TW 600 Please be noted of this manual to avoid problems by any misuse, before you use
YUDO product. Also, Deliver this manual to final processor and keep it in regular
User Manual place to check whenever it needs
ᆞOur policy is one of continuous improvement and we reserve the right to alter
product specifications at any time without giving notice.
ᆞYou can contact YUDO Headquarters or regional sales office for technical
advice.
Thank you for using YUDO product. ᆞNo part of this document may be reproduced in any form of by any means,
electronic, mechanical photocopying or otherwise, without prior written
permission of the copyright owner.
Please be noted of this manual to avoid problems
by any misuse, before you use YUDO product. 1) Appearance Checkup
You can contact YUDO Headquarters or Check actual controller(TW600) received differences from contractual
regional sales office for technical advice. configurations.
Check if there’s no fault on each timer units and externally. Contact supplier
or YUDO sales office if you find any damaged or missing parts.
4. Function and way of use ··················································· 08 Attention High Displays dangerous situation caused
electricity by the high-voltage electrical
5. MODE Specification ························································· 10
Ground Connection of the product is recommended
Grounding
to prevent electric shock and earth fault
6. Sequence system application ············································ 12
01
TW 600 User Manual
SEQUENCE INJECTION TIMER
2. Outline
3) Check List before use Timer 1) Uses
YUDO Sequence System is to provide the following benefits.
(1) Read all of these instructions before connecting power and turning on the
(1) Removal or Positioning of Weld Line
system. Follow all warnings and instructions mentioned on the manual.
Quality of Molded part can be improved by removing or re-positioning of
(2) Need regular repair to use the controller continuously and safely. weld lines on visual surfaces, or sections where a weld line would cause a
(3) Some components have their own product Lifecycle. weakness.
(2) Regulation of the Injection Quantity by Gate opeartion.
(4) One year warranty in normal condition. Injection balance can be adjusted in Family mold application.
(5) Input socket has danger of electric shock, Must not contact with body and (3) Improvement on Flash and short-shot
goods which is applying an electric current. By Gate open control in an orderly manner, it can eliminate Flash and
short-shot problem.
(6) Be sure that all of the cables (power cables, thermocouple cables, and input
power cables) are free from wear or damage. 2) Power Supply
(7) Establish locking device in case of maintenance this product. Main Power Supply (Timer Case) AC100~250V , 50/60 Hz, 1.5A
(8) To prevent Breakage or trouble this product, Be sure that the input power is Injection Signal Input Power DC 24V , AC100V~240V (Free Voltage)
rated and sequence of phases is correct. Solenoid Valve output voltage DC 24V , AC100V~250V (Free Voltage)
(*AC Solenoid Valveoutput must be same with AC input power.)
(9) Check the system is completely disconnected from the power source before
doing wearing. Operating temperature 0℃ ~ 50℃
PCB Structure
(10) Do not modify the controller or insert in-genuine parts.
① Power board Power PCB
(11) Do not disassemble or modify the controller. It may cause malfunction or ② Relay board Relay (Solenoid Valve ON/OFF)
injury. ③ CPU board MPU, out signal Input/Output Display,
(12) Check that earth/ground connection is in good condition. Switch Signal input
④ Front board Solenoid Valve output display
(Be sure to do ground connection for any eventuality) (DC24V , AC100~250V )
(13) Do not handle the controller with wet hands. ⑤ Mother board DC Main Power distribution and Connector
(14) When water infiltrated, Inspect certainly because there is electric leakage,
3) Environment Specifications
danger of fire.
(15) Clean up any water, oil, dirt, cleaning fluids etc. that may have spilled Installation Place Use interior space
during a mold change or since the last production run. It may cause injury. Operating temperature 0 ~ 50℃
Operating humidity 20 ~ 90%RH(Non-condensing)
Maximum use altitude Max. 2,000m
Storage temperature -25 ~ 70℃
500Vdc, Over 20MΩ
Insulation resistance
[Input Power-Field Ground, Input/Output-Field Ground]
Permissive signal resistance Less than 250Ω
1,500Vac, 50/60Hz 1min.
