GENERAL NOTES

ELECTRICAL NOTES:
Z 1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED
EXHAUST AIR REQUIREMENTS:
AND WIRED TO J-BOX D BY CADDY. RECONNECTED ON JOBSITE 1. EXHAUST C.F.M. BASED ON 350 C.F.M. PER LINEAR FOOT.
BY ELECTRICAL CONTRACTOR. 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE OPERATION AT MEAN SEA LEVEL.
3" BY ELECTRICAL CONTRACTOR. 3. DUCT SIZE BASED ON 1,500 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE HINGED ACCESS
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM 1 EXHAUST FAN REQUIREMENTS:
DOORS
COOKING EQUIPMENT" 1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
NATIONAL SANITATION FOUNDATION TOTAL EXHAUST : 3,850 C.F.M. FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
4'-6" 2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT"
D WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR 12" X 31" EXHAUST DUCT MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER 1 3,850 C.F.M. @ 1.60" S.P.
CONTROL # 3177269 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS (9) HANGER
BRACKETS
CL ANSUL
ENCLOSURE 2.
SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.
MAKE-UP AIR MUST BE TEMPERED-HEATED OR COOLED-CONSISTENT
THE BOCA NATIONAL MECHANICAL CODE (SEE DETAIL A-A) WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND
CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT APPLICABLE CODES.
5'-6"
STANDARD MECHANICAL CODE (SBCCI)
11'-0" 1'-0" INSTALLATION:
SECTION 504 - COMMERCIAL HOODS 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES.
12'-0"
UNIFORM BUILDING CODE (ICBO) CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE
INTERNATIONAL MECHANICAL CODE (IMC) PLAN AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION.
SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS
SECTION 507 - COMMERCIAL KITCHEN HOODS SCALE: 1/2"=1'-0"
STN./STL. ENCLOSURE PANEL RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE
EXCLUDES CODE #507.2.1.1, CONSULT FACTORY
FOR COMPLIANCE OPTIONS. Z FURNISHED BY CADDY
2.
CONSTRUCTION (WALL, CEILINGS, ETC.).
VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO
AND INSTALLED BY K.E.C.
HANDLE ENVIRONMENTAL AIR.
3. ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE-OFF COLLAR TO
BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH
JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG,
GREASE AND WATER TIGHT.
4'-6" 4. MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS.
CONSTRUCTION:
(2) RECESSED FLUORESCENT 1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH
3'-6" (48") LIGHT FIXTURES CADDY SPECIFICATIONS.
3"
2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.

K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING 1'-0" FIRE PROTECTION:
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION A-A (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR 4" BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
2'-0" ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO
HIGH VELOCITY ELECTRICAL REQUIREMENTS:
SERVICE COMPONENTS AND UTILITIES 1 GREASE EXTRACTOR
1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.

12'-0"
STN./STL. ENCLOSURE PANEL FIN. CLG.
AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F,
FURNISHED BY CADDY HEIGHT REMOVABLE
BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR
AND INSTALLED BY K.E.C. [X] VERIFY STN./STL.
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD
GREASE CUP

2'-0"
STN.\STL.
GREASE CUPS 8'-6"
TOP OF
VENTILATOR JADE
1'-2" 1'-4" JMRH-48B
2'-0" 1'-6" 1'-0" 1'-1" CHARBROILER
1/2" DIA. BY 6'-0" LONG PLATED PITCO PITCO 6'-6" ITEM #161
STEEL HANGER RODS AND BOLTS 2-SSH55RSSTCS/FD PCF-14 A.F.F.
JADE JADE
FURNISHED BY K.E.C. FRYER DUMP STATION
7"* JMRH-48B JMRH-2A 7"*
ITEM #159 ITEM #160 CHARBROILER RANGE
ITEM #161 ITEM #163
JADE
9/16" HOLE FOR 1/2" 12 GA. STN. STL. JMRH-12G
THREADED ROD HANGER BRACKETS GRIDDLE JADE
(RODS AND HARDWARE FULLY WELDED TO VENTILATOR ITEM #164 JRLH-04S-T-72
BY K.E.C.) BY CADDY REFRIGERATED
JADE BASE
JLRH-04S-T-72 ITEM #162
REFRIG. BASE
ITEM #162

CM

ELEVATION SECTION Z-Z R

SCALE: 1/2"=1'-0" SCALE: 3/4"=1'-0" R

Intertek

HANGER BRACKET DETAIL A-A REVISIONS


SCALE: 1/4"=1" ROUGH-IN SCHEDULE REV DATE BY REMARKS

SYM QTY DESCRIPTION A 4-18-12 DRA ADDED MUA, AN ANSUL BOX, AND A 12" RANGE
EQUIPMENT SCHEDULE
K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA REMOVED CEILING SUPPLY PLENUMS

* - MINIMUM OVERHANG FROM EDGE OF COOKING D 1 120V, 60HZ, 1PH, 0.16 K.W. CONNECTED LOAD
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER C 11-2-12 DRA REVISED PER RECEIVED P.O.

LINE-UP PRIOR TO FABRICATION OF VENTILATORS, EQUIPMENT TO END OF HOOD MUST BE 6" D 1-7-13 DRA NO CHANGES
SHBC-C-W-132-ND-54
AND TO NOTIFY CADDY OF ANY CHANGES. E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.

ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH


STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
CADDY NO. 10710 -3 ITEM NO. 165
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. INSTALLATION INFORMATION LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES CUST: SINGER EQUIPMENT
ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR VENTILATOR TO BE SHIPPED IN (1) UNIT.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR INTO KITCHEN AREA MAXIMUM VENTILATOR DIMENSIONS ALL PLUMBING AND ELECTRICAL DISCONNECTED CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. 12-'0" LONG x 4'-6" WIDE x 29" HIGH ESTIMATED TOTAL FOR SHIPMENT. RECONNECTED IN FIELD BY
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL HANGING WEIGHT: 1,050 LBS. PLUMBING AND ELECTRICAL CONTRACTORS.

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 1
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
GENERAL NOTES
ELECTRICAL NOTES:
EXHAUST AIR REQUIREMENTS:
1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED 1. EXHAUST C.F.M. BASED ON 400 C.F.M. PER LINEAR FOOT.
AND WIRED TO J-BOX D BY CADDY. RECONNECTED ON JOBSITE 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
BY ELECTRICAL CONTRACTOR. COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
OPERATION AT MEAN SEA LEVEL.
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE 3. DUCT SIZE BASED ON 1,500 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION BY ELECTRICAL CONTRACTOR.
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM
EXHAUST FAN REQUIREMENTS:
COOKING EQUIPMENT" 1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED

NATIONAL SANITATION FOUNDATION


Z BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT"
WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER TOTAL EXHAUST : 3,066 C.F.M.
CONTROL # 3177269 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
2'-9" DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS 10" X 29" EXHAUST DUCT SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.
1
3,066 C.F.M. @ 1.60" S.P.
THE BOCA NATIONAL MECHANICAL CODE 5'-6" CL 1
2. MAKE-UP AIR MUST BE TEMPERED-HEATED OR COOLED-CONSISTENT
WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND
CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT APPLICABLE CODES.
STANDARD MECHANICAL CODE (SBCCI) D
INSTALLATION:
SECTION 504 - COMMERCIAL HOODS 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES.
UNIFORM BUILDING CODE (ICBO) CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE
INTERNATIONAL MECHANICAL CODE (IMC) AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION.
SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS
SECTION 507 - COMMERCIAL KITCHEN HOODS RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE
EXCLUDES CODE #507.2.1.1, CONSULT FACTORY (4) HANGER
FOR COMPLIANCE OPTIONS. CL BRACKETS 5'-6"
2.
CONSTRUCTION (WALL, CEILINGS, ETC.).
VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO
(SEE DETAIL A-A) HANDLE ENVIRONMENTAL AIR.
3'-10" Z 3. ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE-OFF COLLAR TO
STN./STL. ENCLOSURE PANEL BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH
7'-8"
FURNISHED BY CADDY JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG,
PLAN AND INSTALLED BY K.E.C.
4.
GREASE AND WATER TIGHT.
MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS.
SCALE: 1/2"=1'-0"
CONSTRUCTION:
1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH
CADDY SPECIFICATIONS.
3'-6" 2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
2'-4" 10" 2'-4"

K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING FIRE PROTECTION:
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT A-A 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE 4" INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
(4) RECESSED PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
1 FLUORESCENT ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO 2'-0"
(36") LIGHT FIXTURES ELECTRICAL REQUIREMENTS:
SERVICE COMPONENTS AND UTILITIES
1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.

12'-0"
AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F, STN./STL. ENCLOSURE PANEL HIGH VELOCITY
FIN. CLG.
BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR FURNISHED BY CADDY GREASE EXTRACTOR
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD HEIGHT
AND INSTALLED BY K.E.C. [X] VERIFY REMOVABLE
STN./STL.
1'-6"
GREASE CUP

STN.\STL.
GREASE CUPS 8'-6"
TOP OF
VENTILATOR

1/2" DIA. BY 6'-0" LONG PLATED


2'-7" 2'-6"
STEEL HANGER RODS AND BOLTS 6'-6"
FURNISHED BY K.E.C. A.F.F.
1'-4"* 1'-4"*

9/16" HOLE FOR 1/2" 12 GA. STN. STL.


THREADED ROD HANGER BRACKETS
FULLY WELDED TO VENTILATOR JADE
(RODS AND HARDWARE
BY CADDY JMRH-60G
BY K.E.C.)
JADE JADE JADE GRIDDLE
JTPR-12 JMRH-60G JTPR-12 ITEM #148
SPREADER GRIDDLE SPREADER
ITEM #149 ITEM #148 ITEM #149

CM

ELEVATION SECTION Z-Z R


R

SCALE: 1/2"=1'-0" SCALE: 3/4"=1'-0" Intertek

HANGER BRACKET DETAIL A-A REVISIONS


SCALE: 1/4"=1" ROUGH-IN SCHEDULE REV DATE BY REMARKS

SYM QTY DESCRIPTION A 4-18-12 DRA ADDED MUA AND REMOVED A 12" RANGE
EQUIPMENT SCHEDULE
K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA REMOVED CEILING SUPPLY PLENUMS

* - MINIMUM OVERHANG FROM EDGE OF COOKING D 1 120V, 60HZ, 1PH, 0.32 K.W. CONNECTED LOAD
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER C 11-2-12 DRA REVISED PER RECEIVED P.O.

LINE-UP PRIOR TO FABRICATION OF VENTILATORS, EQUIPMENT TO END OF HOOD MUST BE 6" D 1-7-13 DRA DECREASED HOOD, CFM, AND DUCT SIZE;
REVISED TO FLUORESCENT LIGHTS SHBC-C-II-92-ND-66
AND TO NOTIFY CADDY OF ANY CHANGES. E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.

ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH


STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
CADDY NO. 10710 -2 ITEM NO. 151
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. INSTALLATION INFORMATION LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES CUST: SINGER EQUIPMENT
ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR VENTILATOR TO BE SHIPPED IN (1) UNIT.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR INTO KITCHEN AREA MAXIMUM VENTILATOR DIMENSIONS ALL PLUMBING AND ELECTRICAL DISCONNECTED CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. 7'-8" LONG x 5'-6" WIDE x 29" HIGH ESTIMATED TOTAL FOR SHIPMENT. RECONNECTED IN FIELD BY
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL HANGING WEIGHT: 690 LBS. PLUMBING AND ELECTRICAL CONTRACTORS.

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 2
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
2 2

1
1 1
1

360° 360° 360° 450° 450° 360°

1 1 3 3 1 1 1 1
PITCO PITCO
2-SSH55RSSTCS/FD PCF-14 JADE JADE A
FRYER DUMP STATION JMRH-48B JMRH-2A
ITEM #159 ITEM #160 A
CHARBROILER RANGE
ITEM #161 ITEM #163 B
JADE
JMRH-12G
GRIDDLE
ITEM #164
JADE JADE JADE
JTPR-12 JMRH-60G JTPR-12 JADE
SPREADER GRIDDLE SPREADER JLRH-04S-T-72
ITEM #149 ITEM #148 ITEM #149 REFRIG. BASE
ELECTRIC
ITEM #162 B SNAP-ACTION
SWITCH
B BY CADDY
ELEVATION ITEM #151 ELEVATION ITEM #165 C
3.0 GALLON 3.0 GALLON
SCALE: 1/2"=1'-0" SCALE: 1/2"=1'-0" TANK TANK

REMOTE PULL
STATION

TANK/ENCLOSURE
ASSEMBLIES

ANSUL ROUGH-IN
ANSUL NOZZLE DATA DOUBLE TANK
SYM DESCRIPTION NITROGEN CARTRIDGE

MIN.-MAX.
3/8" SCH 40 BLACK IRON PIPE. ALL EXPOSED FLOW POINTS
A SYM QTY DESCRIPTION HEIGHT
PIPING TO BE CHROME PLATED OR STN./STL. EACH
ABOVE HAZARD
B 1/2" EMT CONDUIT 30"-40" (RANGE)
MICRO SWITCH FOR ELECTRIC 1 10 ANSUL #1N 1 35"-40" (GRIDDLE)
C SHUT-DOWN AND/OR ALARM BY CADDY 15"-40" (CHARBROILER)
WIRING BY E.C. 2 2 ANSUL #2W 2
2" MECHANICAL TYPE GAS VALVE
FURNISHED BY CADDY AND INSTALLED 3 2 ANSUL #3N 3 21"-34"
PLENUM PROTECTION D
NOZZLE BY P.C. ([ ] VERIFY SIZE).

