Professional Documents
Culture Documents
Power Transformers
Ke is dependent upon the core dimensions, the specific resistance of a lamination sheet, and the mass of the
core. Also,
P h = Kh f B Mn (W) (64.2)
In Eq. (64.2), Ph is the hysteresis power loss, n is the Steinmetz constant (1.5 < n < 2.5) and Kh is a constant
dependent upon the nature of core material and varies from 3210–3m to 20210–3m, where m = core mass in
kilograms.
The core loss therefore is
Pe = Pe + P h (64.3)
Transformer Windings
The windings of the power transformer may be either copper or aluminum. These conductors are usually made
of conductors having a circular cross section; however, larger cross-sectional area conductors may require a
rectangular cross section for efficient use of winding space.
The life of a transformer insulation system depends, to a large extent, upon its temperature. The total
temperature is the sum of the ambient and the temperature rise. The temperature rise in a transformer is
intrinsic to that transformer at a fixed load. The ambient temperature is controlled by the environment the
transformer is subjected to. The better the cooling system that is provided for the transformer, the higher the
“kVA” rating for the same ambient. For example, the kVA rating for a transformer can be increased with forced
air (fan) cooling. Forced oil and water cooling systems are also used. Also, the duration of operating time at
high temperature directly affects insulation life.
Taps
Power transformer windings typically have taps, as shown. The effect
on transformer models is to change the turns ratio.
df df df
v1 = N1 v2 = N2 v3 = N3 (64.4)
dt dt dt
where f is the core flux. This produces:
v1 N v2 N v3 N
= 1 = 2 = 3 (64.5)
v2 N2 v3 N3 v1 N1
For sinusoidal steady state performance:
N1 N2 N3
V1 = V2 V2 = V3 V3 = V1 (64.6)
N2 N3 N1
where V, etc. are complex phasors.
The circuit symbol is shown in Fig. 64.2(b). Ampere’s law requires that
0 = N 1i 1 + N 2i 2 + N 3 i 3 (64.8)
N 1I 1 + N 2 I 2 + N 3I 3 = 0 (64.9)
Equations (64.6) and (64.9) are basic to understanding transformer operation. Consider Eq. (64.6). Also
note that –V1, –V2, and –V3 must be in phase, with dotted terminals defined positive. Now consider the total
input complex power –S.
Hence, ideal transformers can absorb neither real nor reactive power.
It is customary to scale system quantities (V, I, S, Z) into dimensionless quantities called per-unit values.
The basic per-unit scaling equation is
actual value
Per-unit value =
base value
The base value always carries the same units as the actual value, forcing the per-unit value to be dimensionless.
Base values normally selected arbitrarily are Vbase and Sbase. It follows that:
S base
I base =
V base
V base V2
Z base = = base
I base S base
© 1999 by CRC Press LLC
When per-unit scaling is applied to transformers Vbase is usually taken as Vrated as in each winding. Sbase is
common to all windings; for the two- winding case Sbase is Srated, since Srated is common to both windings.
Per-unit scaling simplifies transformer circuit models. Select two primary base values, V1base and S1base. Base
values for windings 2 and 3 are:
N2 N3
V2 base = V1 V3 base = V1 (64.11)
N 1 base N 1 base
and
By definition:
It follows that
N1 N1
I 2 base = I1 I 3 base = I1 (64.14)
N 2 base N 3 base
V1pu = V2 pu = V3 pu (64.15)
I 1pu + I 2 pu + I 3 pu = 0 (64.16)
The basic per-unit equivalent circuit is shown in Fig. 64.2(c). The extension to the n-winding case is clear.
The circuit of Fig. 64.3 is a refinement on that of Fig. 64.2(c). The values R1, R2, R3, X1, X2, X3 are all small
(less than 0.05 per-unit) and Rc, Xm, large (greater than 10 per-unit). The circuit of Fig. 64.3 requires that all
values be in per-unit. Circuit data are available from the manufacturer or obtained from conventional tests. It
must be noted that although the circuit of Fig. 64.3 is commonly used, it is not rigorously correct because it
does not properly account for the mutual couplings between windings.
