TABLE OF CONTENTS
7.5 Wind.............................................................................................................................. 11
13.2 Testing.......................................................................................................................... 24
20.2 Testing.......................................................................................................................... 28
1.0 INTRODUCTION
2.0 PURPOSE
This specification together with the referenced documents defines the minimum
requirement for design, manufacture and testing of industrial type diesel generator
package having self-excited Power Generator driven by diesel engine complete with
Generator Control Panel and associated accessories in an skid mounted enclosure, as
specified in Data Sheet, inside CGDF facility.
This specification also specifies requirements in addition to international standards, as
required for plants and facilities designed/constructed.
3.0 DEFINITIONS
4.0 ABBREVIATIONS
AC Alternating Current
AVR Automatic Voltage Regulator
DC Direct Current
EMC Electromagnetic Compatibility
ECV End Cell Voltage
FATP Factory Acceptance Test Procedure
IEC International Electro Technical Commission
IP Ingress Protection
ITP Inspection and Test Plan
UPS Uninterrupted Power Supply
Equipment covered by this specification shall comply with the latest revision of project
specifications, and current revision (at the time of placement of order, unless
otherwise specified) of the codes and standards listed below. Project specification for
Painting & Coating prepared under EPC Phase#1 project shall be followed as listed
below;
The codes and standards referenced above are supplemented by this specification
which states requirements in addition to, or deviating from, those specified in the
codes and standards.
FEED FOR NAG LTFD PHASE II
This specification shall be read in conjunction with all other specifications and data
sheets.
The COMPANY Project Specifications shall be used in conjunction with this design
basis wherever applicable and mentioned hereafter in the respective discipline
section.
• Data sheets
• FEED Specifications.
• Company Specifications/Documents/Procedures.
The SUPPLIER shall list down, if any, all the deviations to the specifications, codes
and standards. Unless any deviations are identified and accepted by the
PURCHASER during bid stage, the SUPPLIER shall be deemed to have confirmed to
comply with all the listed specifications, codes and standards.
7.1 Temperature
TEMPERATURE 0F(0C) APRIL-OCT. OCT.-APRIL
Mean Daily Maximum 115 (46.1) 98.6(37)
Mean Daily Minimum 80(26.6) 61.0(16.1)
7.2 Humidity
• Mean Daily Maximum (Sept./Oct.) : 98%
• Mean Daily Minimum (June) : 75%
7.3 Solar
Design mid-day solar flux for horizontal flat surface, average : 300 Btu/hr/ft2
7.4 Rainfall
• Average rainfall/year : 2.26 inches
7.5 Wind
• Prevailing direction : Predominately from NW or
NNW throughout the year.
7.6 Climate
This is a desert climate and the equipment must be designed for sandstorms and
dust. Lightning must be considered in the design.
FEED FOR NAG LTFD PHASE II
Seismic loading is generally not applicable for this project. However, seismic criteria
given in table below has to be considered by the vendors for the design of major /
critical items of CGDF such as Air cooler, GDU (including Absorber Vessel), Flare
Package, Inlet Separator, Vessels etc., as a sensitive case and design calculation
shall be submitted to CONTRACTOR / COMPANY.
8.4 Training
SUPPLIER shall quote per diem rate (or lump sum as specified) for training services on
the Equipment/System to PURCHASER’s personnel.
Three nos. of Emergency diesel generators are envisaged for CGDF area. Each train
shall have independent dedicated diesel engine generator package. Train-1 is under
EPC stage and 415V switchgear is already designed with provision of a spare future
incomer. For Train-2 and Train-3, 415V switchgear shall be designed to receive DG set
incomer as well apart from two incomers from transformer.
The Diesel generators, in general, shall be suitable for continuous operation under the
service conditions specified in the datasheet for mobile diesel generator.
Electrical equipment shall be located in a manner that facilities easy access for routine
operation and maintenance.
Reliability of generator to perform continuously in the service conditions specified is
essential.
10.1 General
The Equipment shall be designed, manufactured, tested and supplied in accordance
with the requirements in the enquiry document taking due account of preservation and
transportation requirements.
The design life of the package shall be 25 years.
The generator packages (415 V AC generators) shall be suitable for a trouble-free
normal operation. Unless otherwise specified, the generator shall be 3 phase
synchronous type and suitable for coupling to the engine on a single baseplate. The
FEED FOR NAG LTFD PHASE II
equipment and skid components shall be laid out to ensure good and safe operability
survey and maintenance access taking into account any requirements of health, safety,
environment, and ergonomics.