DUCT PROTECTION
NOZZLE

DETECTORS
INSTALLATION INFORMATION
DETECTION LINE ANSUL R-102 3/3 SYSTEM ALLOW SUFFICIENT AREA TO MOUNT ANSUL ON
CLOSEST STRUCTURAL WALL TO VENTILATOR
MAXIMUM ANSUL ENCLOSURE DIMENSIONS
FOR VENTILATOR ITEMS #151 & 165 26" LONG x 7 1/2" DEEP x 23 1/2" HIGH
ESTIMATED TOTAL HANGING WEIGHT: 100 LBS.
ENCLOSURE MOUNTING HEIGHT 7'-0"

APPLIANCE PROTECTION POWER TO


NOZZLE COOKING
S EQUIPMENT
AGENT LINE

TYPICAL WET CHEMICAL FIRE PROTECTION SYSTEM INTERLOCK POWER TO


COOKING
EQUIPMENT R

SHUNT TRIP CIRCUIT BREAKER UNDERWRITERS LABORATORIES, INC


IN ELECTRICAL PANEL BY E.C. OR TESTED UNDER STANDARD U.L. 300 "FIRE TESTING OF FIRE
UDS BY UDS MANUFACTURER EXTINGUISHING SYSTEMS FOR PROTECTION OF RESTAURANT R
(CONDUIT AND BOX
TYPICAL ANSUL R102 SYSTEM LAYOUT BY E.C.)
COOKING AREAS ".
WITH REMOTE MOUNTED AUTOMAN CABLE BY FIRE
SYSTEM CONTRACTOR
MANUAL PULL
REMOTE MECHANICAL
CABLE ASSEMBLY MECHANICAL GAS VALVE REVISIONS
MANUAL PULL FIRE
(NORMALLY CLOSED)
PROTECTION REV DATE BY REMARKS
STATION HVAC/MAKE-UP AIR AND GAS/ ELECTRICAL EQUIPMENT PANEL
SYSTEM CONTROL AUTOMAN
SHUTDOWN WHEN USING AN MECHANICAL GAS VALVE CABLE BY FIRE SYSTEM CONTRACTOR A 4-18-12 DRA REVISED ANSUL DROPS PER CHANGED
WITH AGENT TANK ENCLOSED CONDUIT BY E.C. EQUIPMENT
1. CONNECT THE INCOMING LIVE LEAD (A) TO THE COMMON
TERMINAL SWITCH.
(B)
B 5-31-12 DRA NO CHANGES
EQUIPMENT SCHEDULE
120v (A) BY E.C. HVAC UNIT
2. CONNECT THE FIRE-STAT RELAY (B).
CONTROL PANEL C 11-2-12 DRA REVISED PER RECEIVED P.O.
(C)
3. CONNECT THE SHUNT TRIP RELAY TO THE D 1-7-13 DRA DECREASED DUCT SIZE OF ITEM # 151
MICRO-SWITCH (C). NEUTRAL BY E.C. ANSUL R-102 3/3
MICRO-SWITCH E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
OPERATION SPDT
WHEN DETECTION LINES OR HAND "PULL" STATION ENERGIZE
ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH
STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
THE FIRE PROTECTION SYSTEM, THE MICRO-SWITCH
NC
CADDY NO. 10710 -2 ITEM NO. 151A
REPOSITIONS TO:
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
1. ACTIVATE SHUNT TRIP CIRCUIT BREAKER, SHUTTING TO NC OR NO
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL OFF FUEL AND POWER TO THE EQUIPMENT SWITCH AS REQ'D
JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. NO
2. TRANSFER POWER TO THE FIRE-STAT RELAY TO BY ALARM ALARM IF LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET OPEN CONTACT TO SHUT DOWN HVAC UNIT (SUPPLY AIR). REQ'D FIRE-STAT
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES CUST: SINGER EQUIPMENT
RELAY BY
3. DETECTION LINE WILL CLOSE MECHANICAL GAS VALVE.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR MICRO-SWITCH HVAC CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION.
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
WIRING BETWEEN COMPONENTS BY E.C. 2-21-12 AS NOTED SHT 3
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. (LOCATED IN PANEL) DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
ELECTRICAL NOTES:
GENERAL NOTES
1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED EXHAUST AIR REQUIREMENTS:
Z AND WIRED TO J-BOX D BY CADDY. RECONNECTED ON JOBSITE 1. EXHAUST C.F.M. BASED ON 400 C.F.M. PER LINEAR FOOT.
BY ELECTRICAL CONTRACTOR. 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE OPERATION AT MEAN SEA LEVEL.
BY ELECTRICAL CONTRACTOR. 3. DUCT SIZE BASED ON 1,500 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM
EXHAUST FAN REQUIREMENTS:
COOKING EQUIPMENT" 1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
NATIONAL SANITATION FOUNDATION (6) HANGER FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
BRACKETS 2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT" (SEE DETAIL A-A) D TOTAL EXHAUST : 3,000 C.F.M. WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER 1
CONTROL # 3177269 10" X 29" EXHAUST DUCT 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
1 DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
3,000 C.F.M. @ 1.60" S.P.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.
2. MAKE-UP AIR MUST BE TEMPERED-HEATED OR COOLED-CONSISTENT
THE BOCA NATIONAL MECHANICAL CODE WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND
CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT APPLICABLE CODES.
STANDARD MECHANICAL CODE (SBCCI)
INSTALLATION:
SECTION 504 - COMMERCIAL HOODS 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES.
STN./STL. ENCLOSURE PANEL
UNIFORM BUILDING CODE (ICBO) CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE
INTERNATIONAL MECHANICAL CODE (IMC)
CL Z FURNISHED BY CADDY
AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION.
AND INSTALLED BY K.E.C. SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS
SECTION 507 - COMMERCIAL KITCHEN HOODS 3'-9" RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE
EXCLUDES CODE #507.2.1.1, CONSULT FACTORY CONSTRUCTION (WALL, CEILINGS, ETC.).
FOR COMPLIANCE OPTIONS. 7'-6"
2. VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO
PLAN 3.
HANDLE ENVIRONMENTAL AIR.
ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE-OFF COLLAR TO
SCALE: 1/2"=1'-0" BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH
7'-6" JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG,
GREASE AND WATER TIGHT.
4. MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS.
3'-4" 10" 3'-4" CONSTRUCTION:
4'-6" 1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH
CADDY SPECIFICATIONS.
(2) RECESSED 2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
FLUORESCENT
(48") LIGHT FIXTURES FIRE PROTECTION:
K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION A-A (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE 4" INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO 2'-0"
SERVICE COMPONENTS AND UTILITIES ELECTRICAL REQUIREMENTS:
1
1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.
13'-0"
FIN. CLG.
AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F, HEIGHT
BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR
STN./STL. ENCLOSURE PANEL [ x] VERIFY
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD FURNISHED BY CADDY
HIGH VELOCITY
AND INSTALLED BY K.E.C.
GREASE EXTRACTOR
2'-6" REMOVABLE
STN./STL.
GREASE CUP
STN.\STL.
GREASE CUPS 8'-6"
TOP OF JADE
VENTILATOR JMRHE-2-2
RANGE
1/2" DIA. BY 6'-0" LONG PLATED 1'-3" 1'-0" 1'-0" ITEM #189
STEEL HANGER RODS AND BOLTS 2'-3"
6'-6"
FURNISHED BY K.E.C.
JADE A.F.F.
1'-6"* 1'-6"*
JMRHE-2-2
RANGE
JADE ITEM #189
9/16" HOLE FOR 1/2" 12 GA. STN. STL.
JMRH-18B JADE
THREADED ROD HANGER BRACKETS
CHARBROILER JMRH-12G
(RODS AND HARDWARE FULLY WELDED TO VENTILATOR JADE
ITEM #190 GRIDDLE
BY K.E.C.) BY CADDY ITEM #188 JRLH-02S-T-48
REFRIGERATED
JADE BASE
JRLH-02S-T-48 ITEM #191
REFRIG. BASE
ITEM #191
CM