Dielectric
[Input Power-F/G, Input/Output-F/G, Input/Output-Input Power]
Vibration 10 ~ 55Hz, Bandwidth 0.75mm, 3 directions 4 swings, 5 min/swing
Shock withstand 147㎨, 3 directions-3 times
Magnetic influence Less than 400 AT/m
02 03
TW 600 User Manual
SEQUENCE INJECTION TIMER
MODE B
T1 DELAY OPEN
04 05
TW 600 User Manual
SEQUENCE INJECTION TIMER
ᆞTurning the timer on without notice when a worker maintains equipment -Never disassemble Power board of Timer when the timer power is on.
is very dangerous. Disassemble Board after confirming the safe. Put the power switch out,
wait and check residual electricity of inner timer.
ᆞIt can cause severe injury since currents can be flowing into the worker
accidently. Thus, the worker has to notice maintenance to prevent -A worker has to notice maintenance to prevent co-worker to operate
co-worker to operate timer. timer.
ᆞTouching on the side flowing currents accidently, it can cause electric -Take proper equipment and procedure during the maintenance.
shock and even severe injury or death by flowing currents in a flash. Thus, -Wear proper protective equipment during the maintenance.
please follow below procedures and instructions.
-Do not do anything while the power is on. Do not wear the accessory
-After confirming whether the power is off or not, please check residual including metal (ring, watch, bracelet and so on) that can be flowed
electricity on timer by tester. currents.
-Do not wear the accessory including metal (ring, watch, bracelet and so -In case you do maintenance while the power is on, please do work after
on) that can be flowed currents. It is at high risk for electric shock. making co-workers to be noticed for the work optically /acoustically.
ᆞIn case of melting a fuse or switching off, the reason can be a leakage -Attach the direction board showing an emergency exit in working area.
current. If you turn equipment on without notice, not only the power is off
-Be sure about emergency shelter and aisle.
but also the worker could be frosted cause by leakage current.
At this moment, you have to maintain equipment after disassembling -Remove obstructions on the emergency aisle.
equipment. -Attach the direction board showing emergency shelters in working area.
-Do not handle equipment when you are drunk or sick.
-Maintenance without guidance or supervision of manager is restricted.
ᆞBefore starting maintenance work, Inform that you’re doing maintenance
to everyone, and be careful not to enter the power on Timer while
working.
ᆞIf Timer is operating, make it stop working and check whether it’s
completely stopped.
If circumstances require, install power protection device.
06 07
TW 600 User Manual
SEQUENCE INJECTION TIMER
5. MODE Specification
YUDO Sequence Timer( TW 600 ) has 3 types of MODE.
The user can adjust Gate open/close/delay time for the optimal injection 3) MODE C
application in a convenient way. In MODE C, Users can carry out MODE B operation twice successively.
1) MODE A Ex1 ) Injection time : 20 seconds.
Selection Mode A - After the injection signal has been received, The first Del. time : 3 seconds / The first Open time : 4 seconds
The second Del. Time : 5 seconds / The second Open time : 6 seconds
the gate remains closed during the DEL time. After the Del time
Operation : After 3 sec. delay, the Gate opens for 4 seconds.
has elapsed, the gate Opens and remains open until the end of the
Successively after 5 sec. close, the Gate opens for 6 seconds.
injection signal.
Ex1 ) Injection time : 10 seconds DEL Time ( T1) : 3 second setting
Gate Open Gate Open
Operation : Gate opens 3 seconds after receiving the injection signal,
and remains open for 7 seconds, and then closes. T t1 t2 t3 t4
Gate Open 3 Sec 7 Sec 12 Sec 18 Sec 20 Sec
Signal On Signal Off
T t1 t2
3 Sec 10 Sec
t1 : First Delay Time t2 : First Open Time
Signal On Signal Off
t3 : Second Delay Time t4 : Second Open Time
t1 : Delay Time
2) MODE B 4) Injection signal extension function
Generally a valve Gate closes, when injection signal ends. But in some cases,
Selecting Mode B - After the injection signal has been received,
the valve Gate should be kept open even though the injection signal ends.
the gate remains Closed during the Del time.
