BIKANER, RAJASTHAN
22111-CV-DWG-0294
Drawing/ Doc Title
Rev No. 0
Date: 1/23/2023
Transmittal: TATA-TCE-WTRAN-002829
1 Please mention SOP Doc No Noted and updated. Load testing is as per IS 2911.4.Kindly refer revised document.
2 Please define failure criteria separately for each type of test Noted and updated. Please refer Cl.no. D (1).Kindly refer revised document.
3 Please revise as per code requirement. Noted.
Please refer Pile Testing Layout for varying depths considered for both cases.
For seven different depths (1.7m, 1.85m, 2m, 2.2m, 2.4m, 2.7m & 3m depths) both 0.15m & 1.35m
4 Kindly specify which pile has 1.35m & which pile has 0,15m? loading distance is considered.
As per discussion with Client, half pile nos. are being tested for 0.15m & other half for 1.35m.
Kindly refer revised document.