ELEVATION SECTION Z-Z R


R

SCALE: 1/2"=1'-0" SCALE: 3/4"=1'-0" Intertek

HANGER BRACKET DETAIL A-A REVISIONS


SCALE: 1/4"=1" ROUGH-IN SCHEDULE REV DATE BY REMARKS

SYM QTY DESCRIPTION A 4-18-12 DRA ADDED MUA, INCREASED HOOD 6" AND INCREASED 12"
CHARBROILER TO A 18"
EQUIPMENT SCHEDULE
K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA REMOVED CEILING SUPPLY PLENUMS

* - MINIMUM OVERHANG FROM EDGE OF COOKING D 1 120V, 60HZ, 1PH, 0.16 K.W. CONNECTED LOAD C
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER 11-2-12 DRA REVISED PER RECEIVED P.O.

EQUIPMENT TO END OF HOOD MUST BE 6" D


LINE-UP PRIOR TO FABRICATION OF VENTILATORS, 1-7-13 DRA REVISED TO FLUORESCENT LIGHTS

SHBC-C-II-84-ND-84
E 01/14/13 DRA REVISED FOR FABRICATION PER "APPROVED
AND TO NOTIFY CADDY OF ANY CHANGES. AS NOTED" DRAWING RECEIVED ON 01/14/13.

ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH


STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
CADDY NO. 10710 -7 ITEM NO. 196
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. INSTALLATION INFORMATION LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES
CUST: SINGER EQUIPMENT
ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR VENTILATOR TO BE SHIPPED IN (1) UNIT.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR INTO KITCHEN AREA MAXIMUM VENTILATOR DIMENSIONS ALL PLUMBING AND ELECTRICAL DISCONNECTED CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. 7-'6" LONG x 7'-6" WIDE x 29" HIGH ESTIMATED TOTAL FOR SHIPMENT. RECONNECTED IN FIELD BY
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL HANGING WEIGHT: 675 LBS. PLUMBING AND ELECTRICAL CONTRACTORS.

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 4
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
2

1
1

450°

1 1 1 1

JADE
A
JMRHE-2-2
B RANGE
JADE ITEM #189
JMRH-18B JADE
CHARBROILER JMRH-12G
ITEM #190 GRIDDLE
ITEM #188
JADE
JRLH-02S-T-48
ELECTRIC REFRIG. BASE
SNAP-ACTION B
ITEM #191
SWITCH
BY CADDY B
C
3.0 GALLON
TANK
ELEVATION
SCALE: 1/2"=1'-0"
REMOTE PULL
STATION

TANK/ENCLOSURE
ASSEMBLY

SINGLE TANK
NITROGEN CARTRIDGE

ANSUL ROUGH-IN
SYM DESCRIPTION ANSUL NOZZLE DATA
3/8" SCH 40 BLACK IRON PIPE. ALL EXPOSED MIN.-MAX.
A FLOW POINTS
PIPING TO BE CHROME PLATED OR STN./STL. SYM QTY DESCRIPTION HEIGHT
EACH
B 1/2" EMT CONDUIT ABOVE HAZARD
30"-40" (RANGE)
MICRO SWITCH FOR ELECTRIC
1 6 ANSUL #1N 1 35"-40" (GRIDDLE)
C SHUT-DOWN AND/OR ALARM BY CADDY
WIRING BY E.C. 15"-40" (CHARBROILER)

2" MECHANICAL TYPE GAS VALVE 2 1 ANSUL #2W 2


PLENUM PROTECTION D FURNISHED BY CADDY AND INSTALLED
NOZZLE BY P.C. ([ ] VERIFY SIZE).

DUCT PROTECTION
NOZZLE

DETECTORS
INSTALLATION INFORMATION
DETECTION LINE ANSUL R-102 3 SYSTEM ALLOW SUFFICIENT AREA TO MOUNT ANSUL ON
CLOSEST STRUCTURAL WALL TO VENTILATOR
MAXIMUM ANSUL ENCLOSURE DIMENSIONS
FOR VENTILATOR ITEMS #196 16 1/2" LONG x 7 1/2" DEEP x 23 1/2" HIGH
ESTIMATED TOTAL HANGING WEIGHT: 75 LBS.
ENCLOSURE MOUNTING HEIGHT 7'-0"

APPLIANCE PROTECTION POWER TO


NOZZLE COOKING
S EQUIPMENT
AGENT LINE

TYPICAL WET CHEMICAL FIRE PROTECTION SYSTEM INTERLOCK POWER TO


COOKING
EQUIPMENT R

SHUNT TRIP CIRCUIT BREAKER UNDERWRITERS LABORATORIES, INC


IN ELECTRICAL PANEL BY E.C. OR TESTED UNDER STANDARD U.L. 300 "FIRE TESTING OF FIRE
UDS BY UDS MANUFACTURER EXTINGUISHING SYSTEMS FOR PROTECTION OF RESTAURANT R
(CONDUIT AND BOX
TYPICAL ANSUL R102 SYSTEM LAYOUT BY E.C.)
COOKING AREAS ".
WITH REMOTE MOUNTED AUTOMAN CABLE BY FIRE
SYSTEM CONTRACTOR
MANUAL PULL
REMOTE MECHANICAL
CABLE ASSEMBLY MECHANICAL GAS VALVE REVISIONS
MANUAL PULL FIRE
(NORMALLY CLOSED)
PROTECTION REV DATE BY REMARKS
STATION HVAC/MAKE-UP AIR AND GAS/ ELECTRICAL EQUIPMENT PANEL
SYSTEM CONTROL AUTOMAN
SHUTDOWN WHEN USING AN MECHANICAL GAS VALVE CABLE BY FIRE SYSTEM CONTRACTOR
WITH AGENT TANK ENCLOSED CONDUIT BY E.C. A 4-18-12 DRA ADDED MUA, INCREASED HOOD 6" AND INCREASED 12"
1. CONNECT THE INCOMING LIVE LEAD (A) TO THE COMMON
TERMINAL SWITCH.
(B)
B 5-31-12 DRA
CHARBROILER TO A 18"
NO CHANGES
EQUIPMENT SCHEDULE
120v (A) BY E.C. HVAC UNIT
2. CONNECT THE FIRE-STAT RELAY (B).
(C) CONTROL PANEL C 11-2-12 DRA REVISED PER RECEIVED P.O.

