You are on page 1of 54

APPROVED

by OE,
FOR CONSTRUCTION
13-Mar-23

Approval by the Owner Engineer (inculding the absence


of disapproval) does not relieve the Contractor from any
liabilities for non-compliance to the Contract
requirements and other obligations

1 22.FEB.2023 FUAD M. ROMAKI IWAN T. N. RE-ISSUED FOR CONSTRUCTION


0 06.JAN.2023 FUAD M. ROMAKI IWAN T. N. ISSUED FOR CONSTRUCTION
B 22.DEC.2022 FUAD M. ROMAKI IWAN T. N. RE-ISSUED FOR APPROVAL
A 31.AUG.2022 FUAD M. ROMAKI IWAN T. N. FOR APPROVAL
REV DATE PREPARED CHECKED APPROVED STATUS
Owner
CEO OFFICE

ACKNOWLEDGED
AND
SIGNED
Owner’s Engineer
Date: Mar 13, 2023

Contractor

Sub-Supplier

Project

JAWA 9 & 10 COAL FIRED STEAM POWER PLANT


Document Title
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL
CABLES, CABLE TRAYS, CONDUITS, ETC)
Document Type
□ Basic Engineering Document □ Detail Engineering Document ■ Vendor Document □ Other

Document No.

J910-YT01-P0SAA-145860
From : HK Document Controller
To : IRT Mr. Salam Syah Comment Sheet Document No : J910‐YT01‐P0SAA‐145860_CS
Cc : TEPSCO Mr. Kubota Hiroshi
Dwg Title : HVAC Electrical Equipment Datasheet (Power & Control Cables, Cable Trays, Conduit, etc)
Dwg No : J910‐YT01‐P0SAC‐145860
Purpose : FC

Review Category
A = Approved
B = Approved with comments, forward final document A
C = Not Approved
I = Accepted for reference (For information only)

No. Rev. Sheet/ Page/ Sect. O/E Comments Consortium Response Status
The specifications here should be consistent with higher document by DHI which has
1 A 3 Noted. Closed
already approved.

2 A 4 Electrical Equipment Datasheet is limited for HVAC? Yes, limited for HVAC System. Closed

Confirmed, please refer to J910‐YT01‐P0SAA‐148608 HVAC Electrical Equipment Datasheet


3 A 4 This should be separated. Closed
(Power & Control Cables, Cable Trays, Conduit, etc) for Switchyard

4 A 1 SAC for CCB, for this document better use SAA Noted. Closed

5 0 7 Adding inbow local switch & exploison proof local switch Closed
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

RECORD OF REVISION
Rev. Date Page Affected Description of Revision

A 31.AUG.2022 - First Issue

B 22.DEC.2022 - Second Issue

0 06.JAN.2023 - Adding junction box & outbow local switch

1 21.FEB.2023 - Adding inbow local switch & exploison


proof local switch

Rev.1 2 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

Table of Contents

TABLE OF CONTENTS ......................................................................................................................3


1. POWER AND CONTROL CABLE DATASHEET .........................................................4
1.1. General Data 4
1.2. Cable Specification 4

2. ELECTRICAL ACCESSORIES DATASHEET ..............................................................6


2.1. General Data 6
2.2. Specification 6

3. CABLE WAY SUPPORT SYSTEM DATASHEET ........................................................8


3.1. General Data 8
3.2. Specification 9

4. CABLE TRAY DATASHEET ..........................................................................................10


4.1. General Data 10
4.2. Enviroment Data 11
4.3. Construction 11
4.4. Testing 11
4.5. Tray Specification 11
4.5.1. Ladder-Type Tray 11
4.5.2. Perforated-Type Tray 20

5. CONDUIT DATASHEET .................................................................................................29


5.1. General Data 29
5.2. Conduit Specification 29
5.2.1 Electroplating Conduit 29
5.2.2 Rigid Steel Conduit 31
5.3. Testing 32

ATTACHMENT ..................................................................................................................................33

Rev.1 3 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

1. Power and Control Cable Datasheet


1.1. General Data
1 Building Name - Central Control Building
- Turbine Building
- ESP & FGD Electrical Control Building
- Emergency Diesel Generator Building
- Water Treatment Plant Building
- Waste Water Treatment Plant Building
- CPP Regeneration Building
- CWPH and CWPH Electrical and
Control Room
- Fire Water Booster Pump House
- LFO Pump House
- Chemical Laboratory Building
- General Service Water Pump House
- CHS Control & Electrical Building
- Fire Station Building
- Workshop Building
- Hazardous and Toxic Waste Disposal Building
- Electrochlorination Plant Building
- H2 Generation Plant Building
- Mobile Equipment Garage Building
- Auxiliary Boiler Building
- CHS Jetty Local Electrical Building
- Warehouse Building
2 Brand KMI or Extrana or Jembo or equal
3 Origin Indonesia
1.2. Cable Specification
1 Cable Voltage Grade 0.6 / 1.2 kV
Stranded Annealed Copper Conductor, Class 2
2 Conductor
according to IEC 60229
3 Insulation Cross Linked Polyethylene (XLPE) Insulated
Extruded Flame Retardant PVC Outer Sheath a
4 Overall Sheath
ccording to IEC 60332-3 Category C
Outer sheath : Black
1 Core – Brown
2 Core – Brown, Blue
3 Core – Brown, Black, Grey
4 Core – Brown, Black, Grey, Blue
Protective Earthing - Green / Yellow

5 Color of Power Cable

1. Conductor
2. Insulation
3. Filler
4. Binder
5. Over Sheath
Outer sheath : Black
1 Core – Red
2 Core – Red, Black
6 Color of Control Cable
3 Core – Red, Black, Red
4 Core – Red, Black, Red, Black
Protective Earthing – Green / Yellow

Rev.1 4 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

1. Conductor
2. Insulation
3. Fillers
4. Sheild
5. Drain Wire
6. Binder
7. Over Sheath
7 Amour Unamoured
Temperature rating of conductor under
8 90° C
normal operation
Temperature rating of conductor under
9 250° C
short circuit condition

