This document summarizes primary current injection testing of an 11kV feeder CT for Bangladesh Power Development Board. The test was conducted at Thakurgaon substation to check the ratio and polarity of the CT by injecting currents at its primary and measuring the corresponding secondary currents using a Pulser AC current injector. The test results show the injected and measured currents matched the CT's 800-400/5-5A ratio within acceptable limits.
This document summarizes primary current injection testing of an 11kV feeder CT for Bangladesh Power Development Board. The test was conducted at Thakurgaon substation to check the ratio and polarity of the CT by injecting currents at its primary and measuring the corresponding secondary currents using a Pulser AC current injector. The test results show the injected and measured currents matched the CT's 800-400/5-5A ratio within acceptable limits.
This document summarizes primary current injection testing of an 11kV feeder CT for Bangladesh Power Development Board. The test was conducted at Thakurgaon substation to check the ratio and polarity of the CT by injecting currents at its primary and measuring the corresponding secondary currents using a Pulser AC current injector. The test results show the injected and measured currents matched the CT's 800-400/5-5A ratio within acceptable limits.
Customer Bangladesh Power Development Board (BPDB)
Project Construction of 06 (Six) Nos. New 33/11 kV Substation Including Design, Supply, Installation & Commissioning on Turnkey Basis, Under 10-Town Power Distribution System Development Project. Contract 09845, Dated - 13.09.2012 Substation thakurgaon Location/Feeder Bus Coupler
TEST EQUIPMENT: AC CURRENT INJECTOR
MODEL: PULSER
CT RATIO: 800 - 400 / 5 – 5A
PRIMARY Secondary Current Measured
PHASE CURRENT INJECTED, I IR(A) IY(A) IB(A) IN(A) (A) R 50 0.312 0 0 0.312