Rumaila Project

(FEED) Date: 10-Jan-13


Data Sheet for Medium Term Power Supply 11 kV Switchgear Revision: 0

00100W-C-PG-PP03-EL-DAS-0008 Page: 2 of 13

REVISION DESCRIPTION SHEET

Rev. Sheet/Section Reason for Revision

A Issued for Inter Discipline Check


B Issued for Client Review
0 Issued for Use

Hold No. Sheet/Section Description of Hold

1 Deleted
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 3 of 13
00100W-C-PG-PP03-EL-DAS-0008

NOTES AND ABBREVIATIONS


1 (1) For additional information, refer to Specification - HV Switchgear 00100W-C-G0-G000-EL-SPC-0002 and Initial Template Design Medium Term Single-Line Diagram
2 for 11KV Generator Sets: 00100W-C-PG-PP03-EL-DSL-0003-001.
3
4 (2) Type test certificates for similar rating switchboards shall be submitted with the bid, if available. Otherwise type tests shall be carried out for the equipment.
5
6 (3) Withdrawable vacuum circuit breakers and fused vacuum contactors shall be interchangeable with others of the same voltage and current rating.
7
8 (4) All feeders shall be suitable for termination of cable sizes indicated in relevant documents.
9
10 (5) Manufacturer to advise on Utilisation Category of contactors in accordance with IEC 62271-106, Table 2, where application of contactor is to switch transformer load.
11
12 (6) Earth Fault relay on vacuum contactors shall have a time delay function available for co-ordination purposes.
13
14 (7) Each circuit breaker and vacuum contactor shall have an individual remote OPEN and CLOSE control station.
15
16 (8) SUPPLIER's Standard paint finish procedure may be submitted for COMPANY approval in place of Project Specification.
17
18 (9) Deleted.
19
20 (10) Refer to Basic Engineering Design Data 00100W-C-G0-G000-GE-BOD-0001 for environmental conditions
21
22 (11) Deleted.
23
24 (12) Switchgear specification and cable sizing is based on the assumption that 4 generators operating in parallel will have a fault level of less than 10 kA.
25
26 (13) Where typical core balance CTs are specified, they shall be located internal to the switchboard cubicle.
27
28
29
30 Abbreviations:
31 c/w = Complete with
32 ESD = Emergency Shut Down
33 FVC = Fused Vacuum Contactor
34 IAC = Internal Arc Classification
35 ICMS = Integrated Control and Monitoring System
36 MPR = Motor Protection Relay
37 N/A = Not Applicable
38 STA = Supplier to Advise
39 TBA =To Be Advised
40 VCB = Vacuum Circuit Breaker
41 HDHC = Hard Drawn High Conductivity
42 RCU = Remote Control Unit
43 AFLR = Access from the front (F), from the sides (L = Lateral) and from the rear (R) by Authorised personnel only.
44 UCP = Unit Control Panel
45 CT = Current Transformer
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 4 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 ENVIRONMENTAL CONDITIONS POWER SYSTEM
6 Location: Indoor System Voltage (MV): 11000 V  5%
7 Ambient Temp: HVAC Controlled Min: Note 10 Max: Note 10 System Frequency: 50 Hz  1%
8 HVAC Failed: Min: Note 10 Max: Note 10
9 Humidity: Note 10 Altitude: Note 10
10 Hazardous area classification: Not Applicable System Neutral Earthing: Resistance Earthed, 100A
11 System X/R ratio: TBA
12 Seismic: UBC 97
13 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
14 11kV Switchboard General Data
15 General
16 Standard of manufacture IEC 62271
17 Type / Model No. Air insulated, metal enclosed / STA
18 Location Indoor, non-hazardous
19 Nominal voltage kV 11