3. CONNECT THE SHUNT TRIP RELAY TO THE D 1-7-13 DRA NO CHANGES


MICRO-SWITCH (C). NEUTRAL BY E.C.
E 01/14/13 DRA REVISED FOR FABRICATION PER "APPROVED
ANSUL R-102 3
MICRO-SWITCH AS NOTED" DRAWING RECEIVED ON 01/14/13.
OPERATION SPDT
WHEN DETECTION LINES OR HAND "PULL" STATION ENERGIZE
ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH
STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
THE FIRE PROTECTION SYSTEM, THE MICRO-SWITCH
NC
CADDY NO. 10710 ITEM NO. 196A
REPOSITIONS TO:
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
1. ACTIVATE SHUNT TRIP CIRCUIT BREAKER, SHUTTING TO NC OR NO
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL OFF FUEL AND POWER TO THE EQUIPMENT SWITCH AS REQ'D
JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. NO
2. TRANSFER POWER TO THE FIRE-STAT RELAY TO BY ALARM ALARM IF LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET OPEN CONTACT TO SHUT DOWN HVAC UNIT (SUPPLY AIR). REQ'D FIRE-STAT
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES CUST: SINGER EQUIPMENT
RELAY BY
3. DETECTION LINE WILL CLOSE MECHANICAL GAS VALVE.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR MICRO-SWITCH HVAC CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION.
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
WIRING BETWEEN COMPONENTS BY E.C. 2-21-12 AS NOTED SHT 5
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. (LOCATED IN PANEL) DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
GENERAL NOTES
EXHAUST AIR REQUIREMENTS:
FLUE DUCT BY K.E.C. 1. EXHAUST C.F.M. BASED ON 200 C.F.M. PER LINEAR FOOT.
6" FLUE 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
OR OTHER PRESCRIBED
COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
CONTRACTOR.
OPERATION AT MEAN SEA LEVEL.
3. DUCT SIZE BASED ON 1,800 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM
1 1/2" X 1 1/2" STN./STL. EXHAUST FAN REQUIREMENTS:
COOKING EQUIPMENT" Z MOUNTING ANGLE BY
CADDY. SEE DETAIL
1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
NATIONAL SANITATION FOUNDATION FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT"
WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK 1
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER 2'-6"
CONTROL # 3177269 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.

THE BOCA NATIONAL MECHANICAL CODE


CL 2. MAKE-UP AIR MUST BE TEMPERED-HEATED OR COOLED-CONSISTENT
WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND
CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT 2'-6" APPLICABLE CODES.
STANDARD MECHANICAL CODE (SBCCI) 5'-0"
INSTALLATION:
SECTION 504 - COMMERCIAL HOODS
UNIFORM BUILDING CODE (ICBO)
PLAN 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES.
CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE
SCALE: 1/2"=1'-0" AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION.
INTERNATIONAL MECHANICAL CODE (IMC)
SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS
SECTION 507 - COMMERCIAL KITCHEN HOODS
EXCLUDES CODE #507.2.1.1, CONSULT FACTORY
Z RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE
CONSTRUCTION (WALL, CEILINGS, ETC.).
FOR COMPLIANCE OPTIONS. 2. VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO
HANDLE ENVIRONMENTAL AIR.
3. ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE-OFF COLLAR TO
BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH
TOTAL EXHAUST : 1,100 C.F.M. JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG,
GREASE AND WATER TIGHT.
4. MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS.

2'-6" 2" CONSTRUCTION:


10" X 11" EXHAUST DUCT 1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH
1 10" CADDY SPECIFICATIONS.
1,100 C.F.M. @ 1.60" S.P.
2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
HIGH VELOCITY FIRE PROTECTION:
K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING GREASE EXTRACTOR
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 4" 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
REMOVABLE
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR 1'-0" BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
STN./STL.
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. GREASE CUP IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
1 2'-0"
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
1'-0" PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO
SERVICE COMPONENTS AND UTILITIES ELECTRICAL REQUIREMENTS:
6" FLUE DUCT
CONNECTION 1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.
BY CADDY

AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F,


BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR STN.\STL. STN./STL. MOUNTING
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD GREASE CUPS ANGLE (SEE DETAIL
8'-2" A-A)
FIN. CLG.
HEIGHT
[X] VERIFY

6'-2"
A.F.F.
[X] VERIFY BAKERS
PRIDE
FC-516/DS-805
PIZZA OVEN
ITEM #174

BAKERS PRIDE
FC-516/DS-805
ATTACHING PIZZA OVEN
HARDWARE ITEM #174
BY K.E.C.

STN./STL. ELEVATION SECTION Z-Z


MOUNTING ANGLE SCALE: 1/2"=1'-0" SCALE: 3/4"=1'-0"
FOR SECURING
CM

VENTILATOR TO
KITCHEN EQUIPMENT
R
R

Intertek

REVISIONS
REV DATE BY REMARKS

MOUNTING ANGLE DETAIL A-A A 4-18-12 DRA REVISED HOOD TO 5'-0" LONG AND ADDED
SCALE: 3/4"=1'-0" K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA
FLUE CONNECTION
NO CHANGES
EQUIPMENT SCHEDULE
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER C 11-2-12 DRA REVISED PER RECEIVED P.O.

D 1-7-13 DRA
LINE-UP PRIOR TO FABRICATION OF VENTILATORS, ADDED DIMENSION AND REVISED NOTE TO
CLARIFY 2" X 6" DIA. DUCT CONNECTION. SHBC-BK-I-60-ND-30
AND TO NOTIFY CADDY OF ANY CHANGES. E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.

ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH


STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
CADDY NO. 10710 -5 ITEM NO. 174.1
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. INSTALLATION INFORMATION LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES CUST: SINGER EQUIPMENT
ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR VENTILATOR TO BE SHIPPED IN (1) UNIT.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR INTO KITCHEN AREA MAXIMUM VENTILATOR DIMENSIONS ALL PLUMBING AND ELECTRICAL DISCONNECTED CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. 5'-0" LONG x 2'-8 1/2" WIDE x 28" HIGH ESTIMATED TOTAL FOR SHIPMENT. RECONNECTED IN FIELD BY
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL HANGING WEIGHT: 325 LBS. PLUMBING AND ELECTRICAL CONTRACTORS.

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 6
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
2

360°

A
B

ELECTRIC BAKERS PRIDE


SNAP-ACTION B FC-516/DS-805
SWITCH PIZZA OVEN
BY CADDY ITEM #174
B
C
3.0 GALLON
TANK
ELEVATION
SCALE: 1/2"=1'-0"
REMOTE PULL
STATION

TANK/ENCLOSURE
ASSEMBLY

SINGLE TANK
NITROGEN CARTRIDGE

ANSUL ROUGH-IN
SYM DESCRIPTION ANSUL NOZZLE DATA
3/8" SCH 40 BLACK IRON PIPE. ALL EXPOSED MIN.-MAX.
A FLOW POINTS
PIPING TO BE CHROME PLATED OR STN./STL. SYM QTY DESCRIPTION HEIGHT
EACH
B 1/2" EMT CONDUIT ABOVE HAZARD
1 1 ANSUL #1N 1
MICRO SWITCH FOR ELECTRIC
C SHUT-DOWN AND/OR ALARM BY CADDY 2 1 ANSUL #2W 2
WIRING BY E.C.
2" MECHANICAL TYPE GAS VALVE
PLENUM PROTECTION D FURNISHED BY CADDY AND INSTALLED
NOZZLE BY P.C. ([ ] VERIFY SIZE).

