Calculation Sheet for

Equipment 1 Foundation

CONTRACT NO. : 032/CNI-EFNI-PP/X/2019


PROJECT CODE : 719002
DOCUMENT NO. : CAL-1-012-C-0012
PURPOSE : FOR APPROVAL
CONTRACTOR :

REV. NO. DATE DESCRIPTION PREPARED CHECKED APPROVED

A 5/12/2022 IFA DP AM / MTD ST


PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV : A

REVISION CONTROL SHEET

REV NO. DATE DESCRIPTION


0 5/12/2022 ISSUED FOR INFORMATION

DISTRIBUTION ORDER

EXTERNAL DISTRIBUTION PT PP (PERSERO) TBK - INTERNAL DISTRIBUTION


x PT. CERIA NUGRAHA x PROJECT MANAGER o OTHERS
INDOTAMA
x ENGINEERING MANAGER
o CONSTRUCTION MANAGER
o PROCUREMENT MANAGER
o ADMINISTRATION MANAGER
o SHE MANAGER
o QC MANAGER
o PROJECT CONTROL
o PROJECT MANAGER
PROJECT CODE : 719002
Calculation Sheet for
DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation DATE : 5/12/2022
Calculation REV :A

TABLE OF CONTENTS Page Number


Revision History

1.2 SHALLOW FOUNDATION


[A] Material Data
[B] Geometri data
[C] Check for Stability againts sliding & overtuning
[D] Check for Moment and One way Shear in Z direction
[E] Check for Punching Shear
[F] Check Setlement

1.3 Result
[A] Sletch
[B] Interaction Curve

1.4 REFERENCES
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV :A
Foundation Mkd. Node 1 #REF!
MATERIAL DATA:
Grade of Concrete f'c (cylinder strength)= 29 N/mm2
2
Yield Strength of reinforcement, fy = 480 N/mm
Bot. reinf. dia in direction of L & spacing = 16 mm @ 200 mm
Bot. reinf. dia in direction of B & spacing = 16 mm @ 200 mm
Top reinf. in both direction dia & spacing = 16 mm @ 200 mm
Clear Cover to Reinforcement = 50 mm
3
Unit Weight of Concrete 24 KN/m
3
Unit Weight of Soil = 16,7 KN/m
3
Unit Weight of Backfill = 18 KN/m
Net allowable bearing pressure = 123 KN/m2
O
Internal angle of friction f of soil = 32 (Refer soil report )
Coeff. of friction bet. conc and soil, tan(2/3*f) = 0,35
Load factor for S/w and Soil wt = 1,2
Factor of safety against overturning = 1
Factor of safety against sliding = 1 (For passive considered) = 1,5
Factor of safety against Uplift = 1,25
Number of Load Combinations 7 nos
Depth of Water table from Ground = 7 m (no water table encountered)

GEOMETRICAL DATA :
Footing Slab & Pedestal +ve direction of support reactions
FY
Z
Y
FX
ezp
FZ X
exp lo
X CB B
Z (Water Table)

CL H
D

L L

Width of Footing, B = 1,50 m Width of Pedestal, CB = 0,60 m


Length of Footing, L = 1,50 m Length of Pedestal, CL = 0,60 m
Embedment depth, H = 1,00 m Thickness of Footing, D = 0,50 m
Height of Pedestal, lo = 0,80 m Projection of pedestal above ground = 0,3 m
Ecc. about Z axis,ezp = 0,00 m Ecc. about X axis, exp = 0,00 m

Shearkey : Notrequired
Not required

LOAD DATA (+ve value of FY implies compression in Pedestal)


(a) Load for Stability
JOINT L/C FY FX FZ MX MZ

1 111 124 0,42884625 0 0 0,536057813

(b) Ultimate load combination for concrete design.


JOINT L/C FY FX FZ MX MZ

1 235 148,8 15,4344 0 0 19,293

(c) Load combination for bearing pressure check:.


