You are on page 1of 1

Group 1 rooms can be protected with any of clean agent extinguishing systems

which can be HFC-227ea, FK-5-1-12 or Inert Gas Suppression Systems.


According to feeedback from CSCEC, suppression type is chosen as IG 55
Systems.

Group 2 rooms can be protected with automatic foam extinguishing systems or


automatic dry powder systems. According to feeedback from CSCEC,
suppression type is chosen as Automatic Dry Powder Systems.

2. Properties of Areas To Be Protected for Group 1 Rooms


There are 9 pieces of rooms that are going to protected by IG 55 Inert Gas
Suppression System.

All room dimension infos are shown below;

Raised Main Total


Area False Floor Total
# Room Name Floor Room Volume
(m2) Height (m) Height (m)
Height (m) Height (m) (m3)

1 DATA CENTER 86 0 5 0 5 430


LOCAL DE
2 170 0 5.46 0 5.46 928.2
GENERATEUR
LOCAL DE TABLEAU
3 57 0 5.46 0 5.46 311.22
DE SECOURS
LOCAL MOYENNE
4 67.1 0 5.46 0 5.46 366.366
TENSION
LOCAL DE L'ASI ET
5 DES BATTERIES DE 110 0 5.46 0 5.46 600.6
L'ASI
LOCAL DES
6 114 0 5.46 0 5.46 622.44
TRANSFORMATEURS