This document summarizes the primary current injection test of an 11kV feeder CT for the Bangladesh Power Development Board. The test was conducted on the Thakurgaon substation's Incomer Feeder 1 to check the CT ratios and secondary currents measured from injecting primary currents. The test found the secondary currents matched across the CT's cores when primary currents of 50-51A were injected into each phase.
This document summarizes the primary current injection test of an 11kV feeder CT for the Bangladesh Power Development Board. The test was conducted on the Thakurgaon substation's Incomer Feeder 1 to check the CT ratios and secondary currents measured from injecting primary currents. The test found the secondary currents matched across the CT's cores when primary currents of 50-51A were injected into each phase.
This document summarizes the primary current injection test of an 11kV feeder CT for the Bangladesh Power Development Board. The test was conducted on the Thakurgaon substation's Incomer Feeder 1 to check the CT ratios and secondary currents measured from injecting primary currents. The test found the secondary currents matched across the CT's cores when primary currents of 50-51A were injected into each phase.
Customer Bangladesh Power Development Board (BPDB)
Project Construction of 06 (Six) Nos. New 33/11 kV Substation Including Design, Supply, Installation & Commissioning on Turnkey Basis, Under 10-Town Power Distribution System Development Project. Contract 09845, Dated - 13.09.2012 Substation thakurgaon Location/Feeder Incomer Feeder – 1
TEST EQUIPMENT: AC CURRENT INJECTOR
MODEL: PULSER
CT RATIO: 800 - 400 / 5 – 5A
PRIMARY Secondary Current Measured
PHASE CURRENT INJECTED, I IR(Core1/Core2) IY(Core1/Core2) IB(Core1/Core2) IN(Core1/Core2) (A) (A) (A) (A) (A)