JOINT L/C FY FX FZ MX MZ

1 111 124 0,42884625 0 0 0,536057813

1. CHECK FOR STABILITY AGAINST SLIDING AND OVERTURNING


(a) Uplift Chcek:
P= Footing weight + Pedestal weight +Soil weight- Buoyant force 49,69 kN
Uplift force, Fu = 0,00 kN
F.O.S. against Uplift = N.A No Uplift

(b) Sliding check :


Coeff. of passive earth pressure, Kp = 3,255
Sliding force in X direction, FX = 0,43 kN
Sliding force in Z direction , FZ = 0 kN
Resultant of sliding force,Fr = 0,429 kN
Angle the resultant acting w.r.t X dir, q = 0,0 degree
Passive force on slab edge, Fpsx = 0,00 kN (Along X)
Passive force on slab edge , Fpsz = 0,00 kN (Along Z)
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV :A
Passive force on shearkey, Fpx = 0,00 kN
Passive force on shearkey, Fpz = 0,00 kN
Total passive in X direction, Px = 0,00 kN
Total passive in Z direction, Pz = 0,00 kN
Resultant of passive in q angle w.r.t X = 0,00 kN #NAME?
P= FY+Footing weight + Pedestal weight +Soil weight- Buoyant force
= 173,69 kN
Resisting frictional force = P*m = 60,79 kN

F.O.S. against sliding = 141,76 >1, Safe

Shearkey requirement = No

(d) Overturning about Z axis


Forces acting at bottom of footing about Z
FY = 124,00 kN
MZtot = (MZ +FX*(lo+D)) = 1,09 kN-m #NAME?
Self Weight of Foundation = 27 kN #NAME?
Weight of Pedestal, Pwt = 6,91 kN #NAME?
Weight of Backfill = 17,01 kN #NAME?
Buoyancy force = 0,00 kN

0,3 Taking moment about P


Overturning moment due to eccentricity =
0,50 0,00 kN-m
Overturning moment = MZtot =
1,09 kN-m

P
0,75
Total overturning moment 1,09 kN-m #NAME?

Restoring Moment 131,19 kN-m

F.O.S against overturning = restoring mom/overturning mom = 119,97 >1, Safe

(e) Overturning about X axis


Forces acting at bottom of footing about X
FY = 124,00 kN
MXtot = (MX +FZ*(lo+D)) = 0,00 kN-m #NAME?
Self Weight of Foundation = 27,00 kN #NAME?
Weight of Pedestal,Pwt = 6,91 kN #NAME?
Weight of Backfill = 17,01 kN #NAME?
Buoyancy force = 0,00 kN

0,3
0,50 Taking moment about P
Overturning moment due to eccentricity =
0 kN-m

P Overturning Moment = MXtot


0,75 0,00 kN-m

Total overturning moment = 0,00 kN-m


Restoring Moment = 131,19 kN-m

F.O.S against Overturning = restoring Moment / over turning Moment = N.A. >1, Safe

2. CHECK FOR NET BEARING PRESSURE

Gross vertical load PY = FY+ Weight of Footing including pedestal+ Weight of back fill = 174,92 kN
Total Moment about X = MXtot = MX+ FZ(lo+D)+(Fy+Pwt)*exp = 0,00 #NAME?
Total Moment about Z = MZtot = MZ+ FX(lo+D)+(Fy+Pwt)*ezp = 1,09 #NAME?

ex = MZtot/PY = 0,01 M e<L/6, No Tension in footing. #NAME?


ez = MXtot/PY = 0,00 M e<B/6, No Tension in Footing. #NAME?

