ELECTRICAL NOTES:
Z 1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED
EXHAUST AIR REQUIREMENTS:
AND WIRED TO J-BOX D BY CADDY. RECONNECTED ON JOBSITE 1. EXHAUST C.F.M. BASED ON 350 C.F.M. PER LINEAR FOOT.
BY ELECTRICAL CONTRACTOR. 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE OPERATION AT MEAN SEA LEVEL.
3" BY ELECTRICAL CONTRACTOR. 3. DUCT SIZE BASED ON 1,500 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE HINGED ACCESS
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM 1 EXHAUST FAN REQUIREMENTS:
DOORS
COOKING EQUIPMENT" 1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
NATIONAL SANITATION FOUNDATION TOTAL EXHAUST : 3,850 C.F.M. FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
4'-6" 2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT"
D WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR 12" X 31" EXHAUST DUCT MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER 1 3,850 C.F.M. @ 1.60" S.P.
CONTROL # 3177269 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS (9) HANGER
BRACKETS
CL ANSUL
ENCLOSURE 2.
SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.
MAKE-UP AIR MUST BE TEMPERED-HEATED OR COOLED-CONSISTENT
THE BOCA NATIONAL MECHANICAL CODE (SEE DETAIL A-A) WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND
CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT APPLICABLE CODES.
5'-6"
STANDARD MECHANICAL CODE (SBCCI)
11'-0" 1'-0" INSTALLATION:
SECTION 504 - COMMERCIAL HOODS 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES.
12'-0"
UNIFORM BUILDING CODE (ICBO) CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE
INTERNATIONAL MECHANICAL CODE (IMC) PLAN AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION.
SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS
SECTION 507 - COMMERCIAL KITCHEN HOODS SCALE: 1/2"=1'-0"
STN./STL. ENCLOSURE PANEL RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE
EXCLUDES CODE #507.2.1.1, CONSULT FACTORY
FOR COMPLIANCE OPTIONS. Z FURNISHED BY CADDY
2.
CONSTRUCTION (WALL, CEILINGS, ETC.).
VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO
AND INSTALLED BY K.E.C.
HANDLE ENVIRONMENTAL AIR.
3. ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE-OFF COLLAR TO
BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH
JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG,
GREASE AND WATER TIGHT.
4'-6" 4. MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS.
CONSTRUCTION:
(2) RECESSED FLUORESCENT 1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH
3'-6" (48") LIGHT FIXTURES CADDY SPECIFICATIONS.
3"
2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING 1'-0" FIRE PROTECTION:
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION A-A (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR 4" BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
2'-0" ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO
HIGH VELOCITY ELECTRICAL REQUIREMENTS:
SERVICE COMPONENTS AND UTILITIES 1 GREASE EXTRACTOR
1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.
12'-0"
STN./STL. ENCLOSURE PANEL FIN. CLG.
AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F,
FURNISHED BY CADDY HEIGHT REMOVABLE
BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR
AND INSTALLED BY K.E.C. [X] VERIFY STN./STL.
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD
GREASE CUP
2'-0"
STN.\STL.
GREASE CUPS 8'-6"
TOP OF
VENTILATOR JADE
1'-2" 1'-4" JMRH-48B
2'-0" 1'-6" 1'-0" 1'-1" CHARBROILER
1/2" DIA. BY 6'-0" LONG PLATED PITCO PITCO 6'-6" ITEM #161
STEEL HANGER RODS AND BOLTS 2-SSH55RSSTCS/FD PCF-14 A.F.F.
JADE JADE
FURNISHED BY K.E.C. FRYER DUMP STATION
7"* JMRH-48B JMRH-2A 7"*
ITEM #159 ITEM #160 CHARBROILER RANGE
ITEM #161 ITEM #163
JADE
9/16" HOLE FOR 1/2" 12 GA. STN. STL. JMRH-12G
THREADED ROD HANGER BRACKETS GRIDDLE JADE
(RODS AND HARDWARE FULLY WELDED TO VENTILATOR ITEM #164 JRLH-04S-T-72
BY K.E.C.) BY CADDY REFRIGERATED
JADE BASE
JLRH-04S-T-72 ITEM #162
REFRIG. BASE
ITEM #162
CM
Intertek
SYM QTY DESCRIPTION A 4-18-12 DRA ADDED MUA, AN ANSUL BOX, AND A 12" RANGE
EQUIPMENT SCHEDULE
K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA REMOVED CEILING SUPPLY PLENUMS
* - MINIMUM OVERHANG FROM EDGE OF COOKING D 1 120V, 60HZ, 1PH, 0.16 K.W. CONNECTED LOAD
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER C 11-2-12 DRA REVISED PER RECEIVED P.O.
