Total length of the Building,L = 36.

3 m
Total width of the Building,B = 11.684 m
Eave height,z = 6.3 m
Slope,q = 7.30 degrees
Bay spacing = 6.1 m
Purlin spacing = 1.168 m
Wind speed,Vb = 215 km/h
Side wall span = 5.84 m
Exposure type = A
Importance factor,CI = 1
Colatteral Load = 0 KN/m2
Live Load = 1 KN/m2
Dead load on Mazzanine Floor = 0 KN/m2
Live load on Mazzanine Floor = 0 KN/m2
Weight of Roof sheet = 4.5 Kg/m2 Thick
Weight of Purlin = 2.8 Kg/m
Mean roof height,h = 6.3 m
CC = 0.0000472
Cz ( for wall ) = 0.423
Cz ( for roof ) = 0.423
qz = 0.923 KN/m2
qh = 0.923 KN/m2
CG ( for wall ) = 1.584
CG ( for roof ) = 1.584
Internal pressure coefficient = 0.25
Internal pressure coefficient = -0.25
Dead Load on Roof = 0.40 KN/m
Colatteral Load on Roof = 0.00 KN/m
Live Load on Roof = 6.10 KN/m
Dead Load on Mazzanine Floor = 0.00 KN/m
Live Load on Mazzanine Floor = 0.00 KN/m
Design wind pressure Pz = 1.462 Cp
Internal wind pressure Pi = 0.231 KN/m2
Internal wind pressure Pi = -0.231 KN/m2
Case-1=Design Wind pressure P = 1.693 KN/m2
Case-2=Design Wind pressure P = 0.365 KN/m2

Wall
Norm
Windward Leeward Side wall Others Windward
Cp = 0.8 -0.36 -0.7 -0.95 -0.04 & -0.85
Wind Load on Frame (KN/m) = 7.13 -3.21 -5.98 -8.47 -0.36 & -7.58
Roof
Normal to ridge
Windward Leeward Others
-0.04 & -0.85 -0.7 -1.01
-0.36 & -7.58 -6.24 -9.01