The terms primary and secondary refer to source and load sides, respectively (i.e., energy flows from primary
to secondary). However, in many applications energy can flow either way, in which case the distinction is
meaningless. Also, the presence of a third winding (tertiary) confuses the issue. The terms step up and step
down refer to what the transformer does to the voltage from source to load. ANSI standards require that for a
two-winding transformer the high-voltage and low-voltage terminals be marked as H1-H2 and X1-X2, respec-
tively, with H1 and X1 markings having the same significance as dots for polarity markings. [Refer to ANSI
C57 for comprehensive information.] Additive and subtractive transformer polarity refer to the physical posi-
tioning of high-voltage, low-voltage dotted terminals as shown in Fig. 64.4. If the dotted terminals are adjacent,
then the transformer is said to be subtractive, because if these adjacent terminals (H1-X1) are connected together,
the voltage between H2 and X2 is the difference between primary and secondary. Similarly, if adjacent terminals
X1 and H2 are connected, the voltage (H1-X2) is the sum of primary and secondary values.
Z e = Z1 + Z 2 (64.17)
Rc ( jXm )
Zm = (64.18)
Rc + jXm
Circuits (a) and (b) are appropriate when –Zm is large enough that magnetizing current and core loss is
negligible.
Pout
h= (64.19)
Pin
where Pout is output power in watts (kW, MW) and Pin is input power in watts (kW, MW).
The situation is clearest for the two-winding case where the output is clearly defined (i.e., the secondary
winding), as is the input (i.e., the primary). Unless otherwise specified, the output is understood to be rated
power at rated voltage at a user-specified power factor. Note that
The transformer is frequently modeled with the circuit shown in Fig. 64.6. Transformer losses are made up of
the following components:
A second concern is fluctuation of secondary voltage with load. A measure of this situation is called voltage
regulation, which is defined as follows:
V2 NL - V2 FL
Voltage Regulation (VR) = (64.23)
V2 FL
where V2FL = rated secondary voltage, with the transformer supplying rated load at a user-specified power
factor, and V2NL = secondary voltage with the load removed (set to zero), holding the primary voltage at the
full load value.
A complete performance analysis of a 100 kVA 2400/240 V single-phase transformer is shown in Table 64.1.
Test Data
Secondary Quantities; LOW Voltage Side Primary Quantities; HIGH Voltage Side
The short-circuit test circuit arrangement is shown in Fig. 64.8. The objective is to derive equivalent circuit
data from the test data provided in Fig. 64.8. Note that measurements are made in winding “i”, with winding
“j” shorted, and winding “k” left open. The short circuit impedance, looking into winding “i” with the
transformer so terminated is designated as Zij. The indices i, j, and k, can be 1, 2, or 3.
The impedance calculations are done in per-unit; base values are provided in Fig. 64.8(c). The transformer
ratings of the transformer of Fig. 64.2(a) would conventionally be provided as follows:
3f 3W Transformer
15kVY/115kVY/4.157kVD
100/100/20 MVA
where 3f means that the transformer is a three-phase piece of equipment (as opposed to an interconnection
of three single-phase devices). 3W means three three-phase windings (actually nine windings). Usually the
schematic is supplied also. The 15 kV rating is the line (phase-to-phase) value; three-phase apparatus is always
rated in line values. “Y” means winding No. 1 is internally wye connected. 115kVY means that 115 kV is the
line voltage rating, and winding No. 2 is wye connected. In 4.157kVD, again, “4.157kV” is the line voltage rating,
and winding No. 3 is delta connected. 100/100/20 MVA are the total (3f) power ratings for the primary,
secondary, and tertiary winding, respectively; three-phase apparatus is always rated in three-phase terms.
