VIJAYNAGAR,MYSORE
EB Requirement
Connected Load 94 kW
Maximum demand load 88 kW
Demand load for the facilities @ 0.9 power factor 98 kVA
DG Requirement
Maximum demand load for facility 88 kW
KVA @ 0.8 PF 110 kVA
@85% Loaded DG set 129 kVA
Require 1 no. 140 KVA DG set for 100 % power back-up.
Recommended 100% power backup.
We required Single feeder up to Main Electrical room after Auto Power factor correction system and auto
change over system (APFC 60 KVAR)
FEEDER REQUIREMENTS :
Breaker specs : 200 Amp. (25 KA) FP, MCCB. with Energy meter.
Feeder No-1 Recommended 1R x 3.5C x 150 sq.mm. XLPE AL armoured cable from Builder's Changeover panel
up to Main Electrical Panel as mentioned above also cabling from Main panel to all DB's & its End Termination
as per Style Union requirement. 2R # 25 x
3mm GI strip for Earthing purpose. Separate Earthing for the server & low system.
NOTE :
1 100% D.G. SET BACK UP REQUIRED.
2 We have considered Electrical load for HVAC as per VRV Unit.