PLUMBING LEGEND:

AC AIR CHAMBER PPR CWL POLYPROPYLENE COLD WATER LINE WC WATER CLOSET

PT BLADDER/ PNEUMATIC TANK PPR DS POLYVINYL CHLORIDE DOWNSPOUT LAV LAVATORY 50 600 50
E ELECTRIC MOTOR PVC DP POLYVINYL CHLORIDE DRAIN PIPE KS KITCHEN SINK
250 100 250
P PUMP PVC DS POLYVINYL CHLORIDE DOWNSPOUT

U UNION PATENTE CO CLEAN OUT

100
SP
FTV FOOT VALVE PVC SP POLYVINYL CHLORIDE SOIL PIPE
VAC
FV FLOAT VALVE PVC AC POLYVINYL CHLORIDE VENT.
ACROSS CEILING
PP PRIMING PORT @ 200mm O.C. BENT UP 2 OUT OF 3 AT L/4
CB CATCH BASIN V
PVC VP POLYVINYL CHLORIDE VENT. PIPE
@ 200mm O.C. B.W. FROM FACE SUPPORT BOTHWAYS - COVER DETAIL
V S
P-* SCALE 1 : 20 M.
CDP CONCRETE DRAIN PIPE PVC VS POLYVINYL CHLORIDE VENT STACK 8600
VTR
CV CHECK VALVE PVC VTR/ W POLYVINYL CHLORIDE VENT THRU 700 C.O.
ROOF/ WALL 150 4000 150 2000 150 2000 150
HB HOSE BIBB
600 600 600
N.G.L.
FD FLOOR DRAIN WP PVC WP POLYVINYL CHLORIDE WASTE PIPE 150mm THK.+ FIN. SLAB
WS
PPR POLYPROPYLENE COLD WATER LINE PVC WS POLYVINYL CHLORIDE WASTE STACK

VAR.
600 OF 3 @ L/4 FROM FACE
PPR POLYPROPYLENE COLD WATER RISER PPR POLYPROPYLENE COLD WATER RISER SUPPORT B.W.
G.V.
GV GATE VALVE RD ROOF DRAIN
CO MH CO MH CO MH CO MH

300 150
150
MH MAN HOLE UD URINAL DRAIN

250
OUTLET

300

300

350
350

400
AIR SPACE

400
INLET AIR SPACE WATER LEVEL AIR SPACE
PLUMBING NOTES: WATER LEVEL INLET
1. GRADES OF HORIZONTAL PIPINGS
RUN ALL HORIZONTAL PIPINGS IN PERFECT ALIGNMENT AND AT A
FORM GRADE NOT LESS THAN TWO PERCENT (2%) CONCRETE WALL W/ HOT
2100

1800
APPLIED ASPHALT WATER-

1500
2. CHANGE IN DIRECTION DIGESTIVE CHAMBER LEACHING CHAMBER LEACHING CHAMBER PROOFING (INSIDE FACE)
ALL CHANGE IN DIRECTION SHALL BE MADE BY APPROPRIATE
1 2 WALL REINFORCEMENT
QUARTER BEND, SIXTH-EIGHT OR SIXTEENTH BEND. WHEN
THE CHANGE OF FLOW IS FROM HORIZONTAL TO VERTICAL, A @ 200mm O.C. B.W.
SINGLE 81 BEND COMBINATION MAY BE USED ON WASTE LINE, TEE

