Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
I
voltage regulation, and cost-effective power quality N present distribution systems, unbalanced nonlinear loads
improvement. In this paper, an intelligent substation by a
distribution transformer integrated with a capacitive-coupling
in three-phase utility have given rise to a number of power
winding tap injection static synchronous compensator (CWTI- quality (PQ) problems, such as low power factor (PF),
DSTATCOM) is proposed for balance and unbalance harmonic pollution, and unbalanced currents. Excessive
operations. Compared with the state-of-the-art approaches, reactive power demand increases feeder losses and reduces
CWTI-DSTATCOM can operate at a low dc voltage with a small active power transfer capability, whereas the unbalance
active inverter rating, which also can provide distributed current endangers the safe operation of transformers and
voltage, reactive, and unbalanced current compensation. The
power rating reduction mechanism is mathematically revealed
generators [1], [2]. Due to their fast dynamic response and
via balance and unbalance compensation analysis, which is excellent compensation performance, distribution static
further used to determine the optimal inverter power rating of synchronous compensators (DSTATCOMs) [3], [4] have
unbalance operation via an optimal LC filter design method. been widely used to provide reactive power and unbalance
Furthermore, a comprehensive compensation control strategy is compensation and improve the PQ of the network.
developed to coordinate the transformer taps and the active In order to improve the PQ, DSTATCOMs are installed
inverter under balanced and unbalanced operations. Simulation
and real-time digital simulator (RTDS) hardware-in-the-loop
locally at the customer-side to maintain the local bus voltage
(HIL) experiments are performed to prove the validity and [5], [6]. Local compensations at some light-load buses are
effectiveness of the proposed topology over inverter rating unable to share their excess capacity to other heavy-load
reduction and power quality enhancement. buses [7]. As a result, a large number of decentralized
Index Terms—static synchronous compensator (STATCOM), STATCOMs need to be installed, which increases the total
unbalanced compensation, winding tap, LC filter, symmetry investment and maintenance costs. Recently intelligent box-
sequence, power rating. type substations [8] and centralized compensation systems [7]
Manuscript received September 05, 2021; revised January 18,
for low voltage distribution networks are proposed to address
2022; accepted February 18, 2022. This work was supported by Macau the above high-cost issues. The integration of distribution
Science and Technology Development Fund (FDCT, Macao) under transformer and power quality compensator can achieve
Projects FDCT 0026/2019/A1, in part by the State Key Laboratory of
multifunction operations, such as distributed voltage
Internet of Things of University of Macau under Project SKL-
IOTSC(UM)-2021-2023, in part by the Guangdong-Hong Kong-Macau regulation and power flow control, which turns to become
Joint Laboratory for Smart Cities under Project EF008/IOTSC- more and more important to accelerate the smart grid
YKV/2021/GDSTC, in part by Research Committee of University of development.
Macau under project MYRG2018-00056-FST, and in part by the Hunan
Youth Science and Technology Innovation Talents Program under Conventionally, intelligent box-type substations equipped
Project 2021RC3059. (Corresponding author: Lei Wang; Man-Chung with DSTATCOM [8] have promising application prospects
Wong.) in the distribution systems due to their compact design, small
Ziyi Bai, Ying Pang, Zeng Xiang, and Chi-Kong Wong are with the
State Key Laboratory of Internet of Things for Smart City, University of floor space, and flexible installed environment. The
Macau, Macao 999078, China, also with the Department of Electrical centralized compensation system can be easily expanded to
and Computer Engineering, Faculty of Science and Technology, meet future load growth [7]. There are two usual installed
University of Macau, Macao 999078, China (e-mail:
yc07909@um.edu.mo; yb87446@um.edu.mo; yb57435@umac.mo; positions of DSTATCOMs, including the low-voltage (LV)
ckwong@um.edu.mo). and high-voltage (HV) sides of the transformer. While the
Lei Wang is with the College of Electrical and Information larger DSTATCOM current level for the LV side installation
Engineering, Hunan University, Changsha 410000, China (email:
jordanwanglei@hnu.edu.cn).
would result in high heating and power losses of the devices,
Chi-Seng Lam is with the State Key Laboratory of Analog and the DSTATCOM current level for the HV side installation is
Mixed-Signal VLSI, University of Macau, Macao 999078, China, also lower.
with the Institute of Microelectronics, University of Macau, Macao
Fig. 1 summarized the historical development, circuit
999078, China, and also with the Department of Electrical and
Computer Engineering, Faculty of Science and Technology, University configurations, proposed years, and corresponding references
of Macau, Macao 999078, China. (e-mail: cslam@um.edu.mo) for different topologies which integrate the STATCOM with
Man-Chung Wong is with the State Key Laboratory of Internet of the high voltage side of a distribution transformer. As shown
Things for Smart City, University of Macau, Macao 999078, China, and
also with the State Key Laboratory of Analog and Mixed-Signal VLSI, in Fig. 1 (a), the Topology 1 [9] was proposed in 1981, and its
University of Macau, Macao 999078, China, and also with the D-STATCOM is connected to the HV side of a distributed
Department of Electrical and Computer Engineering, Faculty of transformer through a step-down transformer. Further studies
Science and Technology, University of Macau, Macao 999078, China
(e-mail: mcwong@umac.mo). relating to its structure, features, and applications were
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Topology
(proposed year): 1 (1981) 2 (2005) 3 (2013) 4 (2015) 5 (2016) Proposed Topology
References: [9], [10] [11]-[13] [16]-[18] [24]-[26] [27]-[32]
(a) (b) (c) (d) (e) (f)
Fig. 1. DSTATCOM connection type comparison of: (a) Topology 1, (b) Topology 2, (c) Topology 3, (d) Topology 4, (e) Topology 5, and (f) proposed
capacitive DSTATCOM integrated with transformer taps.