20 Nominal frequency Hz 50
21 Number of phases 3
22 Rated lightning impulse withstand voltage (Up) kV (peak) 60
23 Rated short duration power frequency w'stand voltage (Ud) kV (rms) 28
24 Rated short time withstand current and time (Ik) kA (rms) 16 kA for 3 sec
25 Internal arc fault withstand, to IEC 62271-200 Yes (IAC AFLR)
26 Duration of internal arc fault test secs STA
27 Rated peak withstand current kA (peak) 40
28 Design Temperature Degree C 45
29 Panel exterior paint colour SUPPLIER Standard
30 Panel interior paint colour SUPPLIER Standard
31 Paint specification (Note 8) 00100W-C-G0-G000-ML-SPC-0009
32 Overall dimensions of the switchboard: (L X W x H) mm STA
33 Total weight STA
34 Largest shipping section dimensions (L X W x H) mm STA
35 Shipping sections (number and weights) STA
36 Expected assembly heat dissipation W STA
37 Ingress protection rating IP4X
38 Earth busbar withstand current and time kA (rms) As per Switchgear
39 Bus bar System:
40 Rated normal current (main busbar) A 630
41 Phase segregated busbars Yes / No No
42 Busbar arrangement (Single / Duplicate) Single
43 Busbar identification Red-Yellow-Blue
44 Busbar material HDHC copper
45 Busbar insulation (Epoxy coated or sleeved) Yes/No STA
46 Future busbar extension at either end Yes/No Yes (both)
47 Spare feeders required Yes/No Yes
48 Circuit breaker type Vacuum
49 Contactor type Vacuum (latched)
50 Service continuity category LSC2A as per IEC 62271-200
51 Auxiliary supplies
52 Control and protection supply: Voltage V 110V d.c.
53 Total power consumption / Total standing load W STA
54 CB spring charger motor supply: Voltage V 230V a.c.
55 Total power consumption W STA
56 Heating supply: Voltage V 230V a.c.
57 Total power consumption W STA
58 Test requirements
59 Type test Yes/No Note 2
60 Routine tests Yes/No Yes
61 Special tests Yes/No No
62 11kV bus section earth switches
63 Integral earth switch required Yes/No Yes
64 Rated short time withstand current kA (rms) As per Switchgear
65 Rated short circuit making current kA (peak) As per Switchgear
66 Rated duration of short circuit sec As per Switchgear
67 Interlock Yes/No Yes (Mechanical)
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 5 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 INCOMER CIRCUIT BREAKER DATA (for each rating)
7 General
8 Manufacturer name STA
9 Circuit breaker application Generator Incomer
10 Number of incomer circuit breakers No. See schedule in page 13
11 Nominal voltage kV 11
12 Rated operational current A See schedule in page 13
13 Interrupting medium Vacuum
14 Number of poles Three
15 Closing mechanism Motor wound spring with 110V d.c release coil
16 Panel type Modular / Withdrawable
17 Rated short time withstand current and time kA (rms) 16 kA for 3 sec
18 Rated peak withstand current kA (peak) 40
19 Rated short circuit breaking current kA STA
20 Rated short circuit making current kA STA
21 Rated DC component of short circuit breaking current % STA
22 Rated insulation voltage kV STA
23 Rated impulse voltage withstand (Up) kV (peak) 60
24 Rated power frequency withstand voltage (1 min) (Ud) kV (rms) 28
25 Breaker breaking time secs STA
26 Breaker closing time secs STA
27 Maximum panel power dissipation W STA
28 ESD trip (Note 9) Yes/No Yes
29 Load shedding trip Yes/No No
30 Overall dimensions of the panel: (L x W x H) mm STA
31 Gland plate Yes/No Steel, un-drilled
32 Auxiliary voltages
