PROJECT NO.

& TITLE 2502323 – FEED for NAG LTFD Phase II

TP DOCUMENT NO. TP-CGDF-80133-DAS-A4

DOCUMENT TITLE DATASHEET FOR DG PACKAGE

CONTRACT NUMBER SA-080-2015

CONTRACTOR DOC. NO. TP-CGDF-80133-DAS-A4

CONTRACTOR DOC. REV. A0

ISSUED FOR REVIEW IFR X TATWEER PETROLEUM REVIEW STAMP

ISSUED FOR DESIGN IFD 1. APPROVED TO PROCEED


(Submit Final Document)

ISSUED FOR CONSTRUCTION IFC 2. APPROVED TO PROCEED AS NOTED


(Revise and Submit Final Document)

ISSUED FOR INFORMATION IFI 3. NOT APPROVED


(Revise and Re-Submit for Approval)

AS-BUILT ASB 4. FOR INFORMATION ONLY

FINAL/HANDOVER DOSSIER HDD 5. AS-BUILT


(After FAT as Applicable)
CANCELLED CAN 6. CANCELLED
Acceptance in any of these categories in no way relieves the contractor / supplier of its responsibility to the due
and proper performance of the works in accordance with the contract / purchase order.
Reviewe
Signature Date
r Name

A0 MAY 30,2018 ISSUED FOR REVIEW DC SMS SR


REV DATE DESCRIPTION PREPARED CHECKED APPROVED
FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 2 of 9

REVISION DESCRIPTION SHEET

Rev. Para. Revision Description

A0 - Issued for Review

Hold No. Para. Description of Hold


FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 3 of 9

DATA SHEET FOR MOBILE DIESEL GENERATORS


General
01
Item No: CGDF-UPS-05, CGDF-UPS-07 Manufacturer: *
Application: Emergency Diesel Generator Country of Origin: *
Package
No. Required : 03 Model: *
Applicable to: ■ Proposals □ Purchase □ As built

Applicable Codes and Standards


02
Project Specification TP-CGDF-80131-SPC-A4
Site Condition
03
Site Location: □ Indoor ■ Outdoor

Altitude <1000 ft.


Ambient temperature: Max.: 55° C Min. : -5° C
Relative humidity Min 75% Max 98%

Tropicalizing required: No
Area Classification Safe area
System Details
04
Generator Rating (Note 1) 1250 kVA (415 V AC Generator)
Rated Speed *
Load Type: Continuous

ISO rating (ISO 3046) *


Direction of rotation (cw/ccw) *
Loading time *
Max. power at Site Condition *
Rated LV Voltage 415 +/- 10%
Rated Frequency 50 Hz +/- 2%
No. of Phases / Wires 3 Phase / 4 Wire

LV fault level ** kA
FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 4 of 9

System Grounding Neutral solidly earthed

05 Diesel Engine
Manufacturer *
Continuous Net Power, kW *
Direction of rotation from coupling end *
Cycles 4 Stroke
Number of Cylinders *
Stroke, mm *
Bore, mm *
Piston displacement, litres *
Compression Ratio *
Rated Speed, rpm *
Piston Speed, m/s *
Overload Rating 110 % for one hour
Fuel Rate @ 100% load, g/kWh *
Fuel Rate @ 75% load, g/kWh *
Fuel Rate @ 50% load, g/kWh *
Engine Lube Oil Capacity, litre *
Inlet Air Temperature *
Exhaust Temperature *
Engine Efficiency, % *
Engine Governor Type Electronic
Noise Level @ 1 Meter distance ≤85dBA

Starting Batteries
Manufacturer *
Country of Origin *
Design / Manufacturing Standard *
Type Ni Cd
Capacity, A/H *
No of consecutive starts 3 cold starts for 10 seconds each
FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 5 of 9

Number of Battery / Charger 2 set / 2 charger


Nominal Voltage *
No. of Cells *
Type of Mounting *
Dimension of Batteries *

Coupling
Type Metallic Flexible
Coupling Guard Non Sparking

Air Intake and Exhaust System


Air Filter Type *
Exhaust Bellows Required
Exhaust Pipe Size (dia & length) *
Silencer Required
Flame / Spark Arrestor Required
Engine Cooling system
Closed Loop Yes (water)
Cooling Water Pump Shaft driven
Jacket Water Heater If required
Make-up Tank required

Fuel Oil System


Fuel Diesel
Day Tank Separate (Note-10)
Day Tank Capacity (for 24 hours running) *
Fuel Supply/Injection Pumps Shaft driven pump (Note-11)
Tank Material Carbon Steel (with external / internal
painting)
Filter Duplex filter