addressed in [10] in 2014. In 2005, cascaded multilevel TABLE I
COMPARISONS OF TOPOLOGIES 1-5, AND PROPOSED TOPOLOGY
DSTATCOM, as Topology 2 shown in Fig. 1 (b) [11], was
proposed to connect directly to the grid instead. The Topology
Windings DC-link Inverter Unbalance
Cost Structure
customized voltage rating operation
multilevel structure needs relatively more power electronic
1 [9]-[10] No Medium High Yes High Simple
components and dc-linked capacitors [12], which will cause 2 [11]-[13]] No Low High Yes High Complex
more power switching loss, economic and reliability issues 3 [16]-[18] Yes Medium High Yes High Complex
[13]. On the other hand, the multilevel structure requires more 4 [24]-[26] Yes Low Low Yes High Complex
pulses and drivers to control the system so that a complicated 5 [27]-[32] No High High No Medium Simple
Proposed No Low Low Yes Low Simple
controller is required [12].
Note: the unsatisfying characteristics are shaded.
Based on the above concerns for multilevel structure, a
STATCOM integrated with the distribution transformer is relatively medium dc-link voltage and higher inverter rating
researched, which is a cost-effective centralized power of Topology 1 are required so that its initial cost is increased.
quality compensation method to improve the PQ [6], [14], The multilevel structure of Topology 2 decreases the dc-link
[15]. As a result, controllably inductive power filters (CIPF), voltage of each inverter and however the more power
which is a three-winding transformer structure was proposed electronic components increase its cost and structural
in 2013 as Topology 3 [16][20] shown in Fig. 1 (c). Its complexity. Though Topologies 3 and 4 can reduce the dc-
operation mechanism and control strategy were studied in link voltage, the induction filter windings and transformers
[16][18]. Such topology was further applied into non-linear must be customized. Since the active inverter bears all the
compensation power, high inverter ratings are required for
load scenarios [19] in 2013 and photovoltaic power plants [20]
Topologies 1-3, whereas the inverter rating of Topology 4 can
in 2019, respectively. Compared with the L-coupling inverter,
be lower due to its LC filters. As the medium cost and simple
the LC-coupling inverter can reduce the voltage source
structure, more attention on Topology 5 was obtained recently.
inverter (VSI) rating and dc-link voltage [21][23]. Thus,
However, both the VSI rating and dc-link voltage of
hybrid inductive and active filter (HIAF), as Topology 4
Topology 5 are relatively higher comparing to the proposed
shown in Fig. 1 (d), was proposed in 2015 in [24] by replacing
one. Its unbalanced operation and transformer tap ratio to
the L filter with LC filter. After that, Topology 4 was applied
converter rating have not been addressed yet.
in shipboard [25] in 2017 and DC grid applications [26]
In the proposed topology, the VSI of CWTI-DSTATCOM
accordingly in 2020.
is connected to the adjustable transformer primary winding
Based on the cost reduction concern and motivated by the
taps via a capacitive LC part. The capacitive LC part provides
structure of autotransformer, the STATCOM was directly
a high voltage drop between the tap coupling point and the
connected with the distribution transformer via winding taps
active inverter so that the inverter can work at a lower dc-link
instead of an auxiliary step-down transformer in 2016 [27]
voltage level relatively. The capacitive LC also offers a
[29], which were applied to traction power system. After
certain reactive power to reduce the required inverter rating
that, [30] proposed a winding tap injection DSTATCOM
through designing the parameters technically. In such case,
(WTI-DSTATCOM) integrated with a distribution
only a low-rating active inverter is required to absorb the
transformer in 2018, as Topology 5 shown in Fig. 1 (e). Its
residual balanced and unbalanced power. The contributions
operation mechanism and model analysis were studied in [30],
of this paper are summarized as follows.
and the advanced control strategies were analyzed in
1) A CWTI-DSTATCOM is proposed to integrate
[31][32] respectively between 2018 and 2020. For the STATCOM with tapped transformer by coupling LC filters.