Gross pressure distribution under footing is given by:

q= P Y
(1 
6e x 6e Z
 )
LB L B
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV :A
LB L B

= 79,69 75,80 79,69 75,80 Kn/m2 p4 p3


p1 p2 p3 p4 +Mx
Mx
(If there is negative gross pressure then it will be corrected
using Teng's Chart) p2 Mz p1
ex/L = 0,0042 ez/B = 0,0000
Sign Convention
From Teng's chart value of k = 1,025

2
Maximum Gross Pressure = K*P/BL = 79,69 KN/m #NAME?
Net pressure intensities under the footing is given by:
p1net = 62,99 KN/m2 p3net = 62,99 KN/m
2

2 2
p2net = 59,10 KN/m p4net = 59,10 KN/m
2
Maximum net pressure intensity = 62,99 KN/m < 123 kN/sq.m, Safe
#NAME?

3. CHECK FOR MOMENT AND SHEAR

Net pressure generated below footing due to ultimate load.

Gross vertical load PY = FY+ Weight of Footing including pedestal+ Weight of back fill = 209,91 kN
Total Moment about X = MXtot = MX+ FZ(lo+D)+(Fy+Pwt)*exp = 0,00 #NAME?
Total Moment about Z = MZtot = MZ+ FX(lo+D)+(Fy+Pwt)*ezp = 39,36 #NAME?

ex = MZtot/PY = 0,19 M e<L/6, No Tension in footing. #NAME?


ez = MXtot/PY = 0,00 M e<B/6, No Tension in Footing. #NAME?

Gross pressure distribution under footing is given by:

q= P Y
(1 
6e x 6e Z
 )
LB L B

= 163,26 23,32 163,26 23,32 Kn/m


2 p4 p3
p1 p2 p3 p4 +Mx
Mx
(If there is negative gross pressure then it will be corrected
using Teng's Chart) p2 Mz p1
ex/L = 0,13 ez/B = 0,00
Sign Convention
From Teng's chart value of k = 1,750

2
Maximum Gross Pressure = K*P/BL = 163,26 KN/m #NAME?
Net pressure intensities under the footing is given by:
p1net = 143,22 KN/m2 p3net = 143,22 KN/m2
2 2
p2net = 3,28 KN/m p4net = 3,28 KN/m
2
Max. net pressure intensity (fac)= 143,22 KN/m #NAME?

(a) Check for Moment and One way Shear in X direction 1 2

1 2

P2-4 =
d
3,28 P1-3 =
101,24 142,47 143,22 ( d= D-50-8 = 442 mm )
FACTORED PRESSURE DISTRIBUTION AT SALIENT POINTS CRITICAL SECTIONS FOR MOMENT AND SHEAR.

Refer Cl.11.2.1.1 of ACI 318M-14


Shear at critical section 2: Vu = 1,71 kN
Strength reduction factor, f = 0,75 Refer Cl 9.3.2.3 of ACI 318M-2014

Modification factor, l = 1,00 Refer Cl 8.6.1 of ACI 318M-2014

V   0.17 f 'c dB  455,22 kN 455,2 kN >1,7 kN,Hence OK


PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV :A
Bottom Reinf. Refer Cl 10.2.7, 10.3.1, 10.3.2 & 10.3.3 of ACI 318M-2014
Moment at the Critical section 1: Mu= 19,63 kN-m #NAME?

Strength reduction factor, fm = 0,9 Refer Cl 9.3.2.1 of ACI 318M-2014


ec =0.003 0.85f'c
Ts = Cc ………………… (i)
Cc =0.85f'c*a*B
Mu =fmTs(d-a/2)………… (ii) c a

Assume

(d-a/2)
m  fy 0.85 f ' c   19,47
Ru  M u m Bd 2   0,07
es Ts=Ast*fy
Solving equations (i) & (ii) for steel ratio
r =Ast/Bd
1 2mRu 
  1  1   0,00016 Strain, Stress & Internal Force Diagram
m  f y 
Required steel = 103 mm2
2
Minimum Reinforcement 0.09% = 675 mm Refer Cl 7.12.2.1 of ACI 318M-2014
Reqd. Spacing of 16 mm dia bar = 447 mm
Provided Spacing = 200 mm Ast,provided 1508 mm2