Rev.1 5 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

2. Electrical Accessories Datasheet


2.1. General Data
1 Building Name - Central Control Building
- Turbine Building
- ESP & FGD Electrical Control Building
- Emergency Diesel Generator Building
- Water Treatment Plant Building
- Waste Water Treatment Plant Building
- CPP Regeneration Building
- CWPH and CWPH Electrical and
Control Room
- Fire Water Booster Pump House
- LFO Pump House
- Chemical Laboratory Building
- General Service Water Pump House
- CHS Control & Electrical Building
- Fire Station Building
- Workshop Building
- Hazardous and Toxic Waste Disposal Building
- Electrochlorination Plant Building
- H2 Generation Plant Building
- Mobile Equipment Garage Building
- Auxiliary Boiler Building
- CHS Jetty Local Electrical Building
- Warehouse Building
2 Brand Local
3 Origin Indonesia
2.2. Specification
1 Pre-Insulated Terminal Lug
1 Material Name Pre-Insulated Terminal Lug
2 Material Copper
3 Type 1. Pin
2. Ferrules
3. Fork
4. Ring
4 Color of Band L-N – Brown, Blue
L1-L2-L3 – Brown, Black, Grey
DC Circuit – Red, Black
Neutral – Blue
Protective Earthing – Green / Yellow
5 Finish Tinned
Nylon Insulated Crimp Type

6 Description

2 PVC Insullation Tape


1 Material Name PVC Insullation Tape
2 Material PVC
3 Color Brown, Black, Grey, Blue, Red, Green

Rev.1 6 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

3 Electrical Plug & Socket


1 Material Name Electrical Plug & Socket
2 Material PVC
3 Brand Broco
Inbow Installation
Rated Current: 16 A
Rated Voltage: 230 Volt
Color: White

4 Description

4 Local Control Switch


1 Material Name Isolating Switch
2 Material PVC
3 Brand Schneider
Rated Current: 20 A
Rated Voltage: 440 Volt
Dimension (WxHxD): 82mm x 170mm x 90
mm
Ingress Protection Rating: IP66
Outbow Installation

A. Double Pole Isolating Switch

4 Description

B. Triple Pole Isolating Switch

5 Inbow Local Control Switch


1 Material Name Isolating Switch
2 Material Polycarbonate
3 Brand Schneider

Rev.1 7 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

Rated Current: 20 A
Rated Voltage: 250 Volt
Width: 87mm
Height: 87mm
Inbow Installation

4 Description

6 Exploison Proof Local Control Switch


1 Material Name Isolating Switch
2 Material Glass fibre-reinforced polyester resin
3 Brand Helon
Rated Current: 6 A
Rated Voltage: 380 V
Ingress Protection Rating: IP66

4 Description

5 Junction Box
1 Material Name Junction Box
2 Material SS 304 T 1.5 mm
3 Brand Local
Dimension HxWxD: 160 mm x 140 mm x
80 mm
Cable Entry: Side Left & Right
Locking: Bolt Locking
Finishing: Hair Line
Index Protection: IP 65

4 Description

3. Cable Way Support System Datasheet


3.1. General Data
1 Building Name - Central Control Building
- Turbine Building
- ESP & FGD Electrical Control Building

Rev.1 8 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

- Emergency Diesel Generator Building


- Water Treatment Plant Building
- Waste Water Treatment Plant Building
- CPP Regeneration Building
- CWPH and CWPH Electrical and
Control Room
- Fire Water Booster Pump House
- LFO Pump House
- Chemical Laboratory Building
- General Service Water Pump House
- CHS Control & Electrical Building
- Fire Station Building
- Workshop Building
- Hazardous and Toxic Waste Disposal Building
- Electrochlorination Plant Building
- H2 Generation Plant Building
- Mobile Equipment Garage Building
- Auxiliary Boiler Building
- CHS Jetty Local Electrical Building
- Warehouse Building
2 Brand Local
3 Origin Indonesia
3.2. Specification
1 Steel Angle
1 Material Name Steel Angle
2 Used Indoor / Outdoor Used
3 Type L-Type
4 Material Iron Steel
5 Finish Hot Dipped Galvanized
Size 41.5mm x 41.5mm x 5mm

6 Size

2 Steel Channel
1 Material Name Steel Channel
2 Used Indoor / Outdoor Used
3 Type C-Type
4 Material Iron Steel
5 Finish Hot Dipped Galvanized
Size 100mm x 50mm x 5mm

6 Size

3 Steel Channel Unstrut with Hole


1 Material Name Steel Channel Unstrut with Hole
2 Used Indoor / Outdoor Used

Rev.1 9 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

3 Type U-Type
4 Material Iron Steel
5 Finish Hot Dipped Galvanized
Size 41.5mm x 41.5mm x 2.5mm
Note:
With Black Hold 8 x 30mmL

6 Size

4 Conduit Clamp
1 Material Name Conduit Clamp
2 Used Indoor / Outdoor
3 Material Electroplating, Hot Dipped Galvanized
4 Finish Natural
5 Description For channel unstrut & Conduit
SIZE (inch)
3/4
1
1 1/2

6 Size

4. Cable Tray Datasheet


4.1. General Data
1 Building Name - Central Control Building
- Turbine Building
- ESP & FGD Electrical Control Building
- Emergency Diesel Generator Building
- Water Treatment Plant Building
- Waste Water Treatment Plant Building
- CPP Regeneration Building
- CWPH and CWPH Electrical and
- Control Room
- Fire Water Booster Pump House
- LFO Pump House
- Chemical Laboratory Building
- General Service Water Pump House
- CHS Control & Electrical Building
- Fire Station Building
- Workshop Building
- Hazardous and Toxic Waste Disposal Building
- Electrochlorination Plant Building
- H2 Generation Plant Building
- Mobile Equipment Garage Building
- Auxiliary Boiler Building
- CHS Jetty Local Electrical Building

Rev.1 10 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

- Warehouse Building
2 Brand SSM or NOBI or Local
3 Origin Indonesia
4 IEC Standards IEC 61537
4.2. Enviroment Data
1 Elevation 37 m above sea level
2 Ambient Temperature Min. 21 °C Max 37 °C Average 29 °C
3 Relative Humidity Min. 23 % Max 100 % Average 62%
4 Location  Indoor  Outdoor

4.3. Construction
1 Material Hot-dip galvanized steel
2 Width 300mm, 450mm, 600mm
3 Height 100 mm
4 Rung Spacing Max 300mm
5 Cable Bearing Surface 30 mm with radius edges
6 Thickness of Cover 1.5 mm
7 Thickness of Tray 2 mm
8 Section of Each Cable Tray 3m long
9 Elbow Radius 300mm & 600mm
4.4. Testing
1 Visual Inspection  Yes  No
2 Load Test :
Tested as per Manufacture standard test  Yes  No
Add 100kg man in the middle of trays
span and the deflection shall be less than  Yes  No
50mm
Galvanization Test  Yes  No
Load Test as per NEMA 20C
 Yes  No
(Ladder Type)
4.5. Tray Specification
4.5.1. Ladder-Type Tray
1 Straight Ladder
1 Material Name Straight Ladder
2 Material Hot dipped galvanized steel
3 Finish Natural
TH TH
W H L
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300
Description and Remarks
450 100 3000 2 1.5
(A). Standard Quantity of Rung as per
600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

