Data Sheet (Electrical) for Medium Term Power Supply Revision: 0 11 kV Diesel Generator Package 00100W-C-DG-DN00-EL-DAS-0019 Page: 2 of 7
REVISION DESCRIPTION SHEET
Rev. Sheet/Section Reason for Revision
A Issued for Inter Discipline Check
B Issued for Client Review
C Issued for Enquiry
0 pg 3 - Note 10 Issued for Use
Hold No. Sheet/Section Description of Hold
Rumaila Project (FEED) Date: 11-Jan-13 Data Sheet (Electrical) for Medium Term Power Supply Revision: 0 11 kV Diesel Generator Package Page 3 of 7 00100W-C-PG-PP03-EL-DAS-0004
NOTES AND ABBREVIATIONS
1 2 3 (1) For additional information refer the the following documents: 4 a. 00100W-C-G0-G000-EL-SPC-0019 - Electrical Requirements for Emergency Diesel Generators (FEED) 5 (All sections of this specification are applicable except for section 1.1 which refers to 400 V emergency generators) 6 7 b. 00100W-C-PG-PP03-EL-BOD-0001 - Basis of Design for 'Medium Term ESP Power Supplies' 8 (Only sections 3.2 and 5 are applicable) 9 10 (2) For environmental conditions, refer: BEDD 00100W-C-G0-G000-GE-BOD-0001 11 12 (3) Protective painting and coating shall be in accordance with 00100W-C-G0-G000-ML-SPC-0009. 13 14 (4) Generator FAT per IEC 60034 and complete package string test are required. Full String test is required only on the 1st generator set; 15 it shall include load rejection tests. 16 17 (5) Generator package SUPPLIER shall allow for the provision of Generator Paralleling Switchgear where individual generator units 18 shall be synchronised and connected to a common bus. Refer to 00100W-C-PG-PP03-EL-DAS-0007 for more information on the 19 requirements for 11 kV switchgear. 20 21 (6) Voltage restoration to +/- 2.5% within 10 secs and to +/- 3.0% within 1 sec. 22 23 (7) Frequency deviation not more than 5% returning to within 1% of rated frequency within 3 secs for the defined load conditions. 24 25 (8) As per Noise Control Philosophy 00100W-C-G0-G000-SR-PHL-0003 26 27 (9) Generator control and synchronisation panel shall be installed in generator package substation. Generator set monitoring and 28 protection system shall be provided by generator set manufacturer. 29 30 (10) The generator package shall be capable of supplying a total load of 5 MVA in an N + 1 configuration, with spare unit operating as a 31 spinning reserve at an ambient temperature of 55 degree C. The load is predominantly VSD (worst case 100% 12 pulse) driven ESPs. 32 33 (11) Generator Package SUPPLIER shall take into consideration 3rd, 5th and 7th order harmonics contribution from transformer and VSD. 34 Any heat rise inside the container before the air filters, radiator power requirements and any other genset auxiliary that affect the 35 the generator rating shall also be accounted for. 36 37 (12) Generator Package shall be capable of 'Black Start'. It shall be arranged such that control power will be available to the generator 38 package paralleling switchgear upon starting one generator set. 39 40 (13) Generators shall be NFPA 110 compliant for one-step load acceptance with the generator engine set at operating temperature. 41 42 43 44 Abbreviations: 45 PMG = Permanent Magnet Generator 46 STA = Supplier to Advise 47 TBA =To Be Advised 48 TBC =To Be Confirmed 49 N/A = Not Applicable 50 VSD = Variable Speed Drive 51 ESP = Electrical Submersible Pump 52 For other abbreviations, refer specification 00100W-C-G0-G000-PM-PRO-0001 53 54 55 Rumaila Project (FEED) Date: 11-Jan-13
Data Sheet (Electrical) for Medium Term Power Supply Revision: 0
11 kV Diesel Generator Package Page: 4 of 7 00100W-C-PG-PP03-EL-DAS-0004
Equipment Data Sheet for Diesel Generators