inverter rating reduction of the conventional WTI- The following technical issues are studied:
DSTATCOM [27][32], this paper proposes a centralized Reduction of power ratings comparing with existing
compensation topology and control strategy of capacitive- solution WTI-DSTATCOM under balanced and
coupling winding tap injection-based DSTATCOM (CWTI- unbalanced situations;
DSTATCOM) as shown in Fig. 1 (f). Influence of component parameters including the
A comparison among different topologies is summarized transformer winding tap ratio and coupling impedance to
in Table I. Through the additional step-down transformer, the inverter rating;
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
The minimum dc-link voltage of DSTATCOM for relationship among source current, load current, and
acceptable performance and low operational loss under compensation current in Fig. 2 is shown as,
balanced and unbalanced situations; iSa iL a ic a
i M i N i
Cost comparison between existing solution WTI- Sb Lb cb (1)
DSTATCOM and the proposed one. i S c i L c i c c
2) Comparing to existing WTI-DSTATCOM, the inverter where the transform matrix M and N are shown as,
rating of CWTI-DSTATCOM is only 12% and 33% of WTI- W Sa W Sc
DSTATCOM under balanced and 30% unbalanced cases, 0
W Pa W Pc
1 0 1
respectively. W W Sb 1 1
3) The transformer winding tap ratio is firstly studied to M Sa 0 1 0 (2)
W Pa W Pb Kx
0 1 1
reduce the required rating of DSTATCOM, and the tap ratio W Sb W Sc
should be 0.5 for the minimum DSTATCOM rating. 0
W Pb W P c
4) The strategy of computing its minimum dc-link voltage W Pa 2 W P c1
is proposed based on the symmetrical component theory. 0
W Pa W Pc
1 k x 0 kx
5) Corresponding control is given with considering W Pa1 W Pb 2
transformer taps and sufficient dc-link voltage. N 0 k x 1 kx 0
(3)
W Pa W Pb 0 kx 1 k x
II. CIRCUIT CONFIGURATION AND MODELING OF THE W Pb1 W Pc 2
0
PROPOSED CWTI-STATCOM W Pb W P c
In (2) and (3), Kx= WSx/WPx is the turn ratio of the
A. Circuit Configuration transformer and Ka= Kb= Kc. Here, the turn ratio K is larger
Fig. 2 gives the circuit configuration of the proposed than 1 as a result of the step-down transformer. kx represents
CWTI-DSTATCOM, which includes a passive part and an the winding tap ratio. kx = WPx1/WPx and ka= kb= kc. When the
active inverter part connected to the transformer winding taps compensation current icx satisfy (4), only the active current
points. Here, the subscript “x” denotes phase x = a, b, c. vSx, exists in the source current iSx.
vLx, vcx, iSx, iLx, i cx represent the source voltage, the load i ca iLa iLap
i N
voltage, the winding tap coupling point voltage, the source cb
1
M iL b iL bp (4)
iLa vLa a Inductive Load i cc iL c iL cp
vSa iSa WPc a1
u0 WSa a
b0 ida2i
a0
iLb vLb
n
LLa RLa The iLxp in (4) is the active component of the load current.
vSb iSb idb1 idc2
da1 WSb b1 b
WPb idb2idc1 WPa Wo1
b
LLb RLb The load current in 0-1-2 coordinate can be calculated by
Sc n
vSc iSc
v0 w0 c1 iLc vLc c c
n LLc RLc
applying symmetrical component theory as,
c0 n
vca ica vcb icb vcc icc I L 0 IL 0 I L a IL a
I A I
Coupling filter Single phase equivalence
L1 IL 1 Lb IL b (5)
Previous WTI- Main flux I L 2 IL 2 I L c IL c
DSTATCOM:
L idx1
where
+ Sa1 Sb1 Sc1 SW1 iLx 1 1 1 1 1 1
Winding WPx1
1
a 2 , and A 1 1 a
taps
A 1 a a2 (6)
3
Vdc Proposed CWTI- WSx Load
icx
……
DSTATCOM:
Cdc vinva vinvb vinvc L
WPx2 1 a2 a 1 a a 2
C SWn
In (6), a=ej120. The phasor magnitude of the load current
Leakage
– flux
Sa2 Sb2 Sc2
ILx and angle ILx can be obtained by using (7)(9). Noted that
Fig. 2. Circuit configuration of the proposed CWTI-DSTATCOM and
previous WTI-DSTATCOM.
the 0-1-2 coordinate is adopted as the basic framework in this
paper for balance and unbalance operations, while the dq0
current, the load current, the compensation current, framework in (7)-(9) is adopted to calculate the load current
respectively. Cdc and Vdc are the DC capacitor and dc-link ILx and angle ILx. iDLx is the iLx signal delay by 90. iLxd and
voltage. The inverter is connected to the adjustable taps iLxq are the dc components of the d-axis component iLxd and
(labeled as u0, v0, and w0) on primary winding (labeled as a0- q-axis component iLxq. ωt is the input angle of dq
b0, b0-c0, and c0-a0) of the transformer through coupling transformation.
inductor L and capacitor C. LLx and RLx are the load iLxd c o s t s in t i L x
inductance and resistance, respectively. WPx (primary side) (7)
i L xq s in t co s t i LDx
and WSx (secondary side) denote the winding turns of Dyn11
connected distribution transformer. The winding turns on I Lx iL xd 2 iL xq 2 (8)
both sides of the taps are WPx1 and WPx2 (WPx1+WPx2=WPx). idx ILx arctan iLxq iLxd (9)
is delta-loop connected windings currents. The SWn
represents the switches used to select the taps. For the CWTI-DSTATCOM, based on (4)(6), the
compensation current in 0-1-2 coordinate can be deduced as,
B. Current Modeling I c 0 Ic 0 0
Based on the Kirchhoff's current law and ampere-turns I A N 1
M A 1 I L 1 s in IL 1 9 0 (10)
c1 Ic 1
balance principle of the distribution transformer, the I c 2 Ic 2 I L 2 IL 2
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Tap coupling
u0
the transformer, the 0-sequence component is zero. VSa 4000
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Ratio of Runbal/RL_bal
two important points can be summarized as follows: 3 RL_unbal/RL_bal
When the source grid voltage Vsx is given, the winding tap
ratio kx can be chosen at 0.5 so that its coupling point 2
voltage Vcx can be smaller. 1
The VdcLC_bal and RLC_bal of the CWTI-DSTATCOM are RLC_unbal/RL_bal
always smaller than WTI-DSTATCOM. 0
0.5 0 1 1.5
Unbalance coefficient
b) Unbalanced Load
Fig. 6. Ratios RL_unbal /RL_bal and RLC_unbal/RL_bal in terms of .