Top Reinf. Refer Cl 10.2.7, 10.3.1, 10.3.2 & 10.3.3 of ACI 318M-2014

Moment due to overburden soil & selfweight of footing, Mu = 3,71 kN-m #NAME?
Ru  M u m Bd 2   0,014
1 2mRu 
 1  1   0,00003
m  f y 
2
Required steel = 19 mm
2
Minimum Reinforcement 0.09% = 675 mm Refer Cl 7.12.2.1 of ACI 318M-2014
Bar Dia = 16 mm
Required spacing = 447 mm
Provided Spacing = 200 mm Ast,provided 1508 mm2

(b) Check for Moment and One way Shear in Z direction

1 2
1
d 2
3

P3-4 =
143,22 143,22 143,22 P1-2 = ( d= D-50-16-8 = 426 mm )
143,22
FACTORED PRESSURE DISTRIBUTION AT SALIENT POINTS CRITICAL SECTIONS FOR MOMENT AND SHEAR.

Refer Cl.11.2.1.1 of ACI 318M-14


Shear at critical section 2: 5,16 kN
Strength reduction factor, f = 0,75 Refer Cl 9.3.2.3 of ACI 318M-2014
Modification factor, l = 1,00 Refer Cl 8.6.1 of ACI 318M-2014
V   0.17 f 'c dL  438,74 kN 438,7 kN >5,2 kN,Hence OK

Bottom Reinf. Refer Cl 10.2.7, 10.3.1, 10.3.2 & 10.3.3 of ACI 318M-2014
Moment at the Critical section 1:Mu = 21,75 kN-m #NAME?

Strength reduction factor, fm = 0,9 Refer Cl 9.3.2.1 of ACI 318M-2014

Ts = Cc ………………… (i) ec =0.003 0.85f'c


Mu =fmTs(d-a/2)………… (ii) Cc =0.85f'c*a*L
c a
Assume
(d-a/2)

m  f y 0.85 f ' c   19,47


Ru  M u  m Ld 2   0,089
es Ts=Ast*fy
Solving equations (i) & (ii) for steel
r =Ast/Ld
1 2mRu  0,000185
 1  1   Strain, Stress & Internal Force Diagram
m  f y 
2
Required steel = 118 mm
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV :A
Minimum Reinforcement 0.09% = 675 mm2 Refer Cl 7.12.2.1 of ACI 318M-2014
Reqd. Spacing of 16 mm dia bar = 447 mm
Provided Spacing = 200 mm Ast,provided 1508 mm2

Top Reinf. Refer Cl 10.2.7, 10.3.1, 10.3.2 & 10.3.3 of ACI 318M-2014

Moment due to overburden soil & selfweight of footing, Mu = 3,71 kN-m


Ru  M u  m Ld 2   0,015

1 2mRu 
 1  1   0,000032
m  f y 
2
Required steel = 20 mm
Minimum Reinforcement 0.09% = 675 mm2 Refer Cl 7.12.2.1 of ACI 318M-2014
Bar Dia = 16 mm
Required spacing = 447 mm
Provided Spacing = 200 mm Ast,provided 1508 mm2

(c) Check for Punching Shear


(Refer Cl. 11.11.7.2 of ACI 318M-08)