DUCT PROTECTION
NOZZLE

DETECTORS
INSTALLATION INFORMATION
DETECTION LINE ANSUL R-102 3 SYSTEM ALLOW SUFFICIENT AREA TO MOUNT ANSUL ON
CLOSEST STRUCTURAL WALL TO VENTILATOR
MAXIMUM ANSUL ENCLOSURE DIMENSIONS
FOR VENTILATOR ITEMS #174.1 16 1/2" LONG x 7 1/2" DEEP x 23 1/2" HIGH
ESTIMATED TOTAL HANGING WEIGHT: 75 LBS.
ENCLOSURE MOUNTING HEIGHT 7'-0"

APPLIANCE PROTECTION POWER TO


NOZZLE COOKING
S EQUIPMENT
AGENT LINE

TYPICAL WET CHEMICAL FIRE PROTECTION SYSTEM INTERLOCK POWER TO


COOKING
EQUIPMENT R

SHUNT TRIP CIRCUIT BREAKER UNDERWRITERS LABORATORIES, INC


IN ELECTRICAL PANEL BY E.C. OR TESTED UNDER STANDARD U.L. 300 "FIRE TESTING OF FIRE
UDS BY UDS MANUFACTURER EXTINGUISHING SYSTEMS FOR PROTECTION OF RESTAURANT R
(CONDUIT AND BOX
TYPICAL ANSUL R102 SYSTEM LAYOUT BY E.C.)
COOKING AREAS ".
WITH REMOTE MOUNTED AUTOMAN CABLE BY FIRE
SYSTEM CONTRACTOR
MANUAL PULL
REMOTE MECHANICAL
CABLE ASSEMBLY MECHANICAL GAS VALVE REVISIONS
MANUAL PULL FIRE
(NORMALLY CLOSED)
PROTECTION REV DATE BY REMARKS
STATION HVAC/MAKE-UP AIR AND GAS/ ELECTRICAL EQUIPMENT PANEL
SYSTEM CONTROL AUTOMAN
SHUTDOWN WHEN USING AN MECHANICAL GAS VALVE CABLE BY FIRE SYSTEM CONTRACTOR
CONDUIT BY E.C. A 4-18-12 DRA REVISED HOOD TO 5'-0" LONG
WITH AGENT TANK ENCLOSED 1. CONNECT THE INCOMING LIVE LEAD (A) TO THE COMMON
TERMINAL SWITCH.
(B)
B 5-31-12 DRA NO CHANGES
EQUIPMENT SCHEDULE
120v (A) BY E.C. HVAC UNIT
2. CONNECT THE FIRE-STAT RELAY (B).
CONTROL PANEL C 11-2-12 DRA REVISED PER RECEIVED P.O.
(C)
3. CONNECT THE SHUNT TRIP RELAY TO THE D 1-7-13 DRA NO CHANGES
MICRO-SWITCH (C). NEUTRAL BY E.C. ANSUL R-102 3
MICRO-SWITCH E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
OPERATION SPDT
WHEN DETECTION LINES OR HAND "PULL" STATION ENERGIZE
ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH
STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
THE FIRE PROTECTION SYSTEM, THE MICRO-SWITCH
NC
CADDY NO. 10710 -5 ITEM NO. 174.1A
REPOSITIONS TO:
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
1. ACTIVATE SHUNT TRIP CIRCUIT BREAKER, SHUTTING TO NC OR NO
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL OFF FUEL AND POWER TO THE EQUIPMENT SWITCH AS REQ'D
JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. NO
2. TRANSFER POWER TO THE FIRE-STAT RELAY TO BY ALARM ALARM IF LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET OPEN CONTACT TO SHUT DOWN HVAC UNIT (SUPPLY AIR). REQ'D FIRE-STAT
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES CUST: SINGER EQUIPMENT
RELAY BY
3. DETECTION LINE WILL CLOSE MECHANICAL GAS VALVE.
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR MICRO-SWITCH HVAC CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION.
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
WIRING BETWEEN COMPONENTS BY E.C. 2-21-12 AS NOTED SHT 7
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. (LOCATED IN PANEL) DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
20'-6"
[X] VERIFY WALL OPENING
Z 1/2" Ø DRAIN

TOTAL EXHAUST : 4,266 C.F.M.

TOTAL SUPPLY : 3,412 C.F.M.


C D

1 1
5'-0"

14" X 14" EXHAUST DUCTS 12" X 15" SUPPLY DUCTS


1 2
CL 2,133 C.F.M. EACH @ 1.60" S.P. 853 C.F.M. EACH @ 0.20" S.P.

1'-6"

(20) HANGER
BRACKETS
(SEE DETAIL A-A)
2'-6"
[X] VERIFY

1'-6" 2 2 2 2

2'-6" ELECTRICAL NOTES:


CL CL 1'-6"
[X] VERIFY
5'-0"

2'-6 11/16"
5'-1 3/8" 10'-2 3/4" Z 1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED
(TYP.) (TYP.) 3" 11" 1'-2" 2'-11" AND WIRED TO J-BOX D BY CADDY. DISCONNECTED FOR SHIPPING AT
20'-5 1/2" 1'-0" J-BOX C . RECONNECTED ON JOBSITE BY ELECTRICAL CONTRACTOR.

2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE BY
PLAN ELECTRICAL CONTRACTOR.
SCALE: 1/2"=1'-0" 4"
2 1 2 2 1 2
A-A
1'-0"
1/2" DIA. BY 6'-0" LONG PLATED
4"
STEEL HANGER RODS AND BOLTS
FURNISHED BY K.E.C.
20'-6"
SLIDING
10'-3" 10'-2 3/4" DAMPER
2'-0" 9/16" HOLE FOR 1/2" 12 GA. STN. STL.
(4) RECESSED FULL PERIMETER
4'-6 3/8" 1'-2" 4'-6 3/8" 4'-6 3/8" 1'-2" 4'-6 3/8" THREADED ROD HANGER BRACKETS
FLUORESCENT GUTTER
(36") LIGHT FIXTURES (RODS AND HARDWARE FULLY WELDED TO VENTILATOR
BY K.E.C.) BY CADDY

1/2" Ø DRAIN
(INDIRECT WASTE)

8'-6"
FIN. CLG.
HEIGHT
1/2" Ø DRAIN
[X] VERIFY HANGER BRACKET DETAIL A-A
6'-6" SCALE: 1/4"=1"
A.F.F.