For unbalanced load, the compensation current includes 1-
and 2-sequence components. Assume that the unbalance 30
Ratio of RLC_unbal/RLC_bal
coefficient is defined as the 2-sequence current amplitude
20
divided by the 1-sequence one, RLC_unbal/RLC_bal
Ic2
(25) 10
I c1
The maximum compensation current can be treated as the 0
0.5 0 1 1.5
amplitude sum of Ic1 and Ic2 when considering the worst case. Unbalance coefficient
The inverter output voltage includes 1- and 2-sequence Fig. 7. Ratio of RLC_unbal/RLC_bal in terms of .
voltages in (16) and (17). Similarly, the maximum inverter
output voltage can also be treated as the amplitude sum of From the above VSI power rating comparisons, several
Vinv1 and Vinv2. Considering the worst case under unbalanced important points can be summarized as follows:
load, the required VSI power rating ratio between unbalanced When the load is balanced, the CWTI-DSTATCOM has a
and balanced load can be formulated as, lower dc voltage and inverter rating compared with the
R unbal V dc _ unbal ( I c1 I c 2 ) conventional WTI-DSTATCOM, and it is only 12%
(26)
R bal V dc _ bal I c1 inverter rating of the WTI-DSTATCOM.
where the required dc-link voltage ratio between the worst The required inverter rating is increased with the increase
unbalanced and balanced conditions can be expressed as (27) of the unbalance coefficient.
based on (14)(17), and (25). When the unbalanced compensating current becomes
V d cL / L C _ u n b a l V in v 1 V in v 2 V ( V in v 1 V c x ) larger, the CWTI-DSTATCOM is still preferable due to its
in v 1
V dcL / L C _ b al V in v 1 V in v 1 lower rating. When the unbalance compensating current is
(27)
1 V d c _ b a l 6 V cx less than 133% of the balanced one, the VdcLC_unbal and
V dc _ bal RLC_unbal of the CWTI-DSTATCOM are lower than those
Based on the above analysis, for the WTI-DSTATCOM of WTI-DSTATCOM.
and CWTI-DSTATCOM, the required VSI power rating
III. PARAMETER DESIGN AND POWER RATING COMPARISON
ratios between the unbalanced and balanced conditions can
be further deduced as, The selection of coupling parameters such as the
R L _ unbal 1 V d cL _ b a l 6 V cx inductance and capacitance of CWTI-DSTATCOM can
1 (28) affect the required dc-link voltage and rating. In this section,
R L _ bal V d cL _ b a l
a conventional LC design method is given in the following
R LC _ unbal 1 V d cL C _ b a l 6 V cx part A for balanced load, whereas an optimal LC design
1 (29)
R LC _ bal V d cL C _ b a l method for unbalanced load is proposed in the following part
Based on (28) and (29), when the 2-sequence B to further decrease the required dc-link voltage and inverter
compensation current is required, the required VSI power rating.
ratings of WTI-DSTATCOM and CWTI-DSTATCOM A. LC Design Based on Balanced Load
increase due to the VdcL_bal >√6Vcx and VdcLC_bal <√6Vcx. The
required VSI power rating ratio between the CWTI- The coupling L is dedicated to filter out the current ripple
DSTATCOM and WTI-DSTATCOM can be expressed as, brought by the power switches of the active inverter part [23].
Its value can be limited as (31),
R LC _ unbal 1 V d c L C _ b a l 6 V c x
(30) V dc
R L _ unbal 1 V d c L _ b a l 6 V c x L (31)
8 f s ic max
The VSI power rating ratios of RL_unbal/RL_bal,
RLC_unbal/RL_bal, and RLC-unbal/RLC-bal in terms of unbalance where fs is the switching frequency and icmax is the maximum
coefficient are shown in Fig. 6 and 7. Taking RL_bal as the allowed output ripple current.
base value, Fig. 6 shows that the required VSI ratings Since the Icx is a fixed value under full compensation for a
comparison for unbalanced cases. It implies that when the certain load, the minimum dc-link voltage VdcLC_min indicates
unbalance coefficient from 0 to 1.33, the required VSI dc-link the minimum VSI power rating according to Section II-D.
voltage and rating of CWTI-DSTATCOM are lower than Thus, the required minimum dc-link voltage is the key point
these of WTI-DSTATCOM. However, when the unbalance in designing the coupling LC impedance.
