Professional Documents
Culture Documents
by OE, 19-Nov-21
CEO OFFICE
ACKNOWLEDGED
AND
SIGNED
Approved
with
Rejected Comment
Noted.
2 A Sheet 1 of 6 Not listed in J910-DA01-P0ZEN-020002 It was modified to match the document number J910-DA01-P0ZEN- CLOSED
020002.
Noted.
Please equlize with Equipment Numbering
3 A Sheet 1 of 6 It was modified to match the document number J910-DA01-P0ZEN- CLOSED
System(KKS)"J910-DA01-P0ZEN-020002
020002.
The application of cable tray cover depend on each installation
4 A Sheet 1 of 6 Please add necessary area according to the condition condition. The application of the cable tray cover per each installation CLOSED
added in detail.
The application of cable tray cover depend on each installation
5 A Sheet 1 of 6 All area of cable tray must be equiped with cover. condition. The application of the cable tray cover per each installation CLOSED
added in detail.
Noted.
I prefer this arrangement but different from the
6 A Sheet 2 of 6 It was modified to match the document number J910-XW01-P0ZEN- CLOSED
document 140005.
140005.
Noted.
Provide edge protecting rubber on the cable raceway
7 A Sheet 2 of 6 The cable is protected by using blind end plate or drop out material CLOSED
ends to protect the cables damage
at the end of cable tray. The detail was added. (Sheet 4 of 6)
Follow PUIL or page 5 of DESIGN CRITERIA_POWER The general descriptions of “Design Criteria_Power Cable and Cable
12 B Sheet 4 of 6 CABLE & CABLE RACEWAY J910-XW01-P0ZEN-140005 Raceway” and “Typical Installation Drawing _ Cable Raceway” apply CLOSED
the same.
Noted.
13 C Sheet 1 of 6 mention about bonding jumper. CLOSED
It was added in sheet 1,4,5, of 6.
[Self Revsion]
14 0 Sheet 1 of 6 In the cable tray cover of the General Note, the item of Coal Handing CLOSED
Area has been added to Case 4.
[Self Revsion]
15 0 Sheet 6 of 6 CLOSED
The HDPE Conduit Detail to Duct bank installation added.
[Self Revsion]
16 0 Sheet 6 of 6 In the Fixing Method of power cable part, the fixing method of the CLOSED
multi-core cable was modified with a cable tie.
Noted.
To be specific. Especially connecting point of steal pipe
17 1 Sheet 5 of 6 The detail connected between HDPE pipe and steel conduit has been
and PVC or HDPE if you plan to use.
added.
[Self Revsion]
18 1 Sheet 6 of 6 In the Fixing Method of power cable part, the fixing method of the
multi-core cable was modified with a cable tie.