Users can actualize this operation by setting MODE B with (-) open time.
After the Del time has elapsed, the gate Opens for the Open time setting
Then the Timer controller itself keeps the injection signal in an open condition.
After the Open time has elapsed, the gate closes and remains closed.
This function is specially used for controlling Extension Nozzle in Stack-mold
Ex1 ) Injection time : 10 seconds / DEL Time : 3 second setting
/ Open time : 4 second setting which needs to make a Gate close after HRS inner channel pressure becomes
Operation : Gate opens 3 seconds after receiving the injection signal, reduced enough.
and remains in the open condition for 4 seconds, Ex1 ) injection time : 10 sec. / Delay time : 3 sec. / Open time : (-) 2 sec.
and then closes. Operation : Gate opens 3 seconds after receiving the injection signal,
Gate Open
and still remains in the open condition for 2 seconds after
injection signal ends.
T t1 t2
3 Sec 10 Sec Gate Open
Signal On Signal Off T t1 t2
t1 : Delay Time / t2 : Open Time 3 Sec 10 Sec 12 Sec
Signal On Signal Off Signal Off
Ex2) Injection time : 10 seconds. / Del Time : 3 seconds
(Machine) (Timer)
/ Open time : 9 seconds.
Operation : After 3 seconds delay, the Gate opens 7 seconds after t1 : Delay Time / t2 : Open Time
receiving the injection signal, and then closes.
*Note : The gate closes as soon as the injection signal ends,
regardless of Open time setting Value.
Gate Open
T t1 t2
3 Sec 10 Sec 12 Sec
Signal On Signal Off
10 11
TW 600 User Manual
SEQUENCE INJECTION TIMER
Shot Short
Gate 1 Gate 2
(2) To inject products which have a big dimensional difference per cavity,
open G1 first to fill up the big size and then open G2 later to make
the balance. It can optimize the injection precision.
Gate 1 Gate 2
2) MODE B application
(1) To inject complicated products which have a big dimensional difference,
apply MODE 1 for Gate 1~4, and MODE B only for Gate 5. It is used to
fill up the very small sized dimension just before the injection ends. 2) Connector Assembly
Gate 2 Gate 1
Sol Valve No Connector Pin No Connector specifications
No. 1 1, 2
Gate 3 Gate 5 Gate 4
No. 2 3, 4
3) MODE C application
9 1
(1) It is used to apply 'one and after' injection signal control. No. 3 5, 6
10 2
Opening the gates first which could have fill-up Unbalance if Users 11 3 HAN 16A (250V 16A)
No. 4 7, 8
open the all gates at the same time, and then close the gates keeping 12 4 Mold : Male Insert
time with fill up. It is designed to avoid the excessive filling pressure. 13 5 (09 20 016 2612 )
No. 5 9, 10
14 6 Cable : Female Insert
Although this is also possible in MODE B operation, the function to (09 20 016 2812 )
No. 6 11, 12 15 7
keep up the holding pressure in channel by opening the Gate (The Timer
16 8
controller itself keeps the injection signal in an open condition )
No. 7 13, 14
is possible only in MODE C. MODE C is a new type of output pattern
which is able to optimize the various sequence controls to match the No. 8 15, 16
product feature and injection peculiarity.
Gate 1 Gate 2
Gate 5
Gate 3 Gate 4
12 13
TW 600 User Manual
SEQUENCE INJECTION TIMER
14 15
TW 600 User Manual
SEQUENCE INJECTION TIMER
Czech
Germany Finland
Netherlands Russia
Poland
UK
France Slovakia
Ukraine
Italy Romania Weihai Japan
Portugal Turkey Iran Qingdao Korea Tokyo
China USA Michigan
Syria
Spain Israel Bangladesh
Morocco Suzhou Kunshan Headquarters
Egypt
India Dongguan Plant
Thailand
Hongkong 24
(Manufacturing & Sales)
Mexico
Vietnam
Philippines Sales subsidiary 24
Malaysia
Sales office 61
Singapore
Agency 17 Peru
Indonesia
Australia
16 17