coefficient is larger than 1.33, the WTI-DSTATCOM is For balanced load, the LC impedance is selected
lower. On the other hand, taking RLC_bal as the base value, Fig. conventionally to cope with the 1-sequence reactive current,
7 shows the required power rating ratio between unbalance thereby minimizing the inverter output voltage in 1-sequence
case and balance case for the CWTI-DSTATCOM. to achieve low dc-link voltage design [23]. Thus, according
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Stop
In (37), the voltages (vα and vβ) and currents (iα and iβ) in
Fig. 8. Flowchart of the proposed Cunbal design for unbalanced load. the α-β plane can be transformed from a-b–c frames by,
d m a x V in v 1 V in v 1 V in v 2 V in v 2 , a 2 V in v 1 V in v 1 a V in v 2 V in v 2 , a V in v 1 V in v 1 a 2 V in v 2 V in v 2 0 (33)
dC
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Source
v L c 0
-5
-10
i Vsa Vsb Vsc
i 2 1 1 2 1 2 La
i iLb (39)
Source
3 0 3 2 3 2
i L c
where vLx and iLx are the load voltage and current signals. 5
isa isb isc
Tap
0
reference value icx* applying the pulse-width modulation -2.5
(PWM) control method, the trigger signals for the active -5 Vca Vcb Vcc
inverter part can be generated to control the insulated gate
DC-link Compensation
voltage (kV) current (A)
bipolar transistors (IGBTs). Based on the above analysis, the
proposed overall control block of the CWTI-DSTATCOM is
ica icb icc
given in Fig. 10. In the proposed control, the parameters to be 9
measured by the sensors are the load voltage vLx, the load 6 VdcL
current iLx, the compensation current icx, and the dc-link 3
0
voltage Vdc. The implementation of this control scheme does 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14
not require additional sensors compared with the Time (s)
(a)
conventional WTI-STATCOM since the turn ratio Kx, and
Before After Compensation
winding tap ratio kx are settled and given in advance. 10
Compensation
voltage (kV) current (A) voltage (kV) current (A) voltage (kV)
iLa iLb iLc vLa vLb vLc 5
Source 0
-5
i v -10
i 2 1 1 2 1 2 La v 2 1 1 2 1 2 La Vsa Vsb Vsc
i iLb v vLb
3 0 3 2 3 0 3 2 3 2
iLc
3 2
Source
vLc
iα iβ
vα vca vLa
p v v i v K 3k 2 3k 1 v
kx isa isb isc
q v vβ cb Lb 5
v i vcc vLc K 2.5
Tap
LPF LPF
DC-link Compensation
c 3 0 3 2 3 2
p vcc
q
+
+
PI - -
dcp ~ p ~
q vcα vcβ
V. SIMULATION RESULTS 5
Source
0
In this section, the simulation case studies are provided to -5
-10
verify: a) the proposed CWTI-DSTATCOM can compensate Vsa Vsb Vsc
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
TABLE V Runbal /Rbal in simulation and in theory are almost the same,
SIMULATION RESULTS WITH =0.3 WHEN VSX=10KV, KX = 0.5 which verifies the feasibility of power rating calculation
Situations
Vdc Ph-
ISx (A)
QSx
PFSx
THD Loss formulas in Section II-D. Under this unbalanced load, for
(V) ase (kVAR) iSx(%) (%) (kW) CWTI-DSTATCOM based on conventional balanced LC
A 23.4∠-38.4 59.0 0.79 0
design, its dc-link voltage is reduced by 66.8%, and its VSI
Before comp. B 31.2∠-145.7 54.8 0.90 0 30
C 33∠76.9 91.7 0.73 0
power rating is about 1/3 of that of WTI-DSTATCOM. With
A 25.2∠0.4 0.5 1.00 4.9 the proposed unbalanced LC design, its dc-link voltage is
Coupling
L=10mH (WTI- 8300 B 25.1∠120.3 0.4 1.00 4.9 0.2 5.84 reduced approximately by 76.4%, and its VSI power rating is
DSTATCOM) C 25.2∠119.8 0.04 1.00 4.8 about 1/4.
A 23.5∠5.6 -9.8 0.994 9.7
Convention- 2000 B 26∠123.9 6.8 0.998 8.2 11.4 VI. EXPERIMENTAL RESULTS
al design C 21.2∠115.1 7.2 0.996 11.3
with In this section, the proposed CWTI-DSTATCOM and LC
A 23.6∠0.99 -1.9 1.00 1.7
L=10mH, filter design method for unbalance load have been verified in
C=25µF 2800 B 23.9∠121.5 2.2 1.00 2.0 2.7 2.57
a real-time digital simulator (RTDS) hardware-in-the-loop
Proposed topology
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
(d)
Fig. 13. Experimental performance before and after compensation by
applying (a) WTI-DSTATCOM at VdcL= 8300V; (b) CWTI-DSTATCOM
with conventional LC design at VdcLC= 2000V; (c) CWTI-DSTATCOM with
proposed LC design at VdcLC= 2800V; (d) CWTI-DSTATCOM with proposed
LC design with VdcLC= 2000V.
(a) (b)
compensation results reflect that it can well operate in Fig. 14. Investment costs of CWTI-DSTATCOM for the (a) balanced load;
balancing the load current and compensating reactive power (b) unbalanced load.
at a 2000V dc-link voltage. All in all, compared with
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
B. Power Loss Case Study [9] O. P. Mahela and A. G. Shaik, “A review of distribution static
compensator,” Renew. Sustain. Energy Rev., vol. 50, pp. 531–546,
Less dc-link voltage means less power loss. According to May. 2015.
the power loss studies [36], [37], the a) switching loss and b) [10] B. Singh, P. Jayaprakash, D. P. Kothari, A. Chandra and K. Al Haddad,
component conduction loss contribute to the major power “Comprehensive study of DSTATCOM configurations,” IEEE Trans.
Ind. Informat., vol. 10, no. 2, pp. 854-870, May 2014.
loss of the proposed structure. [11] C. O. Gercek and M. Ermis, “Elimination of coupling transformer core
a) Switching Loss saturation in cascaded multilevel converter-based T-STATCOM
The switching loss is influenced by the collector-emitter systems,” IEEE Trans. Power Electron., vol. 29, no. 12, pp. 6796–
voltage and current of each IGBT, which can be classified as 6809, Dec. 2014.