The generator package shall be furnished as a skid mounted unit consisting of
generator, engine drive and auxiliary systems, assembled on a prefabricated steel skid
and equipped with a suitable number of lifting points.
All equipment, instrumentation, and valves shall be easy accessible, so that calibration
activities, maintenance, and operation can be made without any temporary platform or
ladder.
The skid shall be supplied with two earthing bosses located at diagonally opposite
locations.
All skids wiring for external connections shall terminate, where appropriate, in terminal
boxes.
Each Mobile Diesel Generator Package shall include, but not limited to the following:
• Diesel Engine
• Generator
• Engine /Generator Coupling
• Engine Starting System including batteries, charger etc
• Lubrication System
• Cooling System
• Diesel Fuel System
• Fuel Day Tank including fuel supply and return connection to the engine fuel
system, inlet connection for fuel filling, level gauge, overflow tube, drain
connection with valve etc.
• Air Inlet System
• Exhaust System including silencer, duct and flame arrestor
• Engine Speed Control
• Synchronizing Controls
• Automatic Voltage Regulator
• Control Panel, local instruments, GBs, level instruments for alarm/shutdown.
• Necessary interconnecting piping, valves etc
• First fill of lubricants
• Commissioning and Start-up spares
• Three Years Operational Spares
• Special tools
Engine shall have a site condition continuous power rating of not less than 110% of the
maximum power demand at rated speed after deducting internal power losses.
Engines shall be provided with a governor capable of regulating engine speed.
Engine cylinders shall be provided with removable liners.
Guards shall be provided to protect personnel against exposed engine rotating parts
such as the coupling, fan and any other exposed hot or rotating parts.
Engine speed shall be governed in accordance with ISO 3046-4. Oil reservoir, housings
enclosing moving parts and shaft seal parts shall be designed to prevent the ingress of
dust and moisture during operation and periods of idleness.
Engine shall be supplied with a complete fuel oil system including but not be limited to
suction strainer, shaft driven fuel supply and fuel injection pumps, pressure relief valve,
fuel day tank etc.
An engine over speed device shall be provided in accordance with ISO 3046-6. This
over speed device shall shutdown the engine by shutting off the fuel and combustion air
intake independently of the speed governor.
Automatic shutdown system shall be provided to stop the diesel generator in the event
of engine low oil pressure, fuel oil level low, high oil temperature, high water
temperature & engine over speed. A manual reset facility shall be provided at the
control panel.
Provision shall be made for manual emergency shutdown on the generator control
panel.
Appropriate rerating to the diesel engine performance ratings shall be made for the
combination of the highest expected air temperature, highest humidity & lowest
atmospheric pressure.
Engine Starting System
Diesel engine shall not require any preparation for start-up and shall be capable of
immediate start up to rated duty.
Engine starting shall be electric starter motor powered by battery systems.
The starting system shall have a capacity for 3 consecutive cold starts for 10 seconds
each. Batteries shall be minimum maintenance sealed Ni-Cd type.
The charger shall keep the battery fully charged during standby periods.
Two sets of batteries (2x100%) shall be provided for diesel engines intended for electric
starting. Each battery set shall be provided with independent battery charger units.
Batteries shall be of ultra-low maintenance Ni-Cd type requiring no topping up of
electrolyte under normal operation.
Plastic cell container material shall be non-flame propagating, mechanically shock
resistant and translucent, to give a visual indication of electrolyte level.
Fuel Day Tank
The fuel day tank shall supply fuel for 24 hours minimum continuous operation at rated
power.
FEED FOR NAG LTFD PHASE II
10.3 Generator
The rated output of the DG set in kVA shall be as specified in the datasheet. The rating
shall be based on continuous S1 duty and shall be considered as the base continuous
rating of the Generator
The power required shall be delivered from the diesel engine electrical generating
system in continuous service operation, net of all the auxiliaries consumption of the unit
itself and according to the conditions laid down in the specifications and in the
applicable regulations.
The rated output voltage, frequency and power factor of the electric loads will be as
specified in the relevant datasheets.
The MANUFACTURER shall specify conditions and power of short overloading.
Under fully loaded conditions, the generator shall be capable of withstanding the
following, while maintaining the output voltage and frequency within acceptable limits:
Momentary over current of 150% rated full load current for a period of 15s. Sustained
overload of 110% of the rated power for a period of one hour.
The generator shall withstand an over speed of 120% rated for two minutes without any
damage.
Generators shall have a rating suitable to supply the kVA demanded by the load without
overheating and the kVA demanded to start motors and other loads with low power
factor.