2 Horizontal Elbow
1 Material Name Horizontal Elbow
2 Material Hot-dip galvanized steel
3 Finish Natural

Rev.1 11 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

W H R
(mm) (mm) (mm)
Description and Remarks 300 300
(A). Standard Quantity of Rung as per 450 100 450
4 MFR.STD, Heavy-Duty, Ladder Type 600 600
(B). Available Sizes

3 Vertical Outside Riser


1 Material Name Vertical Outside Riser
2 Material Hot-dip galvanized steel
3 Finish Natural

W H R
(mm) (mm) (mm)
300 300
450 100 450
Description and Remarks 600 600
(A). Standard Quantity of Rung as per
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

4 Vertical Inside Riser


1 Material Name Vertical Inside Riser
2 Material Hot-dip galvanized steel
3 Finish Natural

W H R
(mm) (mm) (mm)
300 300
450 100 450
Description and Remarks 600 600
(A). Standard Quantity of Rung as per
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

5 Unequal Tee
1 Material Name Unequal Tee
2 Material Hot-dip galvanized steel
3 Finish Natural

Rev.1 12 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

6 Equal Tee
1 Material Name Equal Tee
2 Material Hot-dip galvanized steel
3 Finish Natural

W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

7 Unequal Cross
1 Material Name Unequal Cross
2 Material Hot-dip galvanized steel
3 Finish Natural

W H R
(mm) (mm) (mm)
300 300
450 100 450
Description and Remarks 600 600
(A). Standard Quantity of Rung as per
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

8 Equal Cross
1 Material Name Equal Cross
2 Material Hot-dip galvanized steel
3 Finish Natural

Rev.1 13 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

9 Left Hand Offset Reducer


1 Material Name Left Hand Offset Reducer
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
(mm) (mm Tray Cover
min.) (mm) (mm)
300
Description and Remarks 450 100 2 1.5
(A). Standard Quantity of Rung as per 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

10 Right Hand Offset Reducer


1 Material Name Right Hand Offset Reducer
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
(mm) (mm Tray Cover
min.) (mm) (mm)
300
Description and Remarks 450 100 2 1.5
(A). Standard Quantity of Rung as per 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

11 Straight Offset Reducer


1 Material Name Straight Offset Reducer
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
Description and Remarks (mm) (mm Tray Cover
(A). Standard Quantity of Rung as per min.) (mm) (mm)
4 MFR.STD, Heavy-Duty, Ladder Type 300
(B). Available Sizes 450 100 2 1.5
600

Rev.1 14 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

12 Straight Ladder Cover


1 Material Name Straight Ladder Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
(mm) (mm Tray Cover
min.) (mm) (mm)
300
450 100 2 1.5
Description and Remarks
600
(A). For Ladder Type, Heavy-Duty
4
(B). Available Sizes

13 90° Horizontal Elbow Cover


1 Material Name 90° Horizontal Elbow Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks
450 100 2 1.5 450
(A). For Ladder Type, Heavy-Duty
4 600 600
(B). Available Sizes

14 90° Outside Riser Cover


1 Material Name 90° Outside Riser Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Description and Remarks Tray Cover
(mm) (mm) (mm)
(A). For Ladder Type, Heavy-Duty (mm) (mm)
4 300 300
(B). Available Sizes
450 100 2 1.5 450
600 600

Rev.1 15 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

15 90° Inside Riser Cover


1 Material Name 90° Inside Riser Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
450 100 2 1.5 450
600 600
Description and Remarks
(A). For Ladder Type, Heavy-Duty
4
(B). Available Sizes

16 Unequal Tee Cover


1 Material Name Unequal Tee Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
450 100 2 1.5 450
600 600
Description and Remarks
(A). For Ladder Type, Heavy-Duty
4
(B). Available Sizes

17 Equal Tee Cover


1 Material Name Equal Tee Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Description and Remarks Tray Cover
(mm) (mm) (mm)
(A). For Ladder Type, Heavy-Duty (mm) (mm)
4
(B). Available Sizes 300 300
450 100 2 1.5 450
600 600

Rev.1 16 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

18 Unequal Cross Cover


1 Material Name Unequal Cross Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
450 100 2 1.5 450
Description and Remarks 600 600
(A). For Ladder Type, Heavy-Duty
4
(B). Available Sizes

19 Equal Cross Cover


1 Material Name Equal Cross Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
450 100 2 1.5 450
Description and Remarks
600 600
(A). For Ladder Type, Heavy-Duty
4
(B). Available Sizes

20 Left Hand Offset Reducer Cover


1 Material Name Left Hand Offset Reducer Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
Description and Remarks W H R
Tray Cover
(A). Standard Quantity of Rung as per (mm) (mm) (mm)
(mm) (mm)
4 MFR.STD, Heavy-Duty, Ladder Type 300 300
(B). Available Sizes 450 100 2 1.5 450
600 600

Rev.1 17 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

21 Right Hand Offset Reducer Cover


1 Material Name Right Hand Offset Reducer Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks 450 100 2 1.5 450
(A). Standard Quantity of Rung as per 600 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

22 Straight Offset Reducer Cover


1 Material Name Straight Offset Reducer Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks 450 100 2 1.5 450
(A). Standard Quantity of Rung as per 600 600
4 MFR.STD, Heavy-Duty, Ladder Type
(B). Available Sizes

23 Cover Clamp
1 Material Name Cover Clamp
2 Material Hot-dip galvanized steel
3 Finish Natural
FOR LADDER
W
(mm)
300
Description and Remarks 450
(A). For Ladder Type, Heavy-Duty 600
4
(B). Available Sizes

Rev.1 18 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

24 Hold Down Clamp (Z-Clamp Type)


1 Material Name Hold Down Clamp (Z-Clamp Type)
2 Material Hot-dip galvanized steel
3 Finish Natural

Description and Remarks


4 (A). Applicable for Cabble Ladder

25 Adjustable Horizontal Splice Plate


1 Material Name Adjustable Horizontal Splice Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
For Ladder Tray
H (mm)
Description and Remarks 100
(A). For Ladder type, length just adjust
able vertical splice plate as per
4
manufacture standard
(B). Available Sizes