[12] M. Vijeh, M. Rezanejad, E. Samadaei and K. Bertilsson, “A general
turn-on and turn-off losses. (42) is the total turn-on and turn- review of multilevel inverters based on main submodules: structural
off power losses. point of view,” IEEE Trans. Power Electron., vol. 34, no. 10, pp.
1 I 1 1 I CM 9479-9502, Oct. 2019.
Plo ss sw V d c I lo ss V d c I C M f sw t o n C M t o ff (42)
8 2 4 I C N [13] J. Falck, C. Felgemacher, A. Rojko, M. Liserre and P. Zacharias,
I CN 3
“Reliability of power electronic systems: An industry perspective,”
where Vdc, ICM, ICN, ton, toff, and fsw are the dc-link voltage, IEEE Ind. Electron. Mag., vol. 12, no. 2, pp. 24-35, Jun. 2018.
maximum collector current, rated collector current, rated rise [14] S. J. Hu et al., “A new integrated hybrid power quality control system
time, rated fall time, and switching frequency, respectively. for electrical railway,” IEEE Trans. Ind. Electron., vol. 62, no. 10, pp.
6222–6232, Oct. 2015
Thus, the higher Vdc of the WTI-STATCOM and CWTI- [15] C. Wang, X. Yin, Z. Zhang, and M. Wen, “A novel compensation
STATCOM, the higher the switching losses are obtained and technology of static synchronous compensator integrated with
vice versa. distribution transformer,” IEEE Trans. Power Del., vol. 28, no. 2, pp.
b) Component Conduction Loss 1032–1039, Apr. 2013.
[16] Y. Li, L. Luo, C. Rehtanz, S. Rüberg, and D. Yang, “An industrial DC
For WTI-DSTATCOM and CWTI-DSTATCOM, the power supply system based on an inductive filtering method,” IEEE
component conduction power losses can be expressed as (43) Trans. Ind. Electron., vol. 59, no. 2, pp. 714–722, Feb. 2012.
and (44). [17] Y. Li et al., “A virtual impedance comprehensive control strategy for
2 (43) the controllably inductive power filtering system,” IEEE Trans.
Ploss ( L ) E S R L I cx
Power Electron., vol. 32, no. 2, pp. 920–926, Feb. 2017.
2
Ploss ( L C ) E S R L I cx 2
E S R C I cx (44) [18] Q. Liu, Y. Li, S. Hu, and L. Luo, “Power quality improvement using
controllable inductive power filtering method for industrial DC supply
where ESRL (=0.18Ω) and ESRC (=0.33Ω) are equivalent system,” Control Eng. Pract., vol. 83, pp. 1–10, Feb. 2019.
series resistance of coupling inductor L, coupling capacitor C. [19] Y. Li, T. K. Saha, O. Krause, Y. Cao and C. Rehtanz, “An inductively
active filtering method for power-quality improvement of distribution
Based on the above analysis, the total power losses of WTI- networks with nonlinear loads,” IEEE Trans. Power Del., vol. 28, no.
STATCOM and CWTI-STATCOM are shown in Table V and 4, pp. 2465-2473, Oct. 2013.
Table VII. It shows that the total power loss of the proposed [20] Q. Liu, Y. Li, L. Luo, Y. Peng, and Y. Cao, “Power quality
CWTI-STATCOM is much lower than that of WTI- management of PV power plant with transformer integrated filtering
method,” IEEE Trans. Power Del., vol. 34, no. 3, pp. 941–949, Jun.
STATCOM. 2019.
[21] Chi-Seng Lam and Man-Chung Wong, “Investigation of a novel
REFERENCES capacitive-coupled STATCOM: modeling and simulation.” IEEE
[1] M. S. Golsorkhi, D. J. Hill, and M. Baharizadeh, “A secondary control 43rd UPEC 2008, Sept. 2008.
method for voltage unbalance compensation and accurate load sharing [22] Chi-Seng Lam, Fan Ng, Man-Chung Wong, “Control scheme of a
in networked microgrids,” IEEE Trans. Smart Grid, vol. 12, no. 4, pp. novel capacitive-coupled STATCOM,” IEEE 43rd UPEC 2008, Sept.
2822–2833, Jul. 2021. 2008.
[2] R. Kalpana, K. S. Chethana, S. P. P, and B. Singh, “Power quality [23] L. Wang, C. S. Lam, and M. C. Wong, “A hybrid STATCOM with
enhancement using current injection technique in a zigzag configured wide compensation range and low dc-link voltage,” IEEE Trans. Ind.
autotransformer-based 12-pulse rectifier,” IEEE Trans. Ind. Appl., vol. Electron., vol. 63, no. 6, pp. 3333–3343, Jun. 2016.
54, no. 5, pp. 5267–5277, Sep./Oct. 2018. [24] Y. Li, F. Liu, T. K. Saha, O. Krause, and Y. Cao, “Hybrid inductive
[3] K. K. Prasad, H. Myneni, and G. S. Kumar, “Power quality and active filtering method for damping harmonic resonance in
improvement and PV power injection by DSTATCOM with variable distribution network with non-linear loads,” IET Power Electron., vol.
DC link voltage control from RSC-MLC,” IEEE Trans. Sustain. 8, no. 9, pp. 1616–1624, Sep. 2015.