Effective depth, d = 426 mm d/2

Effective Vertical Load causing punching = b0


(Considered as zero in case there is uplift)
148,8 + 0,6 x 0,6 x 0,8 x 24 x 1,2 = 157,094 kN d/2
Effective Moments at Pedestal Base
Mux = 0 + 0,000 x 0,8 =
0,00 kN-m
Muz = 19,293 + 15,4344 x 0,8 =
31,64 kN-m
For Base Moment about X
c1 = 600 mm
c2 = 600 mm
Ac = 2 x 426 ( 600 + 600 + 2 x 426 ) =
1748304 Sq. mm
Jcx = 426 x { ( 600 + 426 ) ^ 3 } / 6
+ ( 426 ^ 3 ) x ( 600 + 426 ) / 6
+ 426 x ( 600 + 426 ) x { ( 600 + 426 ) ^ 2 } / 2 =
4
319952744280 mm
For Base Moment about Z
c1 = 600 mm
c2 = 600 mm
Ac = 2 x 426 ( 600 + 600 + 2 x 426 ) =
1748304 Sq. mm
Jcz = 426 x { ( 600 + 426 ) ^ 3 } / 6
+ ( 426 ^ 3 ) x ( 600 + 426 ) / 6
+ 426 x ( 600 + 426 ) x { ( 600 + 426 ) ^ 2 } / 2 =
4
319952744280 mm
gv = ( 1 - gf ) [ Refer Cl. 11.11.7.1
& Cl. 13.5.3 of ACI 318M-08 ]
gf = 1 / [ 1 + (2/3)*( b1 / b2 ) ^ 0.5 ]
Hence,
gvx = 0,4
gvz = 0,4
Maximum Punching Shear Stress due to Vertical Load and Biaxial Moment =
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV :A
[ Refer Cl. R11.11.7.2 of ACI 318M-08 ]
[ 157094 - { 157094 / ( 1500 x 1500 ) } x { ( 600 + 426 ) x ( 600 + 426 ) } ] / 1748304
+ 0,400 x 0 x 513 / 319952744280
+ 0,400 x 31640520 x 513 / 319952744280
= 0,048 + 0,000 + 0,020
= 0,068 N / Sq. mm

Refer Cl 11.11.2.1 of ACI 318M-2014


Effective depth, d = 426 mm
b = (long side /short side) of col = 1,00
l= 1,00
Perimeter of critical section, b0 = 4104 mm
(i) Vc  0.171  2  f ' c  2,7 N/mm2
b0 d  

For edge coulmn, as = 30


Vc  d  2 f '  2
(ii)  0.083  s  2,3 N/mm
b0d  b0 
c

Vc 1,78 N/mm2
(iii)  0.33 f 'c 
b0d
Reduction factor for shear, fs = 0,75 Refer Cl 9.3.2.3 of ACI 318M-2014
Allowable Shear Stress = 1,333 N/mm2 fs x Smallest value of (i), (ii) and (iii)

Developed shear stress = 0,068 N/mm2 < 1,333N/sq.mm, Hence Ok


PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV : A
1.3.4 Foundation Settlement Check

Elastic/Immediate Settlement of Foundation

Se = qo B (1-μs2) / Es Ip (Sect. 10.2 Ref 2.4.1)

where :
Se : elastic settlement of foundation
qo : applied net pressure
B : width of foundation
μs : poisson's ratio of soils
: 0,3
Es : modulus elasticity of soils
Ip : nondimensional influence factors (see table below)

Table Ip Factors
Ip
Shape Flexible
L/B Rigid
Center Corner
Circle - 1 0,64 0,79
1 1,12 0,56 0,88
1,5 1,36 0,68 1,07
2 1,53 0,77 1,21
3 1,78 0,89 1,42
Rectangle 5 2,1 1,05 1,70
10 2,54 1,27 2,10
20 2,99 1,49 2,46
50 3,57 1,80 3,00
100 4,01 2,00 3,43
so :
Elastic settlement
Equipm q0 BF LF LF/BF Se
g'*D Ip Es
ent kN/m2 m m m2 (mm)
Duct 12 62,99 0,60 0,60 1,00 1,12 65.000 1,80

σmax = maximum value for permanent condition


q0 = σmax - existing overburden soil at depth D

Consolidation Settlement

∆σ' = qo BF LF / (BF + z) (LF + z)

Consolidaiton settlement layer 1


Equipm Hc1 z1 = Hc1/2 ∆σ' mv Sc
ent m m kPa m2/kN mm
Duct 9.,1 4,40 2,15 0,00002 0,50