33 Control and protection supply V 110V d.c (External)
34 CB spring charger motor supply V 230V a.c (External)
35 Heating supply V 230V a.c (External)
36 Panel control and indication
37 "Closed" indication (Red) Yes/No Yes
38 "Open" indication (Green) Yes/No Yes
39 'Trip'' indication (Yellow) Yes/No Yes
40 'Trip Circuit Healthy'' indication (White), where applicable Yes/No Yes
41 Anti-condensation heater 'ON' indication Yes/No Yes
42 Ammeter & Voltmeter c/w selector switch Yes/No Yes
43 Running hour counter Yes/No No
44 Control circuit supervision Yes/No No
45 Metering functions and alarm status Yes/No Yes
46 Remote "open" & "close" functional inputs Volt Free Yes/No Yes
47 Generator Protection requirements
48 25 Synchronism check relay Yes/No Yes
49 27/59 Under / overvoltage relay Yes/No Yes
50 32 Directional Power relay Yes/No Yes
51 40 Loss of Field relay Yes/No Yes
52 49G Generator overload Yes/No Yes
53 51V IDMT Voltage-Restrained Over current Yes/No Yes
54 51N IDMT Earth fault Yes/No Yes
55 51G Back-up earth fault Yes/No Yes
56 67/67N Directional O/C + E/F Yes/No Yes
57 81 O/U Over / Under frequency relay Yes/No Yes
58 86 Lockout relay Yes/No Yes
59 87 Differential protective relay Yes/No Yes
60 74TC Trip circuit supervision relay Yes/No Yes
61 Communications
62 Communications with ICMS/DCS: Protocol STA
63 DCS control inputs Yes/No No
64 ICMS/DCS status outputs Yes/No Yes
65 Redundant Yes/No No
66
67
68
69
70
71
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 6 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 INCOMER CIRCUIT BREAKER DATA (for each rating)
7 11kV cable earth switch
8 Integral earth switch required Yes/No Yes
9 Rated short time withstand current kA (rms) As per Switchgear
10 Rated short circuit making current kA (peak) As per Switchgear
11 Rated duration of short circuit sec As per Switchgear
12 Interlock Yes/No Yes. Integral to Circuit Breaker
13 11kV power cables
14 Type of cable Cu/XLPE/SWA/PVC
15 Voltage grade kV 6 / 10 (12)
16 No. of cables and minimum conductor size mm² See schedule in page 11
17 Cable entry Top/Bottom Bottom
18 Facility for HV cable screen earthing Yes/No Yes
19 Armour earthed via the cable gland Yes/No Yes
20 Auxiliary circuit LV cables
21 Motor anti-condensation heater cable size up to 3kW N/A
22 Motor anti-condensation heater cable size above 3kW N/A
2
23 RCU control cable Yes - 7c 2.5mm
24 UCP control cable (if applicable) Yes - 7c 2.5mm2
25 Voltage transformers
26 No. of secondaries No. STA
27 Ratio STA
28 Accuracy class STA
29 VA Rating VA STA
30 Protection current transformers
31 No. of cores No. 3
32 Ratio xxx/1A See schedule in page 11
33 Accuracy class 5P
34 Burden VA STA
35 Thermal rating factor STA
36 Measurement current transformers
37 No. of cores No. 3
38 Ratio xxx/1A See schedule in page 11
39 Accuracy class Class 1
40 Burden VA STA
41 Thermal rating factor STA
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 7 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 FEEDER CIRCUIT BREAKER DATA (for each rating)
7 General
8 Manufacturer name STA
9 Circuit breaker application Feeder
10 Number of feeder circuit breakers No. See schedule in page 13
11 Nominal voltage kV 11
12 Rated operational current A See schedule in page 13
13 Interrupting medium Vacuum
14 Number of poles Three
15 Closing mechanism Motor wound spring with 110V d.c release coil
16 Panel type Modular / Withdrawable