Energy, vol. 10, no. 2, pp. 876–885, Apr. 2019. [25] Y. Li et al., “A controllably inductive filtering method with
[4] M. N. Slepchenkov, K. M. Smedley, and J. Wen, “Hexagram- transformer integrated linear reactor for power quality improvement
converter-based STATCOM for voltage support in fixed-speed wind of shipboard power system,” IEEE Trans. Power Del., vol. 32, no. 4,
turbine generation systems,” IEEE Trans. Ind. Electron., vol. 58, no. pp. 1817–1827, Aug. 2017.
4, pp. 1120–1131, Apr. 2011. [26] Q. Liu, Y. Li, S. Hu and L. Luo, “A transformer integrated filtering
[5] G. Levitin, A. Kalyuzhny, A. Shenkman, and M. Chertkov, “Optimal system for power quality improvement of industrial DC supply
capacitor allocation in distribution systems using a genetic algorithm system,” IEEE Trans. Ind. Electron., vol. 67, no. 5, pp. 3329-3339,
and a fast energy loss computation technique,” IEEE Trans. Power May 2020.
Del., vol. 15, no. 2, pp. 623–628, Apr. 2000. [27] B. Xie, Z. Zhang, S. Hu, Y. Li, L. Luo, and S. Sun, “YN/VD connected
[6] Y. Li, T. K. Saha, O. Krause, Y. Cao, and C. Rehtanz, “An inductively balance transformer‐based electrical railway negative sequence
active filtering method for power-quality improvement of distribution current compensation system with passive control scheme,” IET
networks with nonlinear loads,” IEEE Trans. Power Del., vol. 28, no. Power Electronics, vol. 9, no. 10, pp. 2044–2051, Aug. 2016.
4, pp. 2465–2473, Oct. 2013. [28] Z. Zhang et al., “Reactive power compensation and negative-sequence
[7] S. X. Chen, Y. S. Foo. Eddy, H. B. Gooi, M. Q. Wang, and S. F. Lu, current suppression system for electrical railways with YNvd-
“A centralized reactive power compensation system for LV distribution connected balance transformer—Part I: Theoretical analysis,” IEEE
networks,” IEEE Trans. Power Syst., vol. 30, no. 1, pp. 274–284, Jan. Trans. Power Electron., vol. 33, no. 1, pp. 272–282, Jan. 2018.
2015. [29] S. Hu et al., “A Y-D multifunction balance transformer-based power
[8] Q. Liu, Y. Li, S. Hu and L. Luo, “A transformer integrated filtering quality control system for single-phase power supply system,” IEEE
system for power quality improvement of industrial DC supply Trans. Ind. Appl., vol. 52, no. 2, pp. 1270–1279, Mar./Apr. 2016.
system,” IEEE Trans. Ind. Electron., vol. 67, no. 5, pp. 3329-3339, [30] E. Lei, X. Yin, Z. Zhang, and Y. Chen, “An improved transformer
May 2020. winding tap injection DSTATCOM topology for medium-voltage
reactive power compensation,” IEEE Trans. Power Electron., vol. 33,
no. 3, pp. 2113–2126, Mar. 2018.
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
[31] Y. Chen et al., “Passivity-based control of cascaded multilevel a Lecturer and an Assistant Professor in 1997 and 2008, respectively.
converter based D-STATCOM integrated with distribution His current research interests include power electronics’ controllers,
transformer,” Elect. Power Syst. Res., vol. 154, pp. 1–12, 2018. power system analysis, power quality compensators, and renewable
[32] Z. Wang, X. Yin, Y. Chen, J. Lai, L. Li, and Z. Qi, “DSTATCOM energy.
integrated with Y-y connection transformer for reactive power Dr. Wong has been an IEEE Student Branch Officer since 1997.
compensation,” Int. J. Electr. Power Energy Syst., vol. 117, p. 105721, He is currently the Vice-Chair of IEEE Macau Section and the
May 2020. Committee Member of IEEE Macau PES/PELS Joint Chapter.
[33] M.-C. Wong, Y. Pang, Z. Xiang, L. Wang, and C.-S. Lam, “Assessment
of active and hybrid power filters under space vector modulation,” Lei Wang (SM’20) received the B.Sc. degree
IEEE Trans. Power Electron., vol. 36, no. 3, pp. 2947–2963, Mar. 2021. in Electrical and Electronics Engineering
[34] IEEE recommended practices and requirements for harmonic control from University of Macau (UM), Macao SAR,
in electrical power systems, IEEE standard 519-2014, 2014. P. R. China, in 2011, M.Sc. degree in
[35] L. M. Tolbert, et al., “Power electronics for distributed energy systems Electronics Engineering from Hong Kong
and transmission and distribution applications: Assessing the technical University of Science and Technology
needs for utility applications,” Oak Ridge Nat. Lab., Oak Ridge, TN, (HKUST), Hong Kong SAR, P. R. China, in
USA, Tech. Rep. ORNL/TM-2005/230, Dec. 2005. 2012. and Ph.D. degree in Electrical and
[36] E. Serban; C. Pondiche; and M. Ordonez, “Modulation effects on Computer Engineering from UM, Macao SAR,
power-loss and leakage current in three-phase solar inverters,” IEEE P. R. China, in 2017.