Consolidaiton settlement layer 2


z2 = Hc1 + (Hc2/2)

Equipm Hc2 z2 ∆σ' mv Sc


ent m m kPa m2/kN mm
Duct 3,30 10,10 0,53 0,00005 0,09

Total Settlement

S = Se + Sc

Equipm S
ent mm
Duct 2,39
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV : A

Biaxial Design Short Column/Pedestal using ACI 318M-08: Load Contour Method
Design Forces : Pu
Node & Load case 1/235
Pu = 155,7 kN h
Fux = 15,4 kN b
Fuz
Fuz = 0,0 kN
Fu
Mux = 0,0 kN-m
Z
Muz = 31,6 kN-m Muz Mu
X

Design Parameter :
f'c = 29 Mpa
fy = 480 Mpa
Young's Modulus of rebar Es = 200000 Mpa
Dia of Bar, Db = 16 mm
Total nos of Bar = 20 nos (equally distributed on each face)
Height of column, l = 0,80 m
h= 0,600 m Parallel to Z axis
b= 0,600 m Parallel to X axis
Clear cover +Ds+ Db/2, d' = 0,068 m
Minimum reifn, Astmin = 3600 mm2 (Refer Cl. 10.9.1 of ACI 318M-2014)
Total area of reinf, Ast = 4021 mm2 1,12% > Min Ast 1.0%, OK
Area of Comp reinf, A's = 1206 sq.mm
Area of Tension reinf, As = 1206 sq.mm
ec=0.003 0.85f'c
Cs Cs
e's
c a Cc Cc
N.A.

(d-
Ts Ts
es
Strain, Stress & Internal Force Diagram

Calculation of Moment capacity about X axis Calculation of Moment capacity about Z axis
Depth factor for comp. Block(1), b1 = 0,843 Depth factor for comp. Block 0,843
effective depth, d =h-d' 0,532 m effective depth, d =b-d' 0,532 m
Depth of NA from extreme comp fibre, c = 0,063 m Depth of NA from extreme comp fibre, 0,063 m
Strain in concrete, ec = 0,00300 Strain in concrete, ec = 0,00300
Strain in comp steel, e's = ec*(1-d'/c) = -0,00023 Strain in comp steel, e's = ec*(1-d'/c)
-0,00023
=
Strain in tension steel, et = ec*(d/c-1) = 0,02224 Strain in tension steel, et = e 0,02224
Stress in comp steel(2), f's = e's*Es = -45,14 Mpa Stress in comp steel(2), f's = -45,14 Mpa
Stress in tension steel(2), fs = et*Es = 480,00 Mpa Stress in tension steel(2), fs = 480,00 Mpa
Cc = 0.85*f'c*b1*c*b = 788,36 kN Cc = 0.85*f'c*b1*c*h = 788,36 kN
Cs = f's*A's = -54,46 kN Cs = f's*A's = -54,46 kN
Ts =fs*As = 579,06 kN Ts =fs*As = 579,06 kN
Pu = Cc+Cs-Ts 154,85 kN Pu = Cc+Cs-Ts 154,85 kN
Mox =Cc*(h/2-b 1c/2)+Cs*(h/2-d')+Ts*(d-h/2) 337,03 kN-m Moz =Cc*(b/2-b 1c/2)+Cs*(b/2-d')+Ts*(d-b/2)
337,03 kN-m
(1) Refer Cl.10.2.7.3 of ACI 318M-2014 for value of b1
(2) In above calculation, stress calculated in steel restricted to fy when it exceeds fy.
Po=0.80*(085*f'c(Ag-Ast)+Ast*fy) = 8563,97 kN (Refer Cl. 10.3.6.2 of ACI 318M-2014)

r*fy/f'c = 0,185 (Refer these Values to Col.10.3


Pn/P0 = 0,018 of ACI-340R : 1997 (SP17) for
b= 0,715 (Refer ACI-340R : 1997 (SP-17) Columns 10.3)
a= 2,065 #NAME?
Interaction ratio
(Mux/Mox)a+(Muy/Moz)a = 0,01 < 1.00 , Hence Safe