26 Adjustable Vertical Splice Plate


1 Material Name Adjustable Vertical Splice Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
For Ladder Tray
H (mm)
Description and Remarks 100
(A). For Ladder type, length just adjust
able vertical splice plate as per
4
manufacture standard
(B). Available Sizes

27 End Plate
1 Material Name End Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
Description and Remarks For Ladder Tray
(A). For Ladder type H (mm)
4
(B). Available Sizes 100

Rev.1 19 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

28 Splice Plate
1 Material Name Splice Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
For Ladder Tray
H (mm)
100
Description and Remarks
(A). For Ladder type
4
(B). Available Sizes

4.5.2. Perforated-Type Tray


1 Straight Tray Perforated
1 Material Name Straight Tray Perforated
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H L
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300
Description and Remarks 450 100 3000 2 1.5
(A). Standard Quantity of Rung as per
600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

2 Horizontal Elbow
1 Material Name Horizontal Elbow
2 Material Hot-dip galvanized steel
3 Finish Natural
W H R
(mm) (mm) (mm)
Description and Remarks 300 300
(A). Standard Quantity of Rung as per 450 100 450
MFR.STD, Heavy-Duty, Perforated 600 600
4
Type
(B). Available Sizes

3 Vertical Outside Riser

Rev.1 20 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

1 Material Name Vertical Outside Riser


2 Material Hot-dip galvanized steel
3 Finish Natural
W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

4 Vertical Inside Riser


1 Material Name Vertical Inside Riser
2 Material Hot-dip galvanized steel
3 Finish Natural
W H R
(mm) (mm) (mm)
300 300
450 100 450
Description and Remarks 600 600
(A). Standard Quantity of Rung as per
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

5 Unequal Tee
1 Material Name Unequal Tee
2 Material Hot-dip galvanized steel
3 Finish Natural
W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

6 Equal Tee
1 Material Name Equal Tee
2 Material Hot-dip galvanized steel
3 Finish Natural

Rev.1 21 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

7 Unequal Cross
1 Material Name Unequal Cross
2 Material Hot-dip galvanized steel
3 Finish Natural
W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

8 Equal Cross
1 Material Name Equal Cross
2 Material Hot-dip galvanized steel
3 Finish Natural
W H R
(mm) (mm) (mm)
300 300
Description and Remarks 450 100 450
(A). Standard Quantity of Rung as per 600 600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

9 Left Hand Offset Reducer


1 Material Name Left Hand Offset Reducer
2 Material Hot-dip galvanized steel
3 Finish Natural

Description and Remarks W H TH TH


(A). Standard Quantity of Rung as per (mm) (mm Tray Cover
MFR.STD, Heavy-Duty, Perforated min.) (mm) (mm)
4 300
Type
(B). Available Sizes 450 100 2 1.5
600

Rev.1 22 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

10 Right Hand Offset Reducer


1 Material Name Right Hand Offset Reducer
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
(mm) (mm Tray Cover
min.) (mm) (mm)
Description and Remarks 300
(A). Standard Quantity of Rung as per 450 100 2 1.5
MFR.STD, Heavy-Duty, Perforated 600
4
Type
(B). Available Sizes

11 Straight Offset Reducer


1 Material Name Straight Offset Reducer
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
(mm) (mm Tray Cover
min.) (mm) (mm)
Description and Remarks 300
(A). Standard Quantity of Rung as per 450 100 2 1.5
MFR.STD, Heavy-Duty, Perforated 600
4
Type
(B). Available Sizes

12 Straight Perforated Cover


1 Material Name Straight Perforated Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
W H TH TH
Description and Remarks (mm) (mm Tray Cover
(A). For Perforated Type, Heavy-Duty min.) (mm) (mm)
4 300
(B). Available Sizes
450 100 2 1.5
600

Rev.1 23 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

13 90° Horizontal Elbow Cover


1 Material Name 90° Horizontal Elbow Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks
450 100 2 1.5 450
(A). For Perforated Type, Heavy-Duty
4 600 600
(B). Available Sizes

14 90° Outside Riser Cover


1 Material Name 90° Outside Riser Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
450 100 2 1.5 450
Description and Remarks 600 600
(A). For Perforated Type, Heavy-Duty
4
(B). Available Sizes

15 90° Inside Riser Cover


1 Material Name 90° Inside Riser Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Description and Remarks Tray Cover
(mm) (mm) (mm)
(A). For Perforated Type, Heavy-Duty (mm) (mm)
4 300 300
(B). Available Sizes
450 100 2 1.5 450
600 600

Rev.1 24 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

16 Unequal Tee Cover


1 Material Name Unequal Tee Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks 450 100 2 1.5 450
(A). For Perforated Type, Heavy-Duty 600 600
4
(B). Available Sizes

17 Equal Tee Cover


1 Material Name Equal Tee Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
450 100 2 1.5 450
Description and Remarks 600 600
(A). For Perforated Type, Heavy-Duty
4
(B). Available Sizes

18 Unequal Cross Cover


1 Material Name Unequal Cross Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Description and Remarks Tray Cover
(mm) (mm) (mm)
(A). For Perforated Type, Heavy-Duty (mm) (mm)
4 300 300
(B). Available Sizes
450 100 2 1.5 450
600 600

Rev.1 25 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

19 Equal Cross Cover


1 Material Name Equal Cross Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks 450 100 2 1.5 450
(A). For Perforated Type, Heavy-Duty 600 600
4
(B). Available Sizes

20 Left Hand Offset Reducer Cover


1 Material Name Left Hand Offset Reducer Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
Description and Remarks 300 300
(A). Standard Quantity of Rung as per 450 100 2 1.5 450
MFR.STD, Heavy-Duty, Perforated 600 600
4
Type
(B). Available Sizes

21 Right Hand Offset Reducer Cover


1 Material Name Right Hand Offset Reducer Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
300 300
Description and Remarks
450 100 2 1.5 450
(A). Standard Quantity of Rung as per
600 600
MFR.STD, Heavy-Duty, Perforated
4
Type
(B). Available Sizes

Rev.1 26 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

22 Straight Offset Reducer Cover


1 Material Name Straight Offset Reducer Cover
2 Material Hot-dip galvanized steel
3 Finish Natural
TH TH
W H R
Tray Cover
(mm) (mm) (mm)
(mm) (mm)
Description and Remarks 300 300
(A). Standard Quantity of Rung as per 450 100 2 1.5 450
MFR.STD, Heavy-Duty, Perforated 600 600
4
Type
(B). Available Sizes

