You are on page 1of 7

Rumaila Project

(FEED) Date: 11-Jan-13


Data Sheet (Electrical) for Medium Term Power Supply
Revision: 0
11 kV Diesel Generator Package
00100W-C-DG-DN00-EL-DAS-0019 Page: 2 of 7

REVISION DESCRIPTION SHEET

Rev. Sheet/Section Reason for Revision

A Issued for Inter Discipline Check

B Issued for Client Review

C Issued for Enquiry

0 pg 3 - Note 10 Issued for Use

Hold No. Sheet/Section Description of Hold


Rumaila Project
(FEED) Date: 11-Jan-13
Data Sheet (Electrical) for Medium Term Power Supply Revision: 0
11 kV Diesel Generator Package Page 3 of 7
00100W-C-PG-PP03-EL-DAS-0004

NOTES AND ABBREVIATIONS


1
2
3 (1) For additional information refer the the following documents:
4 a. 00100W-C-G0-G000-EL-SPC-0019 - Electrical Requirements for Emergency Diesel Generators (FEED)
5 (All sections of this specification are applicable except for section 1.1 which refers to 400 V emergency generators)
6
7 b. 00100W-C-PG-PP03-EL-BOD-0001 - Basis of Design for 'Medium Term ESP Power Supplies'
8 (Only sections 3.2 and 5 are applicable)
9
10 (2) For environmental conditions, refer: BEDD 00100W-C-G0-G000-GE-BOD-0001
11
12 (3) Protective painting and coating shall be in accordance with 00100W-C-G0-G000-ML-SPC-0009.
13
14 (4) Generator FAT per IEC 60034 and complete package string test are required. Full String test is required only on the 1st generator set;
15 it shall include load rejection tests.
16
17 (5) Generator package SUPPLIER shall allow for the provision of Generator Paralleling Switchgear where individual generator units
18 shall be synchronised and connected to a common bus. Refer to 00100W-C-PG-PP03-EL-DAS-0007 for more information on the
19 requirements for 11 kV switchgear.
20
21 (6) Voltage restoration to +/- 2.5% within 10 secs and to +/- 3.0% within 1 sec.
22
23 (7) Frequency deviation not more than 5% returning to within 1% of rated frequency within 3 secs for the defined load conditions.
24
25 (8) As per Noise Control Philosophy 00100W-C-G0-G000-SR-PHL-0003
26
27 (9) Generator control and synchronisation panel shall be installed in generator package substation. Generator set monitoring and
28 protection system shall be provided by generator set manufacturer.
29
30 (10) The generator package shall be capable of supplying a total load of 5 MVA in an N + 1 configuration, with spare unit operating as a
31 spinning reserve at an ambient temperature of 55 degree C. The load is predominantly VSD (worst case 100% 12 pulse) driven ESPs.
32
33 (11) Generator Package SUPPLIER shall take into consideration 3rd, 5th and 7th order harmonics contribution from transformer and VSD.
34 Any heat rise inside the container before the air filters, radiator power requirements and any other genset auxiliary that affect the
35 the generator rating shall also be accounted for.
36
37 (12) Generator Package shall be capable of 'Black Start'. It shall be arranged such that control power will be available to the generator
38 package paralleling switchgear upon starting one generator set.
39
40 (13) Generators shall be NFPA 110 compliant for one-step load acceptance with the generator engine set at operating temperature.
41
42
43
44 Abbreviations:
45 PMG = Permanent Magnet Generator
46 STA = Supplier to Advise
47 TBA =To Be Advised
48 TBC =To Be Confirmed
49 N/A = Not Applicable
50 VSD = Variable Speed Drive
51 ESP = Electrical Submersible Pump
52 For other abbreviations, refer specification 00100W-C-G0-G000-PM-PRO-0001
53
54
55
Rumaila Project
(FEED) Date: 11-Jan-13