The generator shall be supplied complete with excitation and voltage regulating
systems including automatic power factor controller.
Unless otherwise specified the generator and its exciting system shall be capable of
producing and sustaining at least 3 times the rated current for the duration of at least
5 s when a three phase symmetrical short circuit occurs at generator terminals.
The temperature rise limitation for the alternator shall be as per IEC 60034 part 1 Table
6 with adjustments for site conditions as per Table 8.
The generator shall be 3-phase synchronous type for AC diesel generator.
The generator shall be designed for continuous running with a maximum rating
according to IEC 60034-1.
FEED FOR NAG LTFD PHASE II
Power capacity of mobile diesel generator shall be sufficient to boost quick charge of
batteries after the deep discharge with parallel supplying of current load during no more
than 8 hours.
Generator cooling shall be totally enclosed, fan cooled. Generator enclosure shall be
with minimum degree of protection to IP 55.
The generator and exciter insulation shall be equivalent to Class 'F', insulation limited to
Class B temperature rise at the specified design ambient.
The generator and exciter shall be capable of continuous uninterrupted operation at
rated output in the ambient conditions stated in clause 7.0.
The Vendor shall, state guaranteed values of efficiency for the alternator and exciter, at
50%, 75% and 100% of rated output at maximum design temperature with specified
tolerances.
The generator and exciter shall be capable of withstanding a 10% overload at rated
voltage, power factor and frequency for one hour without exceeding specified
temperature limits. The overload characteristic shall be as specified in IEC 60034-1.
The waveform of the alternator shall comply with the requirements specified in
IEC 60034-1, Section 11.
The automatic voltage regulator shall be of the static type and shall have a regulation and
stability respectively of 1 - 4 % and ± 0,5 %, high stability and an accuracy of regulation
(between no-load and full-load, 0,8 - 1,0 power factor load condition, cold to hot variation)
not less than 2 %.
The rotating parts of the generator and exciter shall be statically and dynamically
balanced and shall be tested at overspeed equivalent to the engine overspeed trip
setting.
All parts of the windings including the connections to the terminal boxes shall be
adequately braced and wedged to prevent any deformation of the coils and of the
connections during all conditions of service including system short circuits with full
automatic voltage regulator action.
All terminal boxes shall be suitable for terminating the specified type of cable and
should be IP 55 minimum.
Connections for heaters, for instruments, for temperature detectors and for protection
circuits, when provided, shall be brought out to individual terminal boxes separate from
the main terminal boxes.
Current and Voltage transformers shall be in accordance with IEC 60044.
Unless otherwise specified the electrical protective system will include:
• Overcurrent protection
• Earth fault protection
• Generator under voltage protection
• Overvoltage protection
• Thermal overload protection
• Reverse power protection
FEED FOR NAG LTFD PHASE II
10.4 Heaters
The alternator and/or terminal boxes shall be equipped with an anti-condensation
heater capable of excluding moisture at the levels of humidity indicated in the data
sheet. The heater shall be rated for operation from a single phase supply protected by a
miniature circuit breaker and controlled from the control panel.
Space heaters shall be positioned in such a way to avoid influence to the operation of
components.
Anti-condensation heaters shall not exceed or cause any part of the generator to
exceed the generator permitted temperature rise. If necessary, internal thermostats
shall be provided to meet this requirement.
AUTO MODE
On failure of both transformer incomers to 415V switchgear, Emergency diesel
generator shall automatically start to cater to entire switchgear load. On restoration of
normal power the Generator shall automatically synchronize to the mains supply. The
generator shall automatically transfer the load to the mains supply and shutdown after a
pre-set time.
MANUAL MODE
The Generator Package shall be capable of being started manually by means of a local
initiation. Also, it shall be possible to manually restore power upon normal supply
availability from any of the transformers. In the event of failure of normal power supply,
there shall be an under voltage alarm in Local Control Facility (respective LCF).
TEST MODE
In test mode starting of the Generator Package shall be manual. This mode shall be
used for engine exercising and test running operations.
A test facility shall be provided to simulate mains failure to ensure the integrity of control
circuits and Generator Package starting sequence. The loading of the Generator
(connections to the distribution board) shall be inhibited during this testing.
10.9 Earthing
The Vendor shall provide earth bonding conductors from the engine, generator and all
other skid mounted equipment to the baseplate.
At least two earthing bosses shall be provided at diagonally opposite points on the skid
by Vendor. All electrical equipment and metallic parts shall be earthed and connected
to those earthing bosses.