17 Rated short time withstand current and time kA (rms) 16 kA for 3 sec
18 Rated peak withstand current kA (peak) 40
19 Rated short circuit breaking current kA STA
20 Rated short circuit making current kA STA
21 Rated DC component of short circuit breaking current % STA
22 Rated insulation voltage kV STA
23 Rated impulse voltage withstand (Up) kV (peak) 60
24 Rated power frequency withstand voltage (1 min) (Ud) kV (rms) 28
25 Breaker breaking time secs STA
26 Breaker closing time secs STA
27 Maximum panel power dissipation W STA
28 ESD trip (Note 9) Yes/No Yes
29 Load shedding trip Yes/No No
30 Overall dimensions of the panel: (L x W x H) mm STA
31 Gland plate Steel, un-drilled
32 Auxiliary voltages
33 Control and protection supply V 110V d.c (External)
34 CB spring charger motor supply V 230V a.c (External)
35 Heating supply V 230V a.c (External)
36 Panel control and indication
37 "Closed" indication (Red) Yes/No Yes
38 "Open" indication (Green) Yes/No Yes
39 'Trip'' indication (Yellow) Yes/No Yes
40 'Trip Circuit Healthy'' indication (White), where applicable Yes/No Yes
41 Anti-condensation heater 'ON' indication Yes/No Yes
42 Ammeter c/w selector switch Yes/No Yes
43 Running hour counter Yes/No No
44 Control circuit supervision Yes/No No
45 Metering functions and alarm status Yes/No Yes
46 Remote "open" & "close" functional inputs Volt Free Yes/No Yes
47 Protection requirements
48 25 Synchronisation check relay Yes/No Yes
49 27 Undervoltage relay Yes/No No
50 50, 51 IDMT + Instantaneous Over current Yes/No Yes
51 50N/51N IDMT + Instantaneous Earth fault Yes/No Yes
52 51G Back-up earth fault Yes/No No
53 86 Lockout relay Yes/No Yes
54 87 Differential protection Yes/No No
55 74TC Trip circuit supervision relay Yes/No Yes
56 Cable fault impedance relay Yes/No Yes
57
58 Communications
59 Communications with ICMS/DCS: Protocol STA
60 DCS control inputs Yes/No No
61 ICMS/DCS status outputs Yes/No Yes
62 Redundant Yes/No No
63
64
65
66
67
68
69
70
71
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 8 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 FEEDER CIRCUIT BREAKER DATA (for each rating)
7 11kV Cable earth switch
8 Integral earth switch required Yes/No Yes
9 Rated short time withstand current kA (rms) As per Switchgear
10 Rated short circuit making current kA (peak) As per Switchgear
11 Rated duration of short circuit sec As per Switchgear
12 Interlock Yes/No Yes. Integral to Circuit Breaker
13 11kV power cables
14 Type of cable Cu/XLPE/SWA/PVC
15 Voltage grade kV 6 / 10 (12)
16 No. of cables and minimum conductor size mm² See schedule in page 11
17 Cable entry Top/Bottom Bottom
18 Facility for HV cable screen earthing Yes/No Yes
19 Armour earthed via the cable gland Yes/No Yes
20 Auxiliary circuit LV cables
21 Motor anti-condensation heater cable size up to 3kW N/A
22 Motor anti-condensation heater cable size above 3kW N/A
2
23 RCU control cable Yes - 7c 2.5mm
24 UCP control cable (if applicable) Yes - 7c 2.5mm2
25 Voltage transformers
26 No. of secondaries No. STA
27 Ratio STA
28 Accuracy class STA
29 VA Rating VA STA
30 Protection current transformers
31 No. of cores No. 3
32 Ratio xxx/1A See schedule in page 11
33 Accuracy class 5P
34 Burden VA STA
35 Thermal rating factor STA
36 Measurement current transformers
37 No. of cores No. 3
38 Ratio xxx/1A See schedule in page 11
39 Accuracy class 5P
40 Burden VA STA
41 Thermal rating factor STA
42 Core balance transformers