Shear Capcity Check:

Dia stirrups, Ds = 10 mm
Spacing required, Sr = 256 mm (Refer Cl.7.10.5.2 of ACI 318M-2014)
Provided spacing, Sp = 250 mm
Design Resultant Shear, Vu = 15,43 kN
f= 0,75 (Refer Cl 9.3.2.3 of ACI 318M-2014)
Vu/f = 20,58 kN
Modification factor, l = 1,0 (Refer Cl 8.6.1 of ACI 318M-2014)
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-012-C-0012
Duct Pier Foundation Calculation DATE : 5/12/2022
REV : A
Allowable shear, Vc = 301,25 kN (Refer Cl.11.2.1.2 & Cl.11.2.2.3 of ACI 318M-2014)
301,25 kN >20,58 kN, Hence Safe
GA and RC Details of Foundation :

0,6 m

0,30 m

0,6 m 1,5 m 1,00 m

0,50 m

1,5 m
Plan Elevation

16 mm @ 200 mm (T)
16 mm @ 200 mm (B) 10 mm @50 mm

20 Nos Dia 16mm equally


10 mm @250 mm distributed on each face

16 mm @ 200 mm (T)
16 mm @ 200 mm (B)

Reinforcement Detail Reinforcement Detail

Tie Arrangements for Sequare & Rectangular Column:

Note: Anchor Bolt details are not include as the details are given in anchor bolt design calculation.
Interaction Diagram about major axis:
x(mm) M (kN-m) P (kN)
0,000 0,00 -1544,06 Interaction Curve
0,033 119,22 -740,95 1
0,067 358,22 243,70 2 b
0,100 503,68 876,26 3 h= 600 mm
10000
0,134 615,73 1416,00 4 Ast/2
b= 600 mm
2
0,167 704,55 1906,71 5 Ast = 2413 mm
0,201 775,81 2372,90 8000
6 h
0,234 831,95 2825,09 7
Ast/2
0,268 874,19 3268,52 8
6000
0,301 897,57 3730,46 9
0,335 884,12 4291,82 Axial Load (kN) 10
0,368 860,94 4815,91 11
4000
0,402 829,41 5320,25 12
Inter Curve
0,435 789,11 5811,18 13
0,469 739,40 6291,58 2000
14
0,502 679,78 6763,54 15
0,535 616,77 7198,91 16
0,569 536,31 7658,38 17 0
0 200 400 600 800 1000
0,602 445,08 8113,16 18
0,636 342,89 8563,97 -2000
0,00 8563,97

-4000
Moment (kN-m)
Interaction Diagram about minor axis:
x(mm) M (kN-m) P (kN)
0,000 0,00 -1544,06 Interaction Curve h
0,033 119,22 -740,95 1
0,067 358,22 243,70 2
0,100 503,68 876,26 3
10000 Ast/2 h= 600 mm
0,134 615,73 1416,00 4 b= 600 mm
b 2
0,167 704,55 1906,71 5 Ast = 2413 mm
0,201 775,81 2372,90 8000
6
Ast/2
0,234 831,95 2825,09 7
0,268 874,19 3268,52 8
6000
0,301 897,57 3730,46 9
0,335 884,12 4291,82 Axial Load (kN) 10
0,368 860,94 4815,91 11
4000
0,402 829,41 5320,25 12
Inter Curve
0,435 789,11 5811,18 13
0,469 739,40 6291,58 14
2000
0,502 679,78 6763,54 15
0,535 616,77 7198,91 16
0,569 536,31 7658,38 17 0
0,602 445,08 8113,16 18 0 200 400 600 800 1000
0,636 342,89 8563,97
-2000
0,00 8563,97

-4000
Moment (kN-m)