Lube Oil System


FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 6 of 9

Filter Duplex filter with cartridge type


Lube Oil Heater If required
Crank Case Breather Required

06 Generator
Manufacturer *
AC Generator 1250 kVA
AC Generator Type 3-phase synchronous type
Speed 1500 rpm
Voltage 415 V

Frequency 50 Hz
Number of Phase 3 phase
Maximum voltage recovery time *
Total Harmonic Distortion (THD) of the < 5 %
supply network voltage
Power Factor: 0.8
Max. Fault contribution by Generator *
No. of Stator Winding Terminals *

Operation Stand alone


Mounting Covered / Enclosed, skid mounted
Sustain Overload *

Winding Conductor Material *


Winding Connection *
Generator AVR, Metering, Controls & As per Specifications
Protections
Efficiency @ 100% rated output *
Efficiency @ 75% rated output *
Efficiency @ 50% rated output *
Efficiency @ 25% rated output *

Generator Performance – Max. Voltage * %


drop for sudden load application
FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 7 of 9

Total starting time to accept load * Sec


Generator Protection Degree: IP55
Insulation Class F

Cooling Medium Air


Anti-condensation Heater Required
Terminal Box Protection Degree IP55

Control Panel Protection Degree IP55 (external housing)


Control Panel Protection Degree IP41 (inside the board)
Cable terminal box Required

07 Exciter
Manufacturer *

Exciter type Brushless, Self-excited


Output, kW *

08 Automatic Voltage Regulator


Manufacturer *
Model Number *

Output, kW *
Response Time *
Voltage Variation *

Rated Current, Amps *


Rated Voltage, Volts *

09 Overall Package Weight & Dimension


Gross Weight *
Length, mm *

Width, mm *
Height, mm *
FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 8 of 9

10 Inspection and Testing


Stage Inspection during Manufacture Witness
Full Load Test at Engine Manufacturer's Witness
Shop
Fuel consumption & Governing Test at Witness
Engine Manufacturer's Shop
Control Panel Functional Test at LP Witness
vendor's shop
Full Load Test for 4 hours of Engine- Witness
Generator set with all auxiliaries & 1hr @
110% load
No load Mechanical Run test at Witness
Packager's/Driven Eqpt. Mfr. Shop
Noise level test Witness
Vibration test Witness

11 Devices Attached
Rating Plate

Terminal Marking Plate


Coupling between Engine & Alternator
Anti-Vibration Pads
Engine & Generator Control Panels

Earthing Boses (2 Nos)


Lifting Hooks
Warning Plates
Cable Glands

Winding Temperature Detector


Bearing Temperature Detector
Anti-Condensation Heater

Package Enclosure
Acoustic Enclosure
FEED FOR NAG LTFD PHASE II

Datasheet for DG Package


Contract No: SA-080-2015 Date: MAY 30, 2018
TP-CGDF-80133-DAS-A4 Rev. A0
CTR#: CTR#13 Page 9 of 9

First fill of Lubrications


Commissioning & start-up spares
Three years operational spares

Special Tools & Tackles

Notes:
1. Generators ratings shall be in line with final Electrical Load list. Rating shall be
updated during detailed engineering stage based on approved load list of EPC stage.
2. All Generators shall be an enclosed skid mounted package unit.
3. All day tanks shall be in separate skids.
4. Vendor to consider commissioning & start-up spares, three years operational spares &
special tools in their scope of supply.
5. Vendor shall provide auxiliary electrical equipment load list along with all sizing
calculation for review.
6. Noise level shall not exceed 85 dBA @ 1.0 meter distance from the equipment surface.
Vendor shall furnish the noise data for the overall package. Acoustic Enclosure shall be
considered by Vendor.
7. Vendor shall provide the minimum load rate of continuous operation, description the
operating conditions and efficiency under different load rate, provide the diesel
generator efficiency chart and table at different temperature.
8. Generator will be painted in accordance to the project painting specification,
Appendix 4 of TP-MISC-80065-RPT-A4 and shall be suitable for the specified ambient
condition.
9. Vendor shall provide the actual output power change chart and table of diesel
generator at different temperatures, altitude conditions.
10. Day tank shall be designed as per code UL 142 and include Fuel filter, Breather/vent
with flame/spark arrestor, Fuel level indicator, Inspection hatch, Supply and return
connections to the engine fuel system, Inlet connection for filling, Level gauge, High /
Low level switches and drain connection with valve as a minimum.
11. Fuel supply and fuel injection pumps shall be shaft driven and Vendor to supply the
detailed data sheet.
12. For details of I/O interfaces, Specification for LV switchgear doc.no. TP-CGDF-80979-
SPC-A4 and Datasheet for 415V switchgear doc no. TP-CGDF-80528-DAS-A4 shall
be referred.