43 Ratio xxx/1A See schedule in page 11
44 Accuracy class 5P
45 Burden VA STA
46 Thermal rating factor STA
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 9 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 FEEDER FUSED CONTACTOR DATA (for each rating)
7 General
8 Manufacturer name STA
9 Number of fused contactors No. See schedule in page 13
10 Panel type Modular / Withdrawable
11 Rated operational current A See schedule in page 13
12 Nominal voltage kV 11
13 Rated short time withstand current and time kA (rms) 16 kA for 3 sec
14 Rated peak withstand current kA (peak) 40
15 Rated short circuit breaking current kA STA
16 Rated DC component of short circuit breaking current % STA
17 Overall dimensions of the panel: (L x W x H) mm STA
18 Gland plate Steel, un-drilled
19 Insulation levels:
20 Rated impulse voltage withstand (Up) kV (peak) 60
21 Rated power frequency withstand voltage (1 min) (Ud) kV (rms) 28
22 Fused contactor :
23 Auxiliary voltage V 230V a.c.
24 Mechanical endurance No. Of ≥ 1 million
25 Electrical endurance Operations STA
26 Mechanical operation counter Yes/No No
27 Closed/open position indication Yes/No Yes
28 ESD Trip (Note 11) Yes/No Yes
29 Load shedding trip Yes/No No
30 Utilisation category Note 5
31 Rated duty Continuous/intermittent Class 1
32 Contactor type Mechanically Latched type
33 Co-ordination N/A
34 Largest fuse allowable A STA
35 Rated making capacity A STA
36 Rated breaking capacity A STA
37 Maximum power dissipation W STA
38 Maximum cut-off current of contactor A STA
39 Fuse initiated opening time secs STA
40 Release initiated opening time secs STA
41 Auxiliary voltages
42 Control supply: Voltage V 110V d.c (Integral)
43 Power VA STA
44 Trip coil (where applicable): Voltage V 110V d.c (External) + Mechanical Release
45 Power VA STA
46 Supply for heaters V 230V a.c
47 Internal control VT Ratio/connection N/A
48 VA rating N/A
49 Class N/A
50 Panel control and indication
51 "Closed" indication (Red) Yes/No Yes
52 "Open" indication (Green) Yes/No Yes
53 'Trip'' or Blown Fuse indication (Yellow) Yes/No Yes
54 'Trip Circuit Healthy'' indication (White), where applicable Yes/No Yes
55 Anti-condensation heater 'ON' indication Yes/No Yes
56 Ammeter c/w selector switch Yes/No Yes
57 Running Hour Counter Yes/No No
58 Control circuit supervision Yes/No No
59 Metering functions and alarm status Yes/No Yes
60 Remote "open" & "close" functional Inputs Volt Free Yes/No Yes
61 Protection requirements
62 Overload Yes/No Yes
63 Phase unbalance Yes/No No
64 Motor stall Yes/No No
65 Under voltage Yes/No No
66 Start limits Yes/No No
67 Earth fault Yes/No Yes
68 Over temperature - RTD Yes/No No
69 Undervoltage restarting provision Yes/No No
70 Transformer winding temperature alarm / trip Yes/No Yes
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 10 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 FEEDER FUSED CONTACTOR DATA (for each rating)
7 Communications
8 Communications with ICMS/DCS: Protocol STA
9 DCS control inputs Yes/No No
10 ICMS/DCS status outputs Yes/No Yes
11 Redundant Yes/No No
12 11kV power cables
13 Type of cable Cu/XLPE/SWA/PVC
14 Voltage grade kV 6/10 (12)
15 No. of cables and minimum conductor size mm² See schedule in page 11
16 Cable entry Top/Bottom Bottom
17 Facility for HV cable screen earthing Yes/No Yes
18 Armour earthed via the cable gland Yes/No Yes
19 11kV cable earth switch