Data Sheet (Electrical) for Medium Term Power Supply Revision: 0


11 kV Diesel Generator Package Page: 4 of 7
00100W-C-PG-PP03-EL-DAS-0004

Equipment Data Sheet for Diesel Generators


1 Tag No. : TBA Client: BP Iraq NV
2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : N/A Purchase Order No. : TBA
5 No. of Units: 1 Package (up to 4 generator sets) Driver Type: Diesel Engine
6 Service Description: Medium Term Power Generator Driver Data Sheet No. : 00100W-C-PG-PP00-ME-DAS-0001
7 ENVIRONMENTAL CONDITIONS POWER SYSTEM
8 Location: Outdoor (Packaged) System Voltage: 11000 V  5%
9 Ambient air temp: Min: Note 2 Max: Note 2 System Frequency: 50 Hz  1%
10 Humidity: Note 2 Altitude: Note 2 Neutral Earthing: Resistance Earthed
11 Hazardous area classification: Safe Area
12 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
13 GENERATOR DATA
14 Manufacturer STA
15 Type & Model No. STA
16 Paint specification and colour See Note 3
17 Applicable Codes and Standards IEC
18 Rated Voltage V AC 11000
19 Rated Frequency Hz 50
20 Duty Type S1 (Continuous)
21 Max continuous rating at S1 duty (55 degree C) kW See Note 10
22 Power Factor (Lag/Lead) pf 0.8 (lag)
23 Stator Connection Star
24 Neutral Earthing Method Resistance Earthed (See Note 1b)
25 Phase rotation R-Y-B
26 System max. fault current (3-ph sym) kA rms 5 for 1 sec
27 Protection and Metering Drawing No. TBA
28 Rotation facing Drive End STA
29 Insulation Class F
30 Temperature rise B
31 Speed rpm STA
32 First critical / Synch speed rpm STA
33 X/R Ratio STA
34 Overload capability: 30 seconds 150%
35 1 hour 110%
36 Unbalanced load capability STA
37 Voltage/frequency variations to IEC 60034-1 Zone 'B'
38 Generator Efficiency: Full load % STA
39 75% load % STA
40 50% load % STA
41 Type of excitation PMG
42 Telephone Harmonic Factor (THF) STA
43 Suitable for parallel operation with the system Yes/No Yes (up to 4 identical units)
44 Winding temperature detectors (No. & type) 6 off RTDs
45 Winding type Form wound
46 Winding Pitch 0.72 - 0.82
47 Max noise level at no load dB(A) Note 8
48 Pole Pitch STA
49 Space heater for: Generator W STA
50 Control Panel W STA
51 Voltage VAC 230
52
Rumaila Project
(FEED) Date: 11-Jan-13

Data Sheet (Electrical) for Medium Term Power Supply Revision: 0


11 kV Diesel Generator Package Page: 5 of 7

00100W-C-PG-PP03-EL-DAS-0004

Equipment Data Sheet for Diesel Generators


1 Tag No. : TBA Client: BP Iraq NV
2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : N/A Purchase Order No. : TBA
5 No. of Units: 1 Package (up to 4 generator sets)
6 Service Description: Medium Term Power Generator
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
8 Direct Axis Reactances:
9 Synchronous (Xd) - Sat & Unsat % STA
10 Transient (X'd) % ≤ 18
11 Subtransient (X''d) % ≥ 12.5
12 Positive Sequence Resistance (R1) % STA
13 Negative Sequence Resistance (R2) % STA
14 Negative Sequence Reactance (X2) - Sat & Unsat % STA
15 Zero Sequence Resistance (R0) % STA
16 Zero Sequence Reactance (X0) % STA
17 Short Circuit Ratio (X/R) STA
18 Quadrature Axis Reactances:
19 Synchronous (Xq) % STA
20 Transient (X'q) % STA
21 Subtransient (X''q) % STA
22 Direct Axis Open Circuit Time Constants:
23 Transient (T'do) STA
24 Subtransient (T"do) STA
25 Direct Axis Short Circuit Time Constants:
26 Transient (T'ds) STA
27 Subtarnsient (T"ds) STA
28 Quadrature Axis Open Circuit Time Constants:
29 Transient (T'qo) STA
30 Subtransient (T"qo) STA
31 Quadrature Axis Short Circuit Time Constants:
32 Transient (T'qs) STA
33 Subtransient (T''qs) STA
34
35
36 PHYSICAL CHARACTERISTICS (Excluding Driver)
37 Package Dimensions (L X W X H) mm STA
38 Package Weight kg STA
39 Mounting STA
40 Enclosure ingress protection rating IP54
41 Generator cooling method IC4A1A1
42 Air Discharge (Top or Bottom) STA
43 Air filters STA
44 Bearing type (DE & NDE) STA
45 Lubrication STA
46 Terminal Box type, size and arrangement STA
47 Max cable size and No. of cores/phase:
48 Main mm² (1 x 3c) 70 mm² (TBC)
49 Heater mm² (3c + E) 4 mm²
50 Aux mm² 9 Triad 1.5 mm²
Rumaila Project
(FEED) Date: 11-Jan-13