The per-unit bases for S3fbase = 100 MVA are presented in Fig. 64.8(b). Calculating the short-circuit imped-
ances from the test data in Fig. 64.8(c):
Vi line / 3
Z ij =
I i line
R3 f /3
Rij =
I 12
line
X ij = Z ij2 - Rij2
© 1999 by CRC Press LLC
FIGURE 64.9 Autotransformer connection. (a) Conventional step-up connection; (b) autotransformer connection; (c)
part (b) redrawn.
1
Z1 =
2
(
Z 12 - Z 23 + Z 31 )
1
Z2 =
2
(
Z 23 - Z 13 + Z 12 )
1
Z3 =
2
(
Z 31 - Z 12 + Z 23 )
Results are shown in Fig. 64.8(d). Observe that the Y–D winding connections had no impact on the calculations.
Another detail deserves mention. Although the real and reactive parts of the short-circuit impedances (–Z12,
–Z23, ––Z31) will always be positive, this is not true for the transformer impedances (––Z1, ––Z2, ––Z3). One or
more of these can be, and frequently is, negative for actual short-circuit data. Negative values underscore that
the circuit of Fig. 64.7 is a port equivalent circuit, producing correct values at the winding terminals.
64.5 Autotransformers
Transformer windings, though magnetically coupled, are electrically isolated from each other. It is possible to
enhance certain performance characteristics for transformers by electrically interconnecting primary and sec-
ondary windings. Such devices are called autotransformers. The benefits to be realized are lower cost, smaller
size and weight, higher efficiency, and better voltage regulation. The basic connection is illustrated in Fig. 64.9.
The issues will be demonstrated with an example.
Consider the conventional connection, shown in Fig. 64.9(a).
V2 = aV1
1
I2 = I
a 1
S rating = V1I 1 = V2 I 2 = S load
© 1999 by CRC Press LLC
Now for the autotransformer:
V2 = V1 + bV1 = (1 + b )V1
I 1 = I 2 + bI 2 = (1 + b )I 2
1+b=a
æ b ö
S rated = S load ç ÷
è1+b ø
For example if b = 1 (a = 2)
Defining Terms
Autotransformer: A transformer whose primary and secondary windings are electrically interconnected.
Polarity: Consideration of in-phase or out-of-phase relations of primary and secondary ac currents and
voltages.
Primary: The source-side winding.
Secondary: The load-side winding.
Tap: An electrical terminal that permits access to a winding at a particular physical location.
Transformer: A device which converts ac voltage and current to different levels at essentially constant power
and frequency.
Related Topics
1.3 Transformers • 3.4 Power and Energy • 3.5 Three-Phase Circuits
References
ANSI Standard C57, New York: American National Standards Institute.
S. J. Chapman, Electric Machinery Fundamentals, 2nd ed, New York: McGraw-Hill, 1991.
V. Del Toro, Basic Electric Machines, Englewood Cliffs, N.J.: Prentice-Hall, 1990.
M.E. El-Hawary, Electric Power Systems: Design and Analysis, Reston, Va.: Reston Publishing, 1983.
O.I. Elgerd, Electric Energy Systems Theory: An Introduction, 2nd ed., New York: McGraw-Hill, 1982.
R. Feinburg, Modern Power Transformer Practice, New York: Wiley, 1979.
A.E. Fitzgerald, C. Kingsley, and S. Umans, Electric Machinery, 5th ed., New York: McGraw-Hill, 1990.
Further Information
For a comprehensive coverage of general transformer theory, see Chapter 2 of Electric Machines by G.R. Slemon
and A. Straughen (Addison-Wesley, 1980). For transformer standards, see ANSI Standard C57. For a detailed
explanation of transformer per-unit scaling, see Chapter 5 of Power Systems Analysis by C.A. Gross (John Wiley,
1986). For design information see Practical Transformer Design Handbook by E. Lowden (TAB, 1989).