20 Rated short time withstand current kA (rms) As per Switchgear
21 Rated short circuit making current kA (peak) As per Switchgear
22 Rated duration of short circuit sec As per Switchgear
23 Auxiliary circuit LV cables
24 Motor anti-condensation heater cable size up to 3kW N/A
25 Motor anti-condensation heater cable size above 3kW N/A
26 RCU control cable Yes - 7c 2.5mm2
27 UCP control cable (if applicable) Yes - 7c 2.5mm2
28 Protection current transformers
29 No. of cores No. 3
30 Ratio xxx/1A See schedule in page 11
31 Accuracy class 5P
32 Burden VA STA
33 Thermal rating factor STA
34 Measurement current transformers
35 No. of cores No. 3
36 Ratio xxx/1A See schedule in page 11
37 Accuracy class Class 1 (minimum)
38 Burden VA STA
39 Thermal rating factor STA
40 Core balance transformers
41 Ratio xxx/1A See schedule in page 11
42 Accuracy class 5P
43 Burden VA STA
44 Thermal rating factor STA
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 11 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 BUS TIE CIRCUIT BREAKER DATA (for each rating)
7 General
8 Manufacturer name STA
9 Circuit breaker application Bus Tie
10 Number of bus-tie circuit breakers No. 1 (One)
11 Nominal voltage kV 11
12 Rated operational current A See schedule in page 13
13 Interrupting medium Vacuum
14 Number of poles Three
15 Closing mechanism Motor wound spring with 110V d.c release coil
16 Panel type Modular/Withdrawable
17 Rated short time withstand current and time kA (rms) 16 kA for 3 sec
18 Rated peak withstand current kA (peak) 40
19 Rated short circuit breaking current kA STA
20 Rated short circuit making current kA STA
21 Rated DC component of short circuit breaking current % STA
22 Rated insulation voltage kV STA
23 Rated impulse voltage withstand (Up) kV (peak) 60
24 Rated power frequency withstand voltage (1 min) (Ud) kV (rms) 28
25 Breaker breaking time secs STA
26 Breaker closing time secs STA
27 Maximum panel power dissipation W STA
28 ESD trip (Note 9) Yes/No No
29 Load shedding trip Yes/No No
30 Overall dimensions of the panel: (L x W x H) mm STA
31 Gland plate Steel, un-drilled
32 Auxiliary voltages
33 Control and protection supply V 110V d.c (External)
34 CB spring charger motor supply V 230V a.c (External)
35 Heating supply V 230V a.c (External)
36 Panel control and indication
37 "Closed" indication (Red) Yes/No Yes
38 "Open" indication (Green) Yes/No Yes
39 'Trip'' indication (Yellow) Yes/No Yes
40 'Trip Circuit Healthy'' indication (White), where applicable Yes/No Yes
41 Anti-condensation heater 'ON' indication Yes/No Yes
42 Ammeter c/w selector switch Yes/No No
43 Running hour counter Yes/No No
44 Control circuit supervision Yes/No No
45 Metering functions and alarm status Yes/No Yes
46 Remote "open" & "close" functional inputs Volt Free Yes/No Yes
47 Protection requirements
48 25 Synchronisation check relay Yes/No Yes
49 27 Undervoltage relay Yes/No No
50 50 IDMT Over current Yes/No Yes
51 51N IDMT Earth fault Yes/No No
52 51G Back-up earth fault Yes/No No
53 86 Lockout relay Yes/No No
54 87 Differential protection Yes/No No
55 74TC Trip circuit supervision relay Yes/No Yes
56 Communications
57 Communications with ICMS/DCS: Protocol STA
58 DCS control inputs Yes/No No
59 ICMS/DCS status outputs Yes/No Yes
60 Redundant Yes/No No
61
62
63
64
65
66
67
68
69
70
71
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply Revision: 0
11 kV Switchgear Page 12 of 13
00100W-C-PG-PP03-EL-DAS-0008