Trans. Energy Convers., vol. 34, no. 1, pp. 339-350, Jan. 2019. He was a postdoctoral fellow in the Power
[37] L. Wang, C.-S. Lam, and M.-C. Wong, “Minimizing inverter capacity Electronics Laboratory of UM from Jan. 2017 to Feb. 2019. He was a
design and comparative performance evaluation of SVC-coupling visiting fellow in department of electrical and computer engineering,
hybrid active power filters,” IEEE Trans. Power Electron., vol. 34, no. University of Auckland, from Feb. 2019 to Aug. 2019. In 2019, he
2, pp. 1227–1242, Feb. 2019. joined College of Electrical and Information Engineering, Hunan
University, Changsha, China, where he is currently a Full Professor.
Ziyi Bai received the B.Sc. degree in He has authored 1 Springer books, 1 Elsevier book chapter, 5
electrical engineering from Hainan patents (U.S.A and China) and over 30 journal and conference papers.
University, Haikou, China, in 2016, and the Dr. Wang received the champion award in the “Schneider Electric
M.Sc. degree in electrical engineering from Energy Efficiency Cup”, Hong Kong, 2011, Macao Science and
Hunan University, Changsha, China, in 2019. Technology R&D Award for Postgraduates (Ph.D) in 2018.
She is currently pursuing the Ph.D. degree in
electrical and computer engineering with the Chi-Seng Lam (Senior Member, IEEE)
State Key Laboratory of Internet of Things for received the Ph.D. degree in electrical and
Smart City, University of Macau, Macau, electronics engineering from the University
China. Her research interests include power of Macau (UM), Macao, China, in 2012. He
quality, smart grid, renewable energy, and completed the Clare Hall Study Programme
distributed generation. at the University of Cambridge, Cambridge,
U.K., in 2019. From 2006 to 2009, he was an
Ying Pang (S’19) received the B.Sc. degree Electrical and Mechanical Engineer with UM.
in electrical engineering from Southwest From 2009 to 2012, he simultaneously
Jiaotong University, Chengdu, China, in worked as a Laboratory Technician at UM,
2015, and the M.Sc. degree in electrical and and pursued his Ph.D. degree in part-time at UM. In 2013, he was a
computer engineering from the University of Post-Doctoral Fellow with The Hong Kong Polytechnic University,
Macau, Macao, in 2018, where he is Hong Kong, China. He is currently an Associate Professor with the
currently pursuing the Ph.D. degree in State Key Laboratory of Analog and Mixed-Signal VLSI and the
electrical and computer engineering with the Institute of Microelectronics, UM, and also with the Department of
State Key Laboratory of Internet of Things for Electrical and Computer Engineering, Faculty of Science and
Smart City. His research interests include Technology, UM. He has coauthored or co-edited four books and
power filter, smart grid, renewable energy,
more than 110 technical journals and conference papers. He holds
and distributed generation.
four U.S. and two Chinese patents. His research interests include
power quality compensators, renewable energy generation,
Zeng Xiang (Member, IEEE) received the integrated power electronics controllers, power management
B.Sc. degree in Electrical Engineering and integrated circuits, and wireless power transfer.
Automation from Tianjin University of
Dr. Lam serves/served as a member for the Organizing Committee
Science & Technology, in 2009, Tianjin,
or Technical Program Committee of IEEE international conferences,
China. He received his M.Sc. degree in
Electronic Engineering from Hunan including IECON 2020, IECON 2019, ASSCC 2019, APPEEC 2019,
University, in 2012, Changsha, China. IECON 2018, IESES 2018, ASP-DAC 2016, and TENCON 2015. He
From 2012 to 2015, he was an R&D was a recipient or corecipient of the IEEE PES Chapter Outstanding
engineer in Zhuhai Wanlida Electrical Engineer Award in 2016, the Best Track Paper Award of APPEEC
Automation Co., Ltd., Zhuhai, China. 2019, the Best Paper Award of ICTA 2019, the Merit Paper Award of
He is currently working toward the Ph.D. the 3rd RIUPEEEC Conference in 2005, the Macao Science and
degree in Electrical and computer engineering with State Key Technology Invention Award (Second Class and Third Class) and the
Laboratory of Internet of Things for Smart City, University of Macau, Research and Development Award for Postgraduates (Ph.D.) in 2018,
Macau. His research interests include high-performance converters 2014, and 2012, respectively. He was the Vice-Chair of the IEEE
for microgrids, power quality, and distributed power generation Macau Section from 2016 to 2020 and the Chair of the IEEE Macau
system. CAS Chapter from 2017 to 2018. He is currently the Chair of the IEEE
Macau IES Chapter and the Power Quality Subcommittee Chair of the
Chi-Kong Wong (Member, IEEE) received IEEE IES Technical Committee on Power Electronics. He serves as
the B.Sc. and M.Sc. degrees in electrical and an Associate Editor for IEEE Transactions on Industrial Electronics
electronics engineering from the University of and IEEE Access, and a Guest Editor for the IEEE Transactions on
Macau (UM), Macao, China, in 1993 and Circuits and Systems II: Express Briefs and the IET Power Electronics
1997, respectively, and the Ph.D. degree in in 2020.
electrical engineering from Tsinghua
University, Beijing, China, in 2007.
Since 1993, he has been a Teaching
Assistant with the Faculty of Science and
Technology, UM, where he was promoted as
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2022.3156042, IEEE
Transactions on Industrial Electronics
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
0278-0046 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on March 15,2022 at 07:48:43 UTC from IEEE Xplore. Restrictions apply.