Engine, coupling & generator shall be so designed to ensure that complete installation
starts, operates and stops free from torsional vibration and oscillation.
Manufacturer shall be provided with an effective ISO 9001 quality system certificate
issued by an international certification organization.
Manufacturer shall operate Quality Management Systems (QMS) to ensure that the
requirements of this Specification are fully achieved.
Manufacturer shall demonstrate compliance by providing a copy of the accredited
certificate and a copy his quality manual.
Diesel generator set provided by manufacturer shall have successful product operation
achievements of similar dimension for at least 3 years under the same environment
conditions.
Manufacturer shall provide the reference list of the product and achievements in similar
projects in recent five years, including names and locations of users, time of supply of
product etc.
Manufacturer shall be fully responsible for design, manufacturing, supply, inspection
and trial operation of the diesel generator set to ensure that provided diesel generator
can meet international/industrial standards, codes and technical specification.
FEED FOR NAG LTFD PHASE II
Manufacturer shall design, select, manufacture and supply equipment and provide
after-sale services and technical support for them from the viewpoint of long period of
operation. Manufacturer shall also utilize the most appropriate technique at present to
ensure safe and reliable operation of equipment. The Vendor shall have certain
technical support capability of field installation, maintenance and inspection.
The Vendor shall provide compliance to this specification, if any “non-compliance” that
should be specified clearly in the bid. Vendor shall give the detailed technical data of
the provided products. If there is any objection to the requirements of the specification,
the reasons thereof shall be explained.
12.0 NAMEPLATE
Name plates shall be in SS-316 material, suitably engraved and permanently fixed. All
the inscriptions on the nameplate shall be in English Language.
FEED FOR NAG LTFD PHASE II
13.1 General
The Vendor shall submit a detailed Inspection and Test Plan (ITP) to EPC
CONTRACTOR/ EMPLOYER for review & approval. The ITP shall cover all the
inspections and tests carried out at the Vendor’s works as well as those carried out by
Sub-Vendors for all phases of manufacturing and in Site also (SAT).
Vendor shall provide prior notification, minimum two weeks to CONTRACTOR/
EMPLOYER before conducting any inspection or testing specified as Hold or
Witnessed in the approved ITP.
The Inspection and testing requirements shall comply, as a minimum, with referenced
specifications, data sheets and all the applicable codes & standards.
Equipment shall not be shipped before the acceptance or release note is issued by
CONTRACTOR/ EMPLOYER.
13.2 Testing
The testing shall be done as per the approved test procedure, data sheet for mobile
diesel generator complying with the requirements mentioned in the specifications/codes
and standards.
Generator Test
The tests shall be carried out for the generator and exciter, in accordance with the
requirements of IEC 60034.
The following test shall be carried out but not limited:
• Vibration test
• Noise test
• Over speed test
• Dielectric test
• Insulation resistance test before/after Dielectric test
• Phase sequence and direction of rotation test
• Test of auxiliary devices such as generator space heater etc.
• Engine test shall be as per ISO 3046
• Acceptance test
• Type test
• Special test
String Test
Before shipment of the generator package the following tests shall be carried out.
Diesel generator with all associate equipment like radiator, silencer, fans, control panel,
gauges etc.
A full load test shall be carried out for a period of 4 hours under the following conditions:
FEED FOR NAG LTFD PHASE II
13.3 Inspection
All individual equipment included in the package shall be subjected to inspection as per
the applicable specifications, codes & standards and approved Inspection and Test
Plan.
No surfaces of parts of equipment are to be painted until the inspection is completed.
EMPLOYER/ CONTRACTOR reserves the right to engage a third party inspection
agency to provide a quality control service for inspection and witnessing tests in
VENDOR’s workshops ensuring compliance with the requirements of the relevant
codes, standards and project specifications.
Vendor shall replace any equipment or material for free if it is rejected by EMPLOYER/
CONTRACTOR.
14.0 SURFACE PREPARATION AND PAINTING
The treatment and protection of metalwork shall include cleaning, degreasing, rust
resisting primers and paint finishes that provide effective protection against corrosion
under the specified climatic conditions. Painting shall be as per Appendix 4 of
TP-MISC-80065-RPT-A4 material selection report.
Vendor to recommended painting system. Same shall be subjected to approval of
COMPANY.
15.0 PERFORMANCE REQUIREMENTS
The Generator rated voltage and frequency shall be as indicated in the single-line
diagram / Data Sheet. The voltage waveform characteristics shall be sinusoidal and
shall comply with the requirements of IEC 60034.