23 Cover Clamp
1 Material Name Cover Clamp
2 Material Hot-dip galvanized steel
3 Finish Natural
For Perforated
W
(mm)
300
450
Description and Remarks 600
(A). For Perforated Type, Heavy-Duty
4
(B). Available Sizes

24 Hold Down Clamp (Z-Clamp Type)


1 Material Name Hold Down Clamp (Z-Clamp Type)
2 Material Hot-dip galvanized steel
3 Finish Natural

Description and Remarks


4
(A). Applicable for Cabble Perforated

25 Adjustable Horizontal Splice Plate


1 Material Name Adjustable Horizontal Splice Plate
2 Material Hot-dip galvanized steel
3 Finish Natural

Rev.1 27 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

For Perforated Tray


H (mm)
Description and Remarks 100
(A). For Perforated type, length just
adjustable vertical splice plate as per
4
manufacture standard
(B). Available Sizes

26 Adjustable Vertical Splice Plate


1 Material Name Adjustable Vertical Splice Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
For Perforated Tray
H (mm)
Description and Remarks 100
(A). For Perforated type, length just
adjustable vertical splice plate as per
4
manufacture standard
(B). Available Sizes

27 End Plate
1 Material Name End Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
For Perforated Tray
H (mm)
100
Description and Remarks
(A). For Perforated type
4
(B). Available Sizes

28 Splice Plate
1 Material Name Splice Plate
2 Material Hot-dip galvanized steel
3 Finish Natural
For Perforated Tray
H (mm)
100

Description and Remarks


(A). For Perforated type
4
(B). Available Sizes

Rev.1 28 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

5. Conduit Datasheet
5.1. General Data
1 Building Name - Central Control Building
- Turbine Building
- ESP & FGD Electrical Control Building
- Emergency Diesel Generator Building
- Water Treatment Plant Building
- Waste Water Treatment Plant Building
- CPP Regeneration Building
- CWPH and CWPH Electrical and
Control Room
- Fire Water Booster Pump House
- LFO Pump House
- Chemical Laboratory Building
- General Service Water Pump House
- CHS Control & Electrical Building
- Fire Station Building
- Workshop Building
- Hazardous and Toxic Waste Disposal
Building
- Electrochlorination Plant Building
- H2 Generation Plant Building
- Mobile Equipment Garage Building
- Auxiliary Boiler Building
- CHS Jetty Local Electrical Building
- Warehouse Building
2 Brand Wahana or HCK or Local
5.2. Conduit Specification
5.2.1 Electroplating Conduit
1 Electrical Metallic Tubing (EMT)
1 Material Name Electrical Metallic Tubing (EMT)
2 Used Indoor Used
3 Material Sheet Steel
4 Finish Electroplating
5 Description Above Ceiling or in Wall
SIZE (inch)
3/4
1

6 Size 1 1/2

2 Coupling Set Screw (Threadless)


1 Material Name Coupling Set Screw (Threadless)
2 Used Indoor Used
3 Material Sheet Steel
4 Finish Electroplating
5 Description Above Ceiling or in Wall

Rev.1 29 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

SIZE (inch)
3/4
1
1 1/2
6 Size

3 EMT Combination Connector Set


1 Material Name EMT Combination Connector Set
2 Used Indoor Used
3 Material Sheet Steel
4 Finish Electroplating
5 Accessories C/W Screw
6 Description Above Ceiling or in Wall
SIZE (inch)
3/4
1
1 1/2
7 Size

4 EMT Box Connector, Set Screw (Threadless)


EMT Bpx Connector, Set Screw (Threa
1 Material Name
dless)
2 Used Indoor Used
3 Material Sheet Steel
4 Finish Electroplating
5 Accessories C/W Lock Nut
6 Description Above Ceiling
SIZE (inch)
3/4
1
1 1/2
7 Size

5 Flexible Box Connector, Set Screw (Threadless)


Flexible Box Connector, Set Screw (Thr
1 Material Name
eadless)
2 Used Indoor Used
3 Material Sheet Steel
4 Finish Electroplating
5 Accessories C/W Lock Nut
6 Description Above Ceiling

Rev.1 30 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

SIZE (inch)
3/4
1
1 1/2
7 Size

6 Metal Flexible Conduit


1 Material Name Metal Flexible Conduit
2 Used Indoor Used
3 Material Sheet Steel
4 Finish PVC Coated, Black Colour
SIZE (inch)
3/4
1
1 1/2

5 Size

5.2.2 Rigid Steel Conduit


1 Rigid Steel Conduit
1 Material Name Rigid Steel Conduit
2 Used Indoor Used
3 Material Steel Pipe
4 Finish Hot Dipped Galvanized
5 Description Above Ceiling or in Wall
SIZE (inch)
3/4
1
6 Size 1 1/2

2 Conduit Bushing, with Nylon Protector


1 Used Indoor Used
2 Material Steel
3 Finish Hot Dipped Galvanized
SIZE (inch)
3/4
1
4 Size 1 1/2

Rev.1 31 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

3 Conduit Sealing Fittings


1 Used Indoor Used
2 Material Aluminum Alloy
SIZE (inch)
3/4
1
1 1/2

3 Size

5.3. Testing
1 Visual Inspection  Yes  No
2 Load Test :
Tested as per Manufacture standard test  Yes  No

Rev.1 32 of 33
HVAC ELECTRICAL EQUIPMENT DATASHEET (POWER & CONTROL CABLES, CABLE TRAYS, CONDUITS, ETC)
J910-YT01-P0SAA-145860

ATTACHMENT

Rev.1 33 of 33
PT. PRIMA INDAH LESTARI

TECHNICAL PARTICULAR AND GUARANTEE


Type of Cable : CU/XLPE/PVC - FR Cat.C (N2XY-FR)
Customer : PT.HUTAMA KARYA Jawa 9&10 Project