150
AND CROSSES MAYBE USED IN BENT PIPES.
1% SLOPE
150

3. PROHIBITED FITTINGS
NO DOUBLE HUB OR TEE BRANCH SHALL BE USED ON HORIZONTAL
SOIL AND WASTE LINES, THE DRILLINGS AND TAPPING OF HOUSE DRAIN,
CONCRETE WALL W/ HOT REBARS @ 300mm B.W.
WASTE OR VENT PIPES AND USE OF SADDLE HUB AND BEND ARE PROHIBITED.
APPLIED ASPHALT
1 LONGITUDINAL SECTION DETAIL GRAVEL
REBARS @ 300mm BOTHWAYS
4. PIPE CLEAN-OUTS
WATERPROOFING P-* SCALE 1 : 50 M.
CLEAN-OUTS ARE REQUIRED UNDER THE FOLLOWING CONDITIONS:
(INSIDE FACE)
2 CROSS SECTION DETAIL
a) EVERY CHANGE OF HORIZONTAL DIRECTION EXCEEDING
S-1a 150mm THK. + FIN. SLAB P-* SCALE 1 : 50 M. 150mm THK CHB w/
TWENTY TWO AND ONE-HALF DEGREES (22 12
b) ONE AND ONE-HALF METERS (1.50m.) INSIDE THE 700
PROPERTY LINES BEFORE THE HOUSE DRAINAGE 2 OUT OF 3 @ L/4 FROM FACE SUPPORT 150 400 150 @ 2-LAYER VERT.
CONNECTION. @ 600mm O.C.
BARS TOP/ BOT. ON BOTHWAYS 2% SLOPE75 75
c) EVERY FIFTEEN METERS (15.00 m.) IN HORIZONTAL RUN OF
PIPES.
TWO PARALLEL SIDE

100
d) AT THE END OF ANY HORIZONTAL PIPE LINES.
8600
5. THE DIGESTION CHAMBER OF SEPTIC VAULT MUST BE 2% SLOPE

(VARIABLE)
WATERPROOFED. 150 4000 150 2000 150 2000 150 50

600 MIN.
6. NOT LESS THAN 0.30 METER OF AIR SPACE MUST BE LEFT 600 600 600
BETWEEN THE TOP OF THE SEWAGE AND THE UNDER PART OUTLET
OF VAULT ROOF SLAB. INLET

150

100
150

7. NO SEPTIC VAULT SHALL BE CONSTRUCTED UNDER THE BUILDING.

100
8. ALL PLUMBING WORKS SHALL BE UNDER THE SUPERVISION OF A
LICENSED MASTER PLUMBER AND LICENSED PLUMBING
CONTRACTOR.
SECTION
DESIGN CRITERIA: OUTLET 700
CO CO CO
MH MH MH
2300

2000

600

1
i. LIVE LOAD ----------------------------------- 1000 Pa P-* 150 150

ii. ALLOWABLE STRESSES

150
1. CONCRETE (DRAINAGE PIPE)
a. FOR FOOTING, BEAMS AND SLABS CO
fc" = 20 MPa

400
700
150

2. CONCRETE MASONRY UNITS (LOAD BEARING CHB)


fm' = 6.90 Mpa, fm = 2.41 Mpa
INLET OUTLET

150
3. REINFORCING STEEL BARS S2 150mm THK. + FIN. SLAB

fy = 230 Mpa 2
P-*
2/3 OUT @ L/4 FACE SUPPORT AND SHORT PLAN
4. ASSUMED ALLOWABLE BEARING CAPACITY Y = 1000 KPa
INLET
NOTE: - SEPTIC TANK PLAN DETAIL - CATCH BASIN DETAIL
*-* SCALE 1 : 50 M. P-* SCALE 1 : 30 M.
WATER TABLE IS 15000 BELOW GROUND LEVEL.