THE CADDY VENTILATOR TESTING,


LISTING AND APPROVAL REFERENCES:
NATIONAL SANITATION FOUNDATION
Standard #2 - "Food Service Equipment"

ELEVATION SECTION Z-Z


SCALE : 1/2"=1'-0" SCALE: 3/4"=1'-0"
R

NOTES REVISIONS
REV DATE BY REMARKS
INSTALLATION INFORMATION
1. AIR SYSTEMS SHALL NOT BE LIABLE FOR IMPROPER FUNCTION DUE TO CHANGE IN
ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR TO BE SHIPPED IN (2) UNITS. STATIC PRESSURE OR AIR VOLUMES SPECIFIED. A 4-18-12 DRA ADDED MUA
VENTILATOR INTO KITCHEN AREA ALL PLUMBING AND ELECTRICAL DISCONNECT- 2. ALL DIMENSIONS TO BE VERIFIED IN FIELD BY OTHERS BEFORE VENTILATORS B 5-31-12 DRA NO CHANGES
EQUIPMENT SCHEDULE
MAXIMUM VENTILATOR DIMENSIONS TED FOR SHIPMENT. RECONNECTED IN FIELD ARE RELEASED FOR MANUFACTURE.
10'-8" LONG x 5'-0" WIDE x 28 1/2" HIGH C 11-2-12 DRA REVISED PER RECEIVED P.O.
BY PLUMBING AND ELECTRICAL CONTRACTORS. 3. INDICATE ALL BEAMS, COLUMNS, ETC. WHICH MAY CONFLICT WITH VENTILATOR
ESTIMATED HANGING WEIGHT: 1,173 LBS. OR EXHAUST OUTLET COLLAR(S) (INDICATE SIZE, LOCATION, AND HEIGHT ABOVE D 1-7-13 DRA REVISED TO FLUORESCENT LIGHTS AND
FINISHED FLOOR.) UPDATED EQUIPMENT UNDER HOOD CH-C-W-122.75-SD-60
4. INSTALLING CONTRACTOR SHALL CHECK ALL BUILDING ACCESS, ENTRANCE AND FIELD E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
CONDITIONS TO ENSURE SUFFICIENT CLEARANCE TO ALLOW VENTILATOR SECTION(S)
ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH
ROUGH-IN SCHEDULE (SIZE(S) AS DIMENSIONED ON THIS DRAWING) TO BE BROUGHT INTO BUILDING AND
STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
INSTALLED ACCORDING TO AIR SYSTEMS RECOMMENDATIONS. CADDY NO. 10710 -A ITEM NO. B1
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES 5. ALL EXHAUST DUCT COLLARS ARE INSIDE DIMENSIONS.
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL SYM QTY DESCRIPTION 6. ALL DUCTWORK BEYOND THE VENTILATOR OR EXHAUST DUCT COLLAR(S) TO BE PROVIDED
AND INSTALLED BY OTHERS IN ACCORDANCE WITH JURISDICTIONAL CODES, AND MUST
JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET D 1 120V, 60HZ, 1PH, 0.32 K.W. CONNECTED LOAD BE MECHANICALLY STRONG, AND GREASE AND WATER TIGHT.
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES 7. VENTILATOR(S) SHALL BE N.S.F. APPROVED AND SHALL BEAR N.S.F. LABELS VISIBLY CUST: SINGER EQUIPMENT
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR AFFIXED TO EXTERIOR. CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. 8. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 8
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
Z
1/2" DIA. BY 6'-0" LONG PLATED
STEEL HANGER RODS AND BOLTS
FURNISHED BY K.E.C.
1'-6" 1 1 1 1 1 1 1 1

1'-6" MIN. 9/16" HOLE FOR 1/2" 12 GA. STN. STL.


4'-0" MAX. THREADED ROD HANGER BRACKETS
(RODS AND HARDWARE FULLY WELDED TO VENTILATOR
BY K.E.C.) BY CADDY

REFERENCE FOR HOOD ITEM # 85 REFERENCE FOR HOOD ITEM # 84

HANGER BRACKET DETAIL A-A


SCALE: 1/4"=1"

REFERENCE FOR HOOD ITEM # 91 REFERENCE FOR HOOD ITEM # 95

1'-6" MIN. 1'-6" MIN.


1'-6" 9'-6" 1'-6"
3" 4'-0" MAX. 4'-0" MAX. 3"
1'-0" 1'-0"

A-A
1'-6" MIN.
4'-0" MAX. 4" 4"

1'-0" 1'-0"
1'-6" 2 2 2 2 2 2 2 2

CL CL CL CL 40% OPEN STN./STL.


PERFORATED DIFFUSER
2'-7 1/2" Z 2'-7 1/2" 10'-6" 2'-7 1/2" 2'-7 1/2" 10'-6" 2'-0"
21'-0" 21'-0"

PLAN
SCALE: 1/2"=1'-0"

2 2 2 2 2 2 2 2
8'-6"
FIN. CLG.
HEIGHT
[ ] VERIFY

6'-6"
A.F.F.

REFERENCE FOR HOOD ITEM # 91 REFERENCE FOR HOOD ITEM # 95

SECTION Z-Z
MAKE-UP AIR CONNECTION SIZES AND VOLUMES SCALE: 3/4"=1'-0"
TO BE CONFIRMED PRIOR TO FABRICATION.
[ ] VERIFY
REVISIONS
REV DATE BY REMARKS

A 4-18-12 DRA ADDED MUA

B 5-31-12 DRA NO CHANGES


EQUIPMENT SCHEDULE
C 11-2-12 DRA REVISED PER RECEIVED P.O.

ELEVATION D 1-7-13 DRA ADDED VERIFY NOTE

SCALE : 1/2"=1'-0" E 1-16-13 BJW FABRICATED PER APPROVED DRAWINGS


CEILING SUPPLY PLENUMS
RECEIVED ON 1-12-13

ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH


STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE, TOTAL SUPPLY : 17,560 C.F.M. CADDY NO. 10710 -B ITEM NO.
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. INSTALLATION INFORMATION LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET 12" X 19" SUPPLY DUCTS
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES 1 CUST: SINGER EQUIPMENT
1,040 C.F.M. EACH @ 0.20" S.P. ALLOW SUFFICIENT ACCESS TO BRING
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR VENTILATOR TO BE SHIPPED IN (8) UNITS. CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. VENTILATOR INTO KITCHEN AREA ALL PLUMBING AND ELECTRICAL DISCONNECT-
12" X 19" SUPPLY DUCTS
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL 2 MAXIMUM VENTILATOR DIMENSIONS TED FOR SHIPMENT. RECONNECTED IN FIELD
1,155 C.F.M. EACH @ 0.20" S.P.