1 Tag No. : TBA Client: BP Iraq NV 2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq 3 P & ID No. : N/A Manufacturer: TBA 4 Calculation Ref. : N/A Purchase Order No. : TBA 5 No. of Units: 1 Package (up to 4 generator sets) Driver Type: Diesel Engine 6 Service Description: Medium Term Power Generator Driver Data Sheet No. : 00100W-C-PG-PP00-ME-DAS-0001 7 ENVIRONMENTAL CONDITIONS POWER SYSTEM 8 Location: Outdoor (Packaged) System Voltage: 11000 V 5% 9 Ambient air temp: Min: Note 2 Max: Note 2 System Frequency: 50 Hz 1% 10 Humidity: Note 2 Altitude: Note 2 Neutral Earthing: Resistance Earthed 11 Hazardous area classification: Safe Area 12 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE 13 GENERATOR DATA 14 Manufacturer STA 15 Type & Model No. STA 16 Paint specification and colour See Note 3 17 Applicable Codes and Standards IEC 18 Rated Voltage V AC 11000 19 Rated Frequency Hz 50 20 Duty Type S1 (Continuous) 21 Max continuous rating at S1 duty (55 degree C) kW See Note 10 22 Power Factor (Lag/Lead) pf 0.8 (lag) 23 Stator Connection Star 24 Neutral Earthing Method Resistance Earthed (See Note 1b) 25 Phase rotation R-Y-B 26 System max. fault current (3-ph sym) kA rms 5 for 1 sec 27 Protection and Metering Drawing No. TBA 28 Rotation facing Drive End STA 29 Insulation Class F 30 Temperature rise B 31 Speed rpm STA 32 First critical / Synch speed rpm STA 33 X/R Ratio STA 34 Overload capability: 30 seconds 150% 35 1 hour 110% 36 Unbalanced load capability STA 37 Voltage/frequency variations to IEC 60034-1 Zone 'B' 38 Generator Efficiency: Full load % STA 39 75% load % STA 40 50% load % STA 41 Type of excitation PMG 42 Telephone Harmonic Factor (THF) STA 43 Suitable for parallel operation with the system Yes/No Yes (up to 4 identical units) 44 Winding temperature detectors (No. & type) 6 off RTDs 45 Winding type Form wound 46 Winding Pitch 0.72 - 0.82 47 Max noise level at no load dB(A) Note 8 48 Pole Pitch STA 49 Space heater for: Generator W STA 50 Control Panel W STA 51 Voltage VAC 230 52 Rumaila Project (FEED) Date: 11-Jan-13
Data Sheet (Electrical) for Medium Term Power Supply Revision: 0
11 kV Diesel Generator Package Page: 5 of 7
00100W-C-PG-PP03-EL-DAS-0004
Equipment Data Sheet for Diesel Generators
1 Tag No. : TBA Client: BP Iraq NV 2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq 3 P & ID No. : N/A Manufacturer: TBA 4 Calculation Ref. : N/A Purchase Order No. : TBA 5 No. of Units: 1 Package (up to 4 generator sets) 6 Service Description: Medium Term Power Generator 7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE 8 Direct Axis Reactances: 9 Synchronous (Xd) - Sat & Unsat % STA 10 Transient (X'd) % ≤ 18 11 Subtransient (X''d) % ≥ 12.5 12 Positive Sequence Resistance (R1) % STA 13 Negative Sequence Resistance (R2) % STA 14 Negative Sequence Reactance (X2) - Sat & Unsat % STA 15 Zero Sequence Resistance (R0) % STA 16 Zero Sequence Reactance (X0) % STA 17 Short Circuit Ratio (X/R) STA 18 Quadrature Axis Reactances: 19 Synchronous (Xq) % STA 20 Transient (X'q) % STA 21 Subtransient (X''q) % STA 22 Direct Axis Open Circuit Time Constants: 23 Transient (T'do) STA 24 Subtransient (T"do) STA 25 Direct Axis Short Circuit Time Constants: 26 Transient (T'ds) STA 27 Subtarnsient (T"ds) STA 28 Quadrature Axis Open Circuit Time Constants: 29 Transient (T'qo) STA 30 Subtransient (T"qo) STA 31 Quadrature Axis Short Circuit Time Constants: 32 Transient (T'qs) STA 33 Subtransient (T''qs) STA 34 35 36 PHYSICAL CHARACTERISTICS (Excluding Driver) 37 Package Dimensions (L X W X H) mm STA 38 Package Weight kg STA 39 Mounting STA 40 Enclosure ingress protection rating IP54 41 Generator cooling method IC4A1A1 42 Air Discharge (Top or Bottom) STA 43 Air filters STA 44 Bearing type (DE & NDE) STA 45 Lubrication STA 46 Terminal Box type, size and arrangement STA 47 Max cable size and No. of cores/phase: 48 Main mm² (1 x 3c) 70 mm² (TBC) 49 Heater mm² (3c + E) 4 mm² 50 Aux mm² 9 Triad 1.5 mm² Rumaila Project (FEED) Date: 11-Jan-13
Data Sheet (Electrical) for Medium Term Power Supply Revision: 0
