Document No : 328

Page 1
HYDRO TEST REPORT Rev : 0
Date : 28.10.2022

Drawing No.:
CTS-471
Item:
Air Heat Exchanger
Client:
VMARS BIOPHARMA Pvt. Ltd.
PO:
V M B 0 9 2 2 1 1 8 /0 5 .0 9 .2 0 2 2
Test Duration: 8 Hrs

Test Pressure: 5 bar for Inner Pipe & 3.7 bar for Outer Pipe.
Test Date Start Time End Time Pass Side Test Pressure
28.10.2022 9.30 am 1.30 am Inner Pipe 5 bar

28.10.2022 2.30 pm 6.30 pm Outer Pipe 3.7 bar

Pressure Gauge Details:


Nomenclature Pressure Gauge Range 0 to 7 Kg/cm2
Make Excel L.C. 0.1
ID. No. CTS/PG/01
Certificate no UCPL/2122/J02233/01

Remarks:
1. Hydro Test carried out at pressure 5 bar for Inner Pipe side & 3.7 bar for
Outer Pipe side. No leak OR no pressure drop found.
Hydro Test found satisfactory.

For Chemsys Techno Services

Chemsys Techno Services


#301/ B, Ph-1, SUMANSHILP, Parande Nagar, Dighi, Pune- 411015
Cell: +91 7875133110 Tel/Fax: +91-20-27460747, Email: sales@chemsys.co.in