TEST SAPERATOR REBAR CALCULATION FROM STAAD OUTPUT REV.

DOC. NO. DATE 5/3/2023

STRIP WIDTH = 1000 mm

(LEFT) SIDE WALL THICKNESS = 450 mm 375

CONCRETE GRADE = 25 N/sqm

REBAR GRADE = 420 N/sqm

COVER = 75 mm ρ Ast (sqmm)


LEFT SIDE WALL MOMENT FROM STAAD +VE = 50 kN m AS PER HANDBOOK OF CONCRETE 0.002 750
ENGINEERING BY MARK FINTEL
LEFT SIDE WALL MOMENT FROM STAAD -VE = 99 kN m 0.003 1125

REBAR CALCULATION

Dia 16
LEFT SIDE WALL MOMENT FROM STAAD +VE @ 150 mm C/C 1341.0 Sqmm Pt 0.36 GOOD
Dia 16
LEFT SIDE WALL MOMENT FROM STAAD -VE @ 150 mm C/C 1341.0 Sqmm Pt 0.36 GOOD

** REINFORCEMENT IS AT TOP BOTTOM BOTH WAYS

ρ Provided ρ Mini
LEFT SIDE WALL MOMENT FROM STAAD +VE 0.36 0.10 GOOD

LEFT SIDE WALL MOMENT FROM STAAD -VE 0.36 0.10 GOOD

THICKNESS CHECK
Shear strength provided by concrete = fVc = f0.17 (f'c)0.5 = 0.4172 N/sqmm where, f = 0.75

N/sqmm
SHEAR STRESS IN (LEFT) SIDE WALL FROM STAAD ANALYSIS = 0.360 GOOD
=