18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO 10'-6" LONG x 1'-6" WIDE x 16" HIGH BY PLUMBING AND ELECTRICAL CONTRACTORS. DATE SCALE
ESTIMATED HANGING WEIGHT: 1,260 LBS. 2-21-12 AS NOTED SHT 9
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
RESTRAINT
ELECTRICAL CONNECTIONS

FIRE-FUEL
SHUT-OFF

COILED

DEVICE
CONN. ITEM
EQUIPMENT DESCRIPTION
NO. NO. BREAKER CONNECTION CONN. CONN.
KW AMPS VOLTS NEMA NO. OUTLET NO. ACTUATOR KNOB
AMPS TYPE LENGTH STYLE
1E TRAULSEN RAC39 REFRIGERATOR 1.7 14.3 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X PILOT LIGHT
2E FUTURE EQUIPMENT 1.9 16 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X NEMA RECEPTACLE
3E TRAULSEN RAC39 REFRIGERATOR 1.7 14.3 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X
4E FUTURE EQUIPMENT 5.0 24 208 1 30 L6-30R 2620A CORD & PLUG 2'-0" X
5E TRAULSEN RAC39 REFRIGERATOR 1.7 14.3 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X
6E FUTURE EQUIPMENT 1.9 16 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X

CONNECTION LEGEND

Y
D
E=ELECTRICAL G=GAS SS=SUPERSWIVEL CF=CIMFAST

AD
C
S=STEAM SUPPLY R=STEAM RETURN DS=DOUBLE SUPERSWIVEL GF=GROUND FAULT
H=HOT WATER C=COLD WATER QD=QUICK DISCONNET HC=HARD CONN.

3"
TYPICAL CADDY CONNECTION PLATE
PLATE ASSEMBLY HOUSING INCLUDES POINT OF USE CIRCUIT BREAKER WITH
ACTUATOR KNOB, PILOT LIGHT AND NEMA RECEPTACLE. SHALL BE 5" x 9"
AND MOUNTED AS SHOWN.(RECEPTACLE COVER NOT SHOWN.)

4'-7" ALL UTILITIES INCLUDE 25%


OVER-CAPACITY FOR FUTURE EXPANSION
5'-9"

10'-0" BOLTED
6" 6" FIELD JOINT
10'-0" MAIN CIRCUIT BREAKER TO BE
3" FINISHED CEILING HANGER
CEILING RODS BY K.E.C. FURNISHED AND INSTALLED BY E.C.
6"
IN REMOTE LOCATION
1E 2E 3E 4E 5E 6E 1'-2"

PLAN VIEW
SCALE: 1/2"=1'-0"

5'-9"
4'-7"
ACCESS PANEL ACCESS PANEL
6"
(2) UNITS REQUIRED
14'-0"
BOLTED FIELD JOINT BOLTED FIELD JOINT A.F.F.
[ ] VERIFY
NOTE: PLEASE SPECIFY MAKE, MODEL NUMBER,
1'-2"
ELECTRICAL AND PLUMBING CHARACTERISTICS
ACCESS OF ALL ITEMS PLUGGING INTO RACEWAY.
PANEL
ACCESS PANEL
1E 2E 3E 4E 5E 6E
CADDY WILL PROVIDE 2'-0" LONG DROP CORDS. (5) WITH A
NEMA # 2311 LOCKING PLUG AND A NEMA # HBL5369C
6" RECEPTACLE AND (1) WITH A NEMA # 2621 LOCKING PLUG AND
2'-0" DROP A NEMA # 2623 RECEPTACLE.
CORDS BY
14'-0"
CADDY
FIN. CLG.
6" 6" 6"
HEIGHT 8'-6"
[ ] VERIFY A.F.F.
[ ] VERIFY EQUIPMENT CORD AND PLUG'S WILL BE
RISER DETAIL INSTALLED AND FURNISHED BY E.C.
SCALE: 1" = 1'-0"

NOTE:
ALL UDS COMPONENTS AND CONNECTION
POINTS ARE DESIGNED FOR COPPER WIRE.

ELEVATION END VIEW


SCALE: 1/2"=1'-0" SCALE: 3/4"=1'-0"
CM

Intertek

ROUGH-IN SCHEDULE REVISIONS


NOTES
REV DATE BY REMARKS
PLEASE SPECIFY
SYM QTY DESCRIPTION CEILING FLOOR OTHER
1. THIS UNIT IS TO BE SHIPPED IN FOUR (4) PIECES AS SHOWN IN PLAN VIEW. [ ] VERIFY FOR
UTILTIY DISTRIBUTION SYSTEM TO BE ENTRANCE INTO BUILDING AND UNIT AREA. 1 120\208V, 3PH, 60Hz., 60 AMPS
HARDWIRED AT TIME OF MANUFACTURE. EACH 2. [ ] VERIFY ROUGHING SCHEDULE. B 5-31-12 DRA ADDED UDS ITEM # 66.1
EQUIPMENT SCHEDULE
ELECTRICAL CONNECTION TO HAVE INDIVIDUAL 3. NAT'L SANITATION FOUNDATION-STANDARD #2-"FOOD SERVICE EQUIPMENT". UNIFORM
BUILDING CODE (ICBO). ETL LISTED, CONTROL # 3177269. C 11-2-12 DRA REVISED PER RECEIVED P.O.
BREAKERS LOCATED IN UDS RACEWAY.
4. ALL "VERIFIES" ON THIS DRAWING MUST BE CONFIRMED. YOUR FABRICATION APPROVAL SHALL D 1-7-13 DRA ADDED DROP CORDS AND VERIFIES TO DRAWING UTILITIES DISTRIBUTION SYSTEM
INDICATE YOUR ACCEPTANCE AS SHOWN.
5. ELECTRICAL CONTRACTOR MUST ROUGH-IN UP TO THE MAIN CONNECTION POINT. MODEL: CA-OD-E-010 10'-0" LONG

CADDY NO. 10710 ITEM NO. 66.1


GENERAL CONTRACT CONDITIONS CODE COMPLIANCE
ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH STANDARDS PUBLISHED BY THE JOB: READING HOSPITAL
UNDERWRITER'S AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY LABORATORIES, INC. INSOFAR AS THE UTILITY DISTRIBUTION SYSTEM SHALL BE ETL LISTED UNDER THE
CATEGORY "UTILITY DISTRIBUTION SYSTEM" AND MANUFACTURED IN LOC: READING, PA
APPLICABLE, CORPORATION DOES NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), NATIONAL CUST: SINGER EQUIPMENT
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET REGIONAL OR LOCAL CODE ELECTRICAL MANUFACTURER'S ASSOCIATES (NEMA), NATIONAL FIRE PROTECTION CUST#: 03304717
REQUIREMENTS IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES TO CADDY CORPORATION, UNLESS THESE CONDITIONS ASSOCIATION (NFPA) PAMPHLET NUMBER 96 AND 54, UNIFORM PLUMBING CODE
WERE PREVIOUSLY BROUGHT TO OUR ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. (UPC), AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME), NATIONAL

18820E
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL BE CONSTRUCTED IN SANITATION FOUNDATION (NSF), AND OCCUPATIONAL SAFETY AND HEALTH DATE SCALE
ADMINISTRATION (OSHA) USING ONLY U.L. LISTED, BUREAU OF MINES RATES, AGA 2-21-12 AS NOTED SHT 10
ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED
MUST BE SUBMITTED TO US IN WRITING AND ACKNOWLEDGED ON OUR STANDARD FORM. CERTIFIED AND CGA CERTIFIED COMPONENTS. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10