The generator shall be designed for continuous running duty type S1 with a maximum
rating according to IEC 60034-1.
The generator shall be capable of starting and running independently of outside
supplies of electricity.
Total Harmonic Distortion (THD) of the supply network voltage shall not exceed 5%.
Vendor shall provide complete guarantee for the design, material selection and
performance of the equipment in accordance with the design condition given in the
datasheets, this specification, requisition, codes and standards.
Vendor shall be responsible for furnishing all data/drawings in proper form and quantity
as per Material Requisition. The Vendor shall also be responsible for the documentation
required from his sub-vendors.
All drawings and documents must be presented in the English language. The kind and
quantity of all documents shall be as specified in the Material Requisition.
19.0 QUALITY ASSURANCE
20.1 General
SUPPLIER shall submit a detailed written Inspection and Test Plan (ITP); Factory
Acceptance Test Procedure (FATP) in accordance with the Supplier Document
Requirements List (SDRL). ITP and FATP approved by PURCHASER shall be available
prior to commencement of tests.
FAT witness testing will take place only after all the latest relevant drawings, technical
specifications, certificates and completed data sheets have been submitted and
approved by the Purchaser.
The SUPPLIER shall complete all internal inspection and routine tests prior to inspection
by the Purchaser, to ensure that the witnessed testing is not prolonged by fault finding
and rectification. Faults or unsatisfactory operations that result in abortive witness tests
FEED FOR NAG LTFD PHASE II
shall be rectified at the expense of the SUPPLIER. Any expense incurred by the
PURCHASER resulting from abortive tests will be chargeable to SUPPLIER.
All test instruments shall be calibrated, and copy of calibration certificates should be
provided on request.
All parts and components shall be tested and certified, fully in accordance with the
referenced codes and standards.
20.2 Testing
The testing shall be done as per the approved test procedure, data sheet for mobile
diesel generator complying with the requirements mentioned in the specifications/codes
and standards.
Generator Test
The tests shall be carried out for the generator and exciter, in accordance with the
requirements of IEC 60034.
The following test shall be carried out but not limited:
• Vibration test
• Noise test
• Over speed test
• Dielectric test
• Insulation resistance test before/after Dielectric test
• Phase sequence and direction of rotation test
• Test of auxiliary devices such as generator space heater etc.
• Engine test shall be as per ISO 3046
• Acceptance test
• Type test
• Special test
String Test
Before shipment of the generator package the following tests shall be carried out.
Diesel generator with all associate equipment like radiator, silencer, fans, control panel,
gauges etc.
A full load test shall be carried out for a period of 4 hours under the following conditions:
- 30 minutes at 25% rated output.
- 30 minutes at 50% rated output
- Two hours at 100% rated output
- One hour at 110% rated output.
During the load test all engines and generator parameters are to be recorded. These
shall include but not be limited to:
FEED FOR NAG LTFD PHASE II
Name plates shall be in SS-316 material, suitably engraved and permanently fixed. All
the inscriptions on the nameplate shall be in English Language.
Warning label shall be provided in both English and Arabic language.
22.0 SURFACE PREPARATION & PAINTING REQUIREMENTS
Surface preparation, treatment, paint storage, painting and coating application shall be
done in accordance with the project specification TP-MISC-00068-SPC-A4.
MANUFACTURER’s standard painting procedure will be followed if it meets/exceeds the
project specification or in the absence of a project specification. The manufacturer’s
painting procedure shall be submitted for PURCHASER’s approval, as listed in the
SDRL.
FEED FOR NAG LTFD PHASE II
Final paint shade and thickness of coating for exterior and interior shall be as specified in
the data sheet.
23.0 PREPARATION FOR SHIPMENT
SUPPLIER shall comply with the project specification attached with the requisition
(during EPC phase).
24.0 DOCUMENTATION
SUPPLIER shall provide all documents with the number of copies and soft-files, as listed
in the SDRL attached with the requisition (during EPC phase).
25.0 PERFORMANCE GUARANTEE
SUPPLIER shall be fully responsible for all equipment supplied by him including bought
out items. All the equipment shall be fully guaranteed for performance, mechanical
design, workmanship and materials for a period of twelve (12) months after
commissioning or eighteen (18) months after shipping, whichever is earlier.
In the event that the equipment is rectified or replaced by the VENDOR under the
provisions of this article, the guarantee period shall be extended for a period of twelve
(12) months following the satisfactory completion of the rectification or replacement of
the equipment provided the combined guarantee period is more than twelve (12) months
after commissioning or eighteen (18) months after shipping.