NO DESCRIPTION UNIT SPECIFICATION


1 Manufacturing - PT. PRIMA INDAH LESTARI
2 Trade Mark - EXTRANA
3 Standard IEC 60502-1 IEC 60332-3-24
4 Rated Voltage kV 0.6/1(1.2)
5 Reg. No - 02-020.I.2.05.03.0040 02-020.I.2.05.03.0100
2
6 Size of cable mm 3x4 3x10
7 Conductor Phase
- Material - Annealead Copper Wire
- Shape - Round Stranded, Class 2
- Nominal diameter of Conductor (Approx.) mm 2,49 3,93
8 Insulation Phase
- Material - Cross Linked Polyethylene (XLPE) Compound
- Nominal Thickness mm 0,7 0,7
- Diameter of Insulation (Approx.) mm 3,9 5,3
- Colour - Brown - Blue and Yellow with Green stripe
9 Inner Sheath/Bedding
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,0 1,0
- Colour - Black
10 Outer Sheath
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,8 1,8
- Diameter of sheath (Approx.) mm 14,2 17,3
- Colour Black
11 Weight of Cable (Approx.) kg/km 323 559
12 Minimum Bending Radius mm 114 138
13 Electrical and Mechanical test
- Max DC Conductor Resistance, at 20 ⁰C Phase ohm/km 4,61 1,83
- Max. Inductance mH/km 0,275 0,248
- Max. current rating at 30°C In Air A 48 83
In ground A 58 97
- AC Voltage Test 5 Minute kV 3,5
14 Printing of Cable :
IEC 60502-1 IEC 60332-3-24 EXTRANA CU/XLPE/PVC - FR Cat.C ''SIZE mm² '' 0.6/1(1.2) kV (N2XY-FR)

Jakarta, 11 January 2023


Approval by Customer PT. PRIMA INDAH LESTARI

( ) ( Rahman Sajana T.W )


CONSTRUCTION
CU/XLPE/PVC - FR Cat.C (N2XY-FR)
0.6/1(1.2) kV

1. Conductor Phase
Annealead Copper Wire
Round Stranded, Class 2

2. Insulation
Cross Linked Polyethylene (XLPE) Compound
Colour : Brown - Blue and Yellow with Green stripe

3. Inner Sheath/Bedding
PVC-FR Cat.C Compound
Colour : Black

4. Outer Sheath
PVC-FR Cat.C Compound
Colour : Black

Drawing by Approval by Customer


DATE : 11 January 2023 PT.HUTAMA KARYA

STANDARD : IEC 60502-1 IEC 60332-3-24

( Rahman Sajana T.W )


PT. PRIMA INDAH LESTARI

TECHNICAL PARTICULAR AND GUARANTEE


Type of Cable : CU/XLPE/PVC - FR Cat.C (N2XY-FR)
Customer : PT.HUTAMA KARYA Jawa 9&10 Project

NO DESCRIPTION UNIT SPECIFICATION


1 Manufacturing - PT. PRIMA INDAH LESTARI
2 Trade Mark - EXTRANA
3 Standard IEC 60502-1 IEC 60332-3-24
4 Rated Voltage kV 0.6/1(1.2)
5 Reg. No - 02-020.I.2.05.04.0040 02-020.I.2.05.04.0060
2
6 Size of cable mm 4x4 4x6
7 Conductor Phase
- Material - Annealead Copper Wire
- Shape - Round Stranded, Class 2
- Nominal diameter of Conductor (Approx.) mm 2,49 3,03
8 Insulation Phase
- Material - Cross Linked Polyethylene (XLPE) Compound
- Nominal Thickness mm 0,7 0,7
- Diameter of Insulation (Approx.) mm 3,9 4,4
- Colour - Brown - Black - Grey and Yellow with Green stripe
9 Inner Sheath/Bedding
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,0 1,0
- Colour - Black
10 Outer Sheath
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,8 1,8
- Diameter of sheath (Approx.) mm 15,2 16,5
- Colour Black
11 Weight of Cable (Approx.) kg/km 379 479
12 Minimum Bending Radius mm 182 198
13 Electrical and Mechanical test
- Max DC Conductor Resistance, at 20 ⁰C Phase ohm/km 4,61 3,08
- Max. Inductance mH/km 0,275 0,263
- Max. current rating at 30°C In Air A 48 61
In ground A 58 72
- AC Voltage Test 5 Minute kV 3,5
14 Printing of Cable :
IEC 60502-1 IEC 60332-3-24 EXTRANA CU/XLPE/PVC - FR Cat.C ''SIZE mm² '' 0.6/1(1.2) kV (N2XY-FR)

Jakarta, 11 January 2023


Approval by Customer PT. PRIMA INDAH LESTARI

( ) ( Rahman Sajana T.W )


PT. PRIMA INDAH LESTARI

TECHNICAL PARTICULAR AND GUARANTEE


Type of Cable : CU/XLPE/PVC - FR Cat.C (N2XY-FR)
Customer : PT.HUTAMA KARYA Jawa 9&10 Project

NO DESCRIPTION UNIT SPECIFICATION


1 Manufacturing - PT. PRIMA INDAH LESTARI
2 Trade Mark - EXTRANA
3 Standard IEC 60502-1 IEC 60332-3-24
4 Rated Voltage kV 0.6/1(1.2)
5 Reg. No - 02-020.I.2.05.04.0100 02-020.I.2.05.04.0160
2
6 Size of cable mm 4x10 4x16
7 Conductor Phase
- Material - Annealead Copper Wire
- Shape - Round Stranded, Class 2 Round Stranded, Class 2
- Nominal diameter of Conductor (Approx.) mm 3,93 4,89
8 Insulation Phase
- Material - Cross Linked Polyethylene (XLPE) Compound
- Nominal Thickness mm 0,7 0,7
- Diameter of Insulation (Approx.) mm 5,3 6,3
- Colour - Brown - Black - Grey and Yellow with Green stripe
9 Inner Sheath/Bedding
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,0 1,0
- Colour - Black
10 Outer Sheath
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,8 1,8
- Diameter of sheath (Approx.) mm 18,7 21,1
- Colour Black
11 Weight of Cable (Approx.) kg/km 677 899
12 Minimum Bending Radius mm 224 253
13 Electrical and Mechanical test
- Max DC Conductor Resistance, at 20 ⁰C Phase ohm/km 1,83 1,15
- Max. Inductance mH/km 0,248 0,238
- Max. current rating at 30°C In Air A 83 113
In ground A 97 128
- AC Voltage Test 5 Minute kV 3,5
14 Printing of Cable :
IEC 60502-1 IEC 60332-3-24 EXTRANA CU/XLPE/PVC - FR Cat.C ''SIZE mm² '' 0.6/1(1.2) kV (N2XY-FR)

Jakarta, 11 January 2023


Approval by Customer PT. PRIMA INDAH LESTARI

( ) ( Rahman Sajana T.W )


PT. PRIMA INDAH LESTARI

TECHNICAL PARTICULAR AND GUARANTEE


Type of Cable : CU/XLPE/PVC - FR Cat.C (N2XY-FR)
Customer : PT.HUTAMA KARYA Jawa 9&10 Project