Data Sheet (Electrical) for Medium Term Power Supply Revision: 0


11 kV Diesel Generator Package Page: 6 of 7
00100W-C-PG-PP03-EL-DAS-0004

Equipment Data Sheet for Diesel Generators


1 Tag No. : TBA Client: BP Iraq NV
2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : N/A Purchase Order No. : TBA
5 No. of Units: 1 Package (up to 4 generator sets)
6 Service Description: Medium Term Power Generator
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
8 Rotor moment of inertia (GD²) kg m² STA
9 Motor inertia constant (H) STA
10
11 EXCITATION SYSTEM
12 Manufacturer STA
13 Permanent Magnet Pilot Generator (PMG) Type Yes
14 Brushless rotating rectifier type Yes
15 Voltage rating (% of exciter ceiling voltage) % STA
16 Current capacity (% of nominal) % STA
17 Diode bridge element failure detection Yes
18 Rated current A STA
19 Rated voltage V STA
20 Input current A STA
21 Input voltage V STA
22 Hermetically sealed Yes
23
24 AUTOMATIC VOLTAGE REGULATOR (AVR) SYSTEM
25 Manufacturer STA
26 Type Digital (3-Phase sensing)
27 IEC 60034-16-12 model type STA
28 Solid state regulator Yes
29 Excitation Limitation: Max excitation limits V STA
30 Max volts/hertz limits V/Hz STA
31 Output voltage set point adjustment +/- 10%
32 Voltage regulation under following load conditions:
33 100% load rejection % STA
34 50% load acceptance, initial load 0% % STA
35 50% load acceptance, initial load 50% % STA
36 Under frequency protection Yes/No Yes
37 Over voltage protection Yes/No Yes
38 Voltage regulation under transient conditions: % STA (Note 6)
39 Overfluxing control on auto and manual mode Yes/No Yes
40 Main and manual AVR Yes/No Yes
41 Functional without external power supply Yes/No Yes
42
43 EXCITER MODEL PARAMETERS
44 Excitation time constant (TE) STA
45 Exciter Saturation (SE) @ 75% UE max STA
46 @ 100% UE max STA
47 Excitation gain constant (KE) STA
48 Maximum exciter voltage (UE max) V STA
49 Minimum exciter volatge (UE min) V STA
50 Minimum Regulator output (VR min) V STA
Rumaila Project
(FEED) Date: 11-Jan-13

Data Sheet (Electrical) for Medium Term Power Supply Revision: 0


11 kV Diesel Generator Package Page: 7 of 7
00100W-C-PG-PP03-EL-DAS-0004

Equipment Data Sheet for Diesel Generators


1 Tag No. : TBA Client: BP Iraq NV
2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq
3 P & ID No. : N/A Manufacturer: TBA
4 Calculation Ref. : N/A Purchase Order No. : TBA
5 No. of Units: 1 Package (up to 4 generator sets)
6 Service Description: Medium Term Power Generator
7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE
8
9 AVR MODEL PARAMETERS
10 Forward gain constant at AVR (KA) STA
11 AVR amplifier time constant (TA) STA
12 Feedback gain of AVR (KF) STA
13 AVR feedback time constant (TF1) STA
14 AVR feedback time constant (TF2) STA
15
16
17 FILTER/LOAD COMPENSATOR MODEL PARAMETERS
18 Filter time constant (Tc) STA
19 Compensation gain constant (Rc) STA
20 Compensation gain constant (Xc) STA
21
22
23 GOVERNOR (See Diesel Engine Data Sheet)
24 Droop & Isochronous speed control Yes/No Yes
25 Frequency deviation for following load conditions:
26 100% load rejection % STA (Note 7)
27 50% load acceptance, initial load 0% % STA (Note 7)
28 50% acceptance, initial load 50% % STA (Note 7)
29 Full load rejection with no overspeed trip Yes/No Yes
30 Frequency range for steady state conditions % (+/-) 1
31
32
33 SYNCHRONISING CONTROL
34 Manufacturer STA
35 Type STA
36 Auto / manual synchronising unit Yes/No Yes
37 Synchronism check relay Yes/No Yes (at generator switchgear)
38 Synchronization with utility mains Yes/No No
39 Synchronization with other generator units Yes/No Yes (minimum of 5 generator units)
40 Load sharing capability Yes/No Yes
41 Automatic Load Shedding Yes/No Yes
42 LOAD BANK
43 Load Bank Required Yes/No No
44 Load Bank Type N/A
45
46
47
48
49
50

You might also like