11 kV Diesel Generator Package Page: 6 of 7 00100W-C-PG-PP03-EL-DAS-0004
Equipment Data Sheet for Diesel Generators
1 Tag No. : TBA Client: BP Iraq NV 2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq 3 P & ID No. : N/A Manufacturer: TBA 4 Calculation Ref. : N/A Purchase Order No. : TBA 5 No. of Units: 1 Package (up to 4 generator sets) 6 Service Description: Medium Term Power Generator 7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE 8 Rotor moment of inertia (GD²) kg m² STA 9 Motor inertia constant (H) STA 10 11 EXCITATION SYSTEM 12 Manufacturer STA 13 Permanent Magnet Pilot Generator (PMG) Type Yes 14 Brushless rotating rectifier type Yes 15 Voltage rating (% of exciter ceiling voltage) % STA 16 Current capacity (% of nominal) % STA 17 Diode bridge element failure detection Yes 18 Rated current A STA 19 Rated voltage V STA 20 Input current A STA 21 Input voltage V STA 22 Hermetically sealed Yes 23 24 AUTOMATIC VOLTAGE REGULATOR (AVR) SYSTEM 25 Manufacturer STA 26 Type Digital (3-Phase sensing) 27 IEC 60034-16-12 model type STA 28 Solid state regulator Yes 29 Excitation Limitation: Max excitation limits V STA 30 Max volts/hertz limits V/Hz STA 31 Output voltage set point adjustment +/- 10% 32 Voltage regulation under following load conditions: 33 100% load rejection % STA 34 50% load acceptance, initial load 0% % STA 35 50% load acceptance, initial load 50% % STA 36 Under frequency protection Yes/No Yes 37 Over voltage protection Yes/No Yes 38 Voltage regulation under transient conditions: % STA (Note 6) 39 Overfluxing control on auto and manual mode Yes/No Yes 40 Main and manual AVR Yes/No Yes 41 Functional without external power supply Yes/No Yes 42 43 EXCITER MODEL PARAMETERS 44 Excitation time constant (TE) STA 45 Exciter Saturation (SE) @ 75% UE max STA 46 @ 100% UE max STA 47 Excitation gain constant (KE) STA 48 Maximum exciter voltage (UE max) V STA 49 Minimum exciter volatge (UE min) V STA 50 Minimum Regulator output (VR min) V STA Rumaila Project (FEED) Date: 11-Jan-13
Data Sheet (Electrical) for Medium Term Power Supply Revision: 0
11 kV Diesel Generator Package Page: 7 of 7 00100W-C-PG-PP03-EL-DAS-0004
Equipment Data Sheet for Diesel Generators
1 Tag No. : TBA Client: BP Iraq NV 2 Service: Medium Term Power Generator Plant Location: Rumaila Iraq 3 P & ID No. : N/A Manufacturer: TBA 4 Calculation Ref. : N/A Purchase Order No. : TBA 5 No. of Units: 1 Package (up to 4 generator sets) 6 Service Description: Medium Term Power Generator 7 PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS SUPPLIER'S RESPONSE 8 9 AVR MODEL PARAMETERS 10 Forward gain constant at AVR (KA) STA 11 AVR amplifier time constant (TA) STA 12 Feedback gain of AVR (KF) STA 13 AVR feedback time constant (TF1) STA 14 AVR feedback time constant (TF2) STA 15 16 17 FILTER/LOAD COMPENSATOR MODEL PARAMETERS 18 Filter time constant (Tc) STA 19 Compensation gain constant (Rc) STA 20 Compensation gain constant (Xc) STA 21 22 23 GOVERNOR (See Diesel Engine Data Sheet) 24 Droop & Isochronous speed control Yes/No Yes 25 Frequency deviation for following load conditions: 26 100% load rejection % STA (Note 7) 27 50% load acceptance, initial load 0% % STA (Note 7) 28 50% acceptance, initial load 50% % STA (Note 7) 29 Full load rejection with no overspeed trip Yes/No Yes 30 Frequency range for steady state conditions % (+/-) 1 31 32 33 SYNCHRONISING CONTROL 34 Manufacturer STA 35 Type STA 36 Auto / manual synchronising unit Yes/No Yes 37 Synchronism check relay Yes/No Yes (at generator switchgear) 38 Synchronization with utility mains Yes/No No 39 Synchronization with other generator units Yes/No Yes (minimum of 5 generator units) 40 Load sharing capability Yes/No Yes 41 Automatic Load Shedding Yes/No Yes 42 LOAD BANK 43 Load Bank Required Yes/No No 44 Load Bank Type N/A 45 46 47 48 49 50