NO DESCRIPTION UNIT SPECIFICATION


1 Manufacturing - PT. PRIMA INDAH LESTARI
2 Trade Mark - EXTRANA
3 Standard IEC 60502-1 IEC 60332-3-24
4 Rated Voltage kV 0.6/1(1.2)
5 Reg. No - 02-020.I.2.05.04.0350
2
6 Size of cable mm 4x35
7 Conductor Phase
- Material - Annealead Copper Wire
- Shape - Round Stranded, Class 2
- Nominal diameter of Conductor (Approx.) mm 7,26
8 Insulation Phase
- Material - Cross Linked Polyethylene (XLPE) Compound
- Nominal Thickness mm 0,9
- Diameter of Insulation (Approx.) mm 9,1
- Colour - Brown - Black - Grey and Yellow with Green stripe
9 Inner Sheath/Bedding
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,0
- Colour - Black
10 Outer Sheath
- Material - PVC-FR Cat.C Compound
- Nominal Thickness mm 1,8
- Diameter of sheath (Approx.) mm 27,8
- Colour Black
11 Weight of Cable (Approx.) kg/km 1.731
12 Minimum Bending Radius mm 334
13 Electrical and Mechanical test
- Max DC Conductor Resistance, at 20 ⁰C Phase ohm/km 0,524
- Max. Inductance mH/km 0,233
- Max. current rating at 30°C In Air A 186
In ground A 201
- AC Voltage Test 5 Minute kV 3,5
14 Printing of Cable :
IEC 60502-1 IEC 60332-3-24 EXTRANA CU/XLPE/PVC - FR Cat.C ''SIZE mm² '' 0.6/1(1.2) kV (N2XY-FR)

Jakarta, 11 January 2023


Approval by Customer PT. PRIMA INDAH LESTARI

( ) ( Rahman Sajana T.W )


CONSTRUCTION
CU/XLPE/PVC - FR Cat.C (N2XY-FR)
0.6/1(1.2) kV

1. Conductor Phase
Annealead Copper Wire
Round Stranded, Class 2

2. Insulation
Cross Linked Polyethylene (XLPE) Compound
Colour : Brown - Black - Grey and Yellow with Green stripe

3. Inner Sheath/Bedding
PVC-FR Cat.C Compound
Colour : Black

4. Outer Sheath
PVC-FR Cat.C Compound
Colour : Black

Drawing by Approval by Customer


DATE : 11 January 2023 PT.HUTAMA KARYA

STANDARD : IEC 60502-1 IEC 60332-3-24

( Rahman Sajana T.W )


PT. PRIMA INDAH LESTARI

TECHNICAL PARTICULAR AND GUARANTEE


Type of Cable : CU/PVC/OS/PVC FR Cat C LS AT AR UV (RE-Y(St)Y FRLS AT AR UV)
Customer : PT.HUTAMA KARYA Jawa 9&10 Project

NO DESCRIPTION UNIT SPECIFICATION


1 Manufacturing - PT. PRIMA INDAH LESTARI
2 Trade Mark - EXTRANA
3 Standard - IEC 60502-1 IEC 60332-3-24
4 Rated Voltage kV 0.6/1 (1.2)
5 Reg. No - 02-208.O.2.05.08.0025
6 Size of cable mm² 8x2,5
7 Conductor
- Material - Annealead Copper Wire
- Nominal diameter of Conductor Approx. mm 1,98
- Shape - Round Stranded, Class 2
8 Insulation
- Material - Polyvinil Chloride (PVC)
- Nominal Thickness mm 0,8
- Min. Thickness at any point mm 0,62
- Diameter of Insulation Approx. mm 3,7
- Colour - White with Black numbering
9 Overall Screen (OS)
It's Required number of individual Sreen(s) shall be laying up
and covered with PE Aluminium Single Coated which The
- Material -
metalic of aluminium side downward contact by Drain Tin
Copper Wire 1 mm²
10 Outer Sheath
PVC Flame Retardant Cat C. Low Smoke Anti Termite Anti
- Material - Rodent UV Resistance Compound
- Nominal Thickness mm 1,8
- Diameter of sheath (Approx.) mm 17
- Colour - Black
11 Weight of Cable (Approx.) kg/km 443
Minimum Bending Radius mm 133
12 Electrical and Mechanical test
- Max DC Conductor Resistance, at 20 ⁰C Ω/km 7,41
- Min. Insulation Resistance at 20°C MΩ.km 50
- Voltage Test 5 Minute V 3500
13 Printing of Cable
IEC 60502-1 IEC 60332-3-24 EXTRANA CU/PVC/OS/PVC FR Cat C LS AT AR UV ''SIZE'' 0.6/1 (1.2) kV (RE-Y(St)Y FRLS AT AR UV)

Jakarta, 11 January 2023


Approval by Customer PT. PRIMA INDAH LESTARI

( ) ( Rahman Sajana Tresna W. )


CONSTRUCTION

CU/PVC/OS/PVC FR Cat C LS AT AR UV or (RE-Y(St)Y FRLS AT AR UV)

0.6/1 (1.2) kV

1. Conductor
Annealead Copper Wire
Round Stranded, Class 2

2. Insulation
Polyvinil Chloride (PVC)
Colour : White with Black numbering

3. Overall Screen (OS)


2
Polyester tape with Drain wire 1 mm and Aluminium Mylar Tape

4. Outer Sheath
PVC Flame Retardant Cat C. Low Smoke Anti Termite Anti Rodent UV
Resistance Compound
Colour : Black

Drawing by Approval by Customer


DATE : 11 January 2023 PT.HUTAMA KARYA

STANDARD : IEC 60502-1 IEC 60332-3-24

( Rahman Sajana Tresna W. )


PT. PRIMA INDAH LESTARI

TECHNICAL PARTICULAR AND GUARANTEE


Type of Cable : CU/PVC/ISOS/PVC-FR Cat.C LS AT AR UV (RE-Y(St)Y-FRLS AT AR UV Pimf )
Customer : PT.HUTAMA KARYA Jawa 9&10 Project

NO DESCRIPTION UNIT SPECIFICATION


1 Manufacturing - PT. PRIMA INDAH LESTARI
2 Trade Mark - EXTRANA
3 Standard - BS EN 50288-7 IEC 60332-3-24
4 Rated Voltage V 300
5 Reg. No - 01-113.O.2.01.2P.0015
2
6 Size of cable mm 2Px1,5
7 Conductor
- Material - Annealead Copper Wire
- Shape - Round Stranded, Class 2
8 Insulation
- Material - Polyvinyl Chloride (PVC) Compound
- Nominal Thickness mm 0,5
- Min. Thickness at any point mm 0,35
- Diameter of Insulation Approx. mm 2,7
- Colour - Black and White With numbering
9 Individual Screen (IS)

