 275 465 600.63 604.27 438.10 1.37 OK OK FOR 175 MPH 85.7 205

4" DIA. SOLID CONCRETE @ BOLTS


TYPICAL

FG3154-4K PAD

Page 1 of 1