HV SWITCHGEAR DATA SHEET


1 Tag no. TBA Client: BP RUMAILA
2 No. of Units: One (1) Plant Location: Rumaila, Iraq
3 Service Description: HV Power Distribution Manufacturer: STA
4 Ref Specification: 00100W-C-G0-G000-EL-SPC-0002 Purchase Order No. : TBA
5 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
6 BUS TIE CIRCUIT BREAKER DATA (for each rating)
7 Auxiliary circuit LV cables
8 Motor anti-condensation heater cable size up to 3kW N/A
9 Motor anti-condensation heater cable size above 3kW N/A
10 RCU control cable Yes - 7c 2.5mm2
11 UCP control cable (if applicable) Yes - 7c 2.5mm2
12 Voltage transformer
13 No. of secondaries No. STA
14 Ratio STA
15 Accuracy class STA
16 VA Rating VA STA
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Rumaila Project
(FEED) Date: 10-Jan-13
Data Sheet for Medium Term Power Supply
Revision: 0
11 kV Switchgear
00100W-C-PG-PP03-EL-DAS-0008 Page: 13 of 13

HV Switchgear - TYPICAL ARRANGEMENT


1 Panel Identification Number L8 L7 L6 L5 L4 L3 L2 L1 Bus-Tie R1 R2 R3 R4 R5 R6 R7 R8 R9

Harmonic Filter Feeder

Harmonic Filter Feeder


Generator Incomer A

Generator Incomer B

Generator Incomer C

Generator Incomer D

Transformer Feeder
RMU Feeder Spare

RMU Feeder Spare


RMU Feeder

RMU Feeder

RMU Feeder

RMU Feeder

RMU Feeder

RMU Feeder

RMU Feeder

RMU Feeder
Bus-Tie
Circuit Description

2 Type of switching device VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB FVC VCB VCB
3 Rated current of switching device (A) 400 TBA 400 400 400 400 200 200 630 200 200 400 400 400 400 100 TBA 400
4 Voltage transformers
5 No. of secondaries N/A N/A N/A N/A N/A N/A STA STA STA STA STA N/A N/A N/A N/A N/A N/A N/A
6 Ratio N/A N/A N/A N/A N/A N/A STA STA STA STA STA N/A N/A N/A N/A N/A N/A N/A
7 Accuracy class N/A N/A N/A N/A N/A N/A STA STA STA STA STA N/A N/A N/A N/A N/A N/A N/A
8 VA Rating N/A N/A N/A N/A N/A N/A STA STA STA STA STA N/A N/A N/A N/A N/A N/A N/A
9 Protection current transformers
10 No. of cores 3 3 3 3 3 3 3 3 N/A 3 3 3 3 3 3 3 3 3
11 Ratio STA STA STA STA STA STA STA STA N/A STA STA STA STA STA STA STA STA STA
12 Accuracy class 5P 5P 5P 5P 5P 5P 5P 5P N/A 5P 5P 5P 5P 5P 5P 5P 5P 5P
13 Burden STA STA STA STA STA STA STA STA N/A STA STA STA STA STA STA STA STA STA
14 Thermal Rating Factor STA STA STA STA STA STA STA STA N/A STA STA STA STA STA STA STA STA STA
15 Measurement current transformers
16 No. of cores 3 3 3 3 3 3 3 3 N/A 3 3 3 3 3 3 3 3 3
17 Ratio STA STA STA STA STA STA STA STA N/A STA STA STA STA STA STA STA STA STA
18 Accuracy class Class 1 Class 1 Class 1 Class 1 Class 1 Class 1 Class 1 Class 1 N/A Class 1 Class 1 Class 1 Class 1 Class 1 Class 1 Class 1 Class 1 Class 1
19 Burden STA STA STA STA STA STA STA STA N/A STA STA STA STA STA STA STA STA STA
20 Thermal Rating Factor STA STA STA STA STA STA STA STA N/A STA STA STA STA STA STA STA STA STA
21 Core balance transformers
22 Ratio STA STA STA STA STA STA N/A N/A N/A N/A N/A STA STA STA STA STA STA STA
23 Accuracy class 5P 5P 5P 5P 5P 5P N/A N/A N/A N/A N/A 5P 5P 5P 5P 5P 5P 5P
24 Burden STA STA STA STA STA STA N/A N/A N/A N/A N/A STA STA STA STA STA STA STA
25 Thermal Rating Factor STA STA STA STA STA STA N/A N/A N/A N/A N/A STA STA STA STA STA STA STA
26 11kV Power Cables
27 No. of cables and conductor size TBA TBA 1x3x240 1x3x240 1x3x240 1x3x240 1x3x120 1x3x120 TBA 1x3x120 1x3x120 1x3x240 1x3x240 1x3x240 1x3x240 1x3x50 TBA TBA
28
29 RMU: Ring Main Uint
30 VCB: Vacuum Circuit Breaker
31 FVC: Fused Vacuum Contactor
32 N/A = Not Applicable
33
34 No. of Spare Motor/Transformer Feeders TBA
35