Test procedure: AMS Handling of Engine Process Values.


Applicable to MAN/ES 2 stroke ME engines with Triton and MPC controllers.

MAN-ES strongly recommend performing below test to verify that AMS will react
according to design in case no information is received from EMS.
The test is to verify that AMS will not raise alarm, slowdown or shutdown based on
missing EMS data. It is done by disrupting the EMS-AMS Modbus.

The data flow is as shown below with the red line.

Figure 1 Data flow: ECS MOP-B ->EMS MOP -> AMS


In case ECS MOP-B, EMS MOP, managed switch or any of the network cables fail, the
data flow will be interrupted. EMS-AMS Modbus will send “+32767” signifying #Bad
Value for affected Modbus registers; however, they must not result in Out of Range
Alarms (OoR) in AMS.
MAN Energy Solutions MAN PrimeServ PRODUCTION FORWARDING & RECEIVING MAN Energy Solutions
Teglholmsgade 41 Teglholmsgade 41 Teglholmsgade 35 Teglholmsgade 35 Branch of MAN Energy Solutions SE,
2450 Copenhagen SV 2450 Copenhagen SV 2450 Copenhagen SV 2450 Copenhagen SV Germany
Denmark Denmark Denmark Denmark CVR No.: 31611792
P +45 33 85 11 00 P +45 33 85 11 00 P +45 33 85 11 00 Head office: Teglholmsgade 41
P +45 33 85 11 00 F +45 33 85 10 49 F +45 33 85 10 17 F +45 33 85 10 16 2450 Copenhagen SV
F +45 33 85 10 30 PrimeServ-cph@man-es.com manufacturing-dk@man-es.com shipping-cph@man-es.com Denmark
info-cph@man-es.com German Reg.No.: HRB 22056
www.man-es.com Amtsgericht Augsburg
-2-

Test steps:
At a convenient and safe location while operating Engine at low load, but above
slowdown limit:
1. Conduct following tests separately followed by Verification steps 2.1-3:
1.1. disconnect LAN cable 󠆯from port / MOP-B
1.2. disconnect LAN cable from port / PMI DAU
1.3. Power off the EMS computer
2. Confirm that:
2.1. no slowdown or shutdown is requested/activated by AMS
2.2. no alarms – Process value, OoR or any other type alarms are raised in AMS.
Only Acceptable AMS Alarm is one for EMS communication loss.
2.3. values missing in AMS monitoring are indicated:
As missing such as “---“, “N/A”, 󠆯“OoR” 󠆯etc. 󠆯
Not 󠆯as 󠆯physical 󠆯values 󠆯such 󠆯as 󠆯“3276.7 󠆯°C”, 󠆯“327.67 󠆯bar” 󠆯or 󠆯“327.7 󠆯g/kWh” 󠆯etc.

In case above test cause slowdown or shutdown, it is an indication that AMS is not
configured correctly. If assistance from MAN-ES is needed in this respect, please
contact MAN-ES at: OperationControlandElectronics2S@man-es.com

Best regards