PROJECT SHEET CONTENTS: DESIGNED AND CADD: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: SET NO. SHEET NO.
AND
REPUBLIC OF THE PHILIPPINES
LOCATION:
PROPOSED:
DESIE JAN S. MAGBANUA
LONGITUDINAL SECTION DETAIL ADMIN.ASSIST.III
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS SEPTIC TANK PLAN DETAIL
ANTONIO P. CALISTON, JR., ASEP BOD
REGION VI, WESTERN VISAYAS PERMANENT EVACUATION CENTER COVER DETAIL
CROSS SECTION DETAIL ENGINEER II P-1
MULTI-PURPOSE COVERED COURT CATCH BASIN DETAIL MARILOU G. ZAMORA JOSE AL V. FRUTO, CES E LEA N. DELFINADO, CESO IV
FORT SAN PEDRO ILOILO CITY
PLUMBING NOTES & LEGENDS CHECKED: 1 1
B
(STANDARD) SEVERO A. RUIZ OIC - DIVISION CHIEF OIC - ASSISTANT REGIONAL DIRECTOR REGIONAL DIRECTOR
OIC - ASSIST.DIVISION CHIEF
LOCATION: BRGY.HILAMUNAN, KABANKALAN CITY, NEGROS OCCIDENTAL
SLAB on FILL
t = 300mm + FIN. + WP
4000
@ TOP PORTION
4000
TYPICAL IN ALL EXTERIOR SURFACES
100
320 800

@ BOTTOM PORTION BOTH FACE, STAGGERED; TYPICAL IN


100
ALL SURFACES
MH

300
)
AL
PIC

500
( TY
PI T
MP FIN. GRADE LINE FIN. GRADE LINE
SU
RDS
A
OW
ET

1800
O P
2500

3340
SL 100mm THICK
1% WELL COMPACTED
GRAVEL FILL
1% SLOPE

30
TOWARDS SUMP PIT

0
280
SUMP PIT
100 mm THK.
+ WATERPROOFING

100mm THK. LEAN CONCRETE SLAB W/

- PLAN (BOTTOM VIEW) CISTERN TANK 300 600 300


*-* SCALE 1 : 50 M.

3800 TOP SLAB - LONGITUDINAL SECTION OF CISTERN TANK


S-1, t = 150mm + FIN. + WP *-* SCALE 1 : 50 M. TYPICAL IN ALL EXTERIOR SURFACES
3100
ALTERNATE AT L/4; FROM FACE OF
SUPPORT 200 300
VERT. BARS & 600mm BOTH FACE, STAGGERED; TYPICAL IN
100
ALTERNATE AT L/4; FROM FACE OF O.C. , TEMP. BARS ALL SURFACES
100
SUPPORT

300

500
MANHOLE
FIN. GRADE LINE FIN. GRADE LINE

1800
2500

3100

2370
300
100mm THICK WELL COMPACTED
GRAVEL FILL
100mm THK. LEAN CONCRETE
SLAB (REFER TO STRUCT'L. DET.)

300 2500 300


100mm THK. + WATERPROOFING 100mm THK. + WATERPROOFING

- PLAN (TOP VIEW) CISTERN TANK - CISTERN TANK DETAILS - TRANSVERSE SECTION OF CISTERN TANK
*-* SCALE 1 : 50 M. *-* SCALE 1 : 50 M. *-* SCALE 1 : 50 M.

PROJECT SHEET CONTENTS: DESIGNED AND CADD: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: SET NO. SHEET NO.
AND
REPUBLIC OF THE PHILIPPINES
LOCATION:
PROPOSED:
DESIE JAN S. MAGBANUA
SCHEDULE OF ADMIN.ASSIST.III
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS COLUMNS & DETAILS
ANTONIO P. CALISTRON, JR., ASEP BOD
REGION VI, WESTERN VISAYAS PERMANENT EVACUATION CENTER ENGINEER II P-2
MULTI-PURPOSE COVERED COURT MARILOU G. ZAMORA JOSE AL V. FRUTO, CES E LEA N. DELFINADO, CESO IV
FORT SAN PEDRO ILOILO CITY
CHECKED: 2 2
B
(STANDARD) SEVERO A. RUIZ OIC - DIVISION CHIEF OIC - ASSISTANT REGIONAL DIRECTOR REGIONAL DIRECTOR
OIC - ASSIST.DIVISION CHIEF
LOCATION: VARIOUS LOCATION