It's Required number of twist pair(s) covered with PE Aluminium


Single Coated which The metalic of aluminium side downward
- Material -
contact by Drain Tin Copper Wire 0.5 mm² and Polyester tape
upward PE Aluminium Single Coated

10 Overall Screen (OS)


It's Required number of individual Sreen(s) shall be laying up and
- Material - covered with PE Aluminium Single Coated which The metalic of
aluminium side downward contact by Drain Tin Copper Wire 0.5 mm²

11 Outer Sheath
PVC Flame Retardant Cat C. Low Smoke Anti Termite Anti Rodent
- Material - UV Resistance Compound
- Nominal Thickness mm 1,1
- Diameter of sheath (Approx.) mm 12,5
- Colour - Black
12 Weight of Cable (Approx.) kg/km 176
Minimum Bending Radius mm 100
13 Electrical and Mechanical test
- Max DC Conductor Resistance, at 20 ⁰C Ω/km 12,1
- Max mutual Capacitance nF/km 250
- Voltage Test 1 Minute V 2000
14 Printing of Cable
BS EN 50288-7 IEC 60332-3-24 EXTRANA CU/PVC/ISOS/PVC-FR Cat.C LS AT AR UV ''SIZE'' 300 V (RE-Y(St)Y-FRLS AT AR UV Pimf )

Jakarta, 11 January 2023


Approval by Customer PT. PRIMA INDAH LESTARI

( ) ( Rahman Sajana Tresna W. )


PT. PRIMA INDAH LESTARI

CONSTRUCTION
CU/PVC/ISOS/PVC-FR Cat.C LS AT AR UV (RE-Y(St)Y-FRLS AT AR UV Pimf )

300 V

1. Conductor
Annealead Copper Wire
Round Stranded, Class 2

2. Insulation
Polyvinyl Chloride (PVC) Compound
Colour : Black and White With numbering

3. Individual Screen (IS)


Polyester tape with Drain wire 0.5 mm2 and Aluminium Mylar Tape

4. Overall Screen (OS)


Polyester tape with Drain wire 0.5 mm2 and Aluminium Mylar Tape

5. Outer Sheath
PVC Flame Retardant Cat C. Low Smoke Anti Termite Anti Rodent UV
Resistance Compound
Colour : Black

Drawing by Approval by Customer


DATE : 12 Dec 2022 PT.HUTAMA KARYA

STANDARD : BS EN 50288-7 IEC 60332-3-24

( Rahman Sajana Tresna W. )


Lembar data produk
Spesifikasi

20A 440V Wheatherproof Surface


Mount Triple Pole Isolating Switch
IP66
WHT20_GY

Disklaimer: Dokumentasi ini tidak ditujukan sebagai pengganti dan tidak untuk digunakan untuk menentukan kesesuaian atau keandalan produk ini untuk aplikasi pengguna
Main
Range Kavacha

Product or component type Isolating switch

Device short name W

Device application Control

Complementary
[Ie] rated operational current 20 A at 440 V AC-22A

Poles description 3P

Motor Rating M180

Width 82 mm

Height 170 mm

Depth 90 mm

Environment
IP degree of protection IP66

Standards IEC 60947-3

Environmental characteristic Weatherproof

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 17.5 cm

Package 1 Width 9 cm

Package 1 Length 8.3 cm

Package 1 Weight 733.333 g

Unit Type of Package 2 CAR

Number of Units in Package 2 30

Package 2 Height 36.5 cm

Package 2 Width 28.5 cm

Package 2 Length 43.5 cm

22 Des 22 1
Package 2 Weight 22000 g

Unit Type of Package 3 P12

Number of Units in Package 3 540

Package 3 Height 130 cm

Package 3 Width 80 cm

Package 3 Length 120 cm

Package 3 Weight 414000 g

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Penggantian yang disarankan

2
22 Des 22
Lembar data produk
Spesifikasi

20A 440V Wheatherproof Surface


Mount Double Pole Isolating Switch
IP66
WHD20_GY

Disklaimer: Dokumentasi ini tidak ditujukan sebagai pengganti dan tidak untuk digunakan untuk menentukan kesesuaian atau keandalan produk ini untuk aplikasi pengguna
Main
Range Kavacha

Product or component type Isolating switch

Device short name W

Device application Control

Complementary
[Ie] rated operational current 20 A at 440 V AC-22A

Poles description 2P

Motor Rating M180

Width 82 mm

Height 170 mm

Depth 90 mm

Environment
IP degree of protection IP66

Standards IEC 60947-3

Environmental characteristic Weatherproof

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 17.5 cm

Package 1 Width 9 cm

Package 1 Length 8.3 cm

Package 1 Weight 733.333 g

Unit Type of Package 2 CAR

Number of Units in Package 2 30

Package 2 Height 36.5 cm

Package 2 Width 28.5 cm

Package 2 Length 43.5 cm

22 Des 22 1
Package 2 Weight 22000 g

Unit Type of Package 3 P12

Number of Units in Package 3 540

Package 3 Height 130 cm

Package 3 Width 80 cm

Package 3 Length 120 cm

Package 3 Weight 414000 g

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Penggantian yang disarankan

2
22 Des 22
Product data sheet
Specifications

20A 250V 1 Gang Double Pole


Switch with Neon and Earth
KB31D20NE

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Vivace

Product or component type Switch

Device short name KB31

Device application Control

Device presentation Complete mechanism

Complementary
Switch function Double 1-way with earth

Actuator Rocker

Pilot light Neon indicator lamp

Number of gangs 1 gang

Colour tint White

Material Polycarbonate: grid plate


Polycarbonate: surround
Polycarbonate: base

Projecting depth 8 mm

Device mounting Flush

Mounting support Wall mounted

Fixing mode By screw M3.5

Fixing center 60.3 mm

Embedding depth 35 mm

Rated current 20 A at 250 V AC, inductive

[Ue] rated operational voltage 250 V AC

Network frequency 50 Hz

Contacts material Brass and phosphor bronze

Connections - terminals pillar terminal

Terminal identifier L2
N2
N1
L1

Tightening torque 0.4 N.m

Clamping connection capacity 2.5 mm²

Jan 20, 2023 1