LINE-UP PRIOR TO FABRICATION OF VENTILATORS, EQUIPMENT TO END OF HOOD MUST BE 6" D 1-7-13 DRA NO CHANGES
SHBC-C-W-132-ND-54
AND TO NOTIFY CADDY OF ANY CHANGES. E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 1
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
GENERAL NOTES
ELECTRICAL NOTES:
EXHAUST AIR REQUIREMENTS:
1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED 1. EXHAUST C.F.M. BASED ON 400 C.F.M. PER LINEAR FOOT.
AND WIRED TO J-BOX D BY CADDY. RECONNECTED ON JOBSITE 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
BY ELECTRICAL CONTRACTOR. COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
OPERATION AT MEAN SEA LEVEL.
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE 3. DUCT SIZE BASED ON 1,500 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION BY ELECTRICAL CONTRACTOR.
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM
EXHAUST FAN REQUIREMENTS:
COOKING EQUIPMENT" 1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING FIRE PROTECTION:
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT A-A 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE 4" INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
(4) RECESSED PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
1 FLUORESCENT ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO 2'-0"
(36") LIGHT FIXTURES ELECTRICAL REQUIREMENTS:
SERVICE COMPONENTS AND UTILITIES
1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.
12'-0"
AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F, STN./STL. ENCLOSURE PANEL HIGH VELOCITY
FIN. CLG.
BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR FURNISHED BY CADDY GREASE EXTRACTOR
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD HEIGHT
AND INSTALLED BY K.E.C. [X] VERIFY REMOVABLE
STN./STL.
1'-6"
GREASE CUP
STN.\STL.
GREASE CUPS 8'-6"
TOP OF
VENTILATOR
CM
SYM QTY DESCRIPTION A 4-18-12 DRA ADDED MUA AND REMOVED A 12" RANGE
EQUIPMENT SCHEDULE
K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA REMOVED CEILING SUPPLY PLENUMS
* - MINIMUM OVERHANG FROM EDGE OF COOKING D 1 120V, 60HZ, 1PH, 0.32 K.W. CONNECTED LOAD
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER C 11-2-12 DRA REVISED PER RECEIVED P.O.
LINE-UP PRIOR TO FABRICATION OF VENTILATORS, EQUIPMENT TO END OF HOOD MUST BE 6" D 1-7-13 DRA DECREASED HOOD, CFM, AND DUCT SIZE;
REVISED TO FLUORESCENT LIGHTS SHBC-C-II-92-ND-66
AND TO NOTIFY CADDY OF ANY CHANGES. E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 2
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
2 2
1
1 1
1
1 1 3 3 1 1 1 1
PITCO PITCO
2-SSH55RSSTCS/FD PCF-14 JADE JADE A
FRYER DUMP STATION JMRH-48B JMRH-2A
ITEM #159 ITEM #160 A
CHARBROILER RANGE
ITEM #161 ITEM #163 B
JADE
JMRH-12G
GRIDDLE
ITEM #164
JADE JADE JADE
JTPR-12 JMRH-60G JTPR-12 JADE
SPREADER GRIDDLE SPREADER JLRH-04S-T-72
ITEM #149 ITEM #148 ITEM #149 REFRIG. BASE
ELECTRIC
ITEM #162 B SNAP-ACTION
SWITCH
B BY CADDY
ELEVATION ITEM #151 ELEVATION ITEM #165 C
3.0 GALLON 3.0 GALLON
SCALE: 1/2"=1'-0" SCALE: 1/2"=1'-0" TANK TANK
REMOTE PULL
STATION
TANK/ENCLOSURE
ASSEMBLIES
ANSUL ROUGH-IN
ANSUL NOZZLE DATA DOUBLE TANK
SYM DESCRIPTION NITROGEN CARTRIDGE
MIN.-MAX.
3/8" SCH 40 BLACK IRON PIPE. ALL EXPOSED FLOW POINTS
A SYM QTY DESCRIPTION HEIGHT
PIPING TO BE CHROME PLATED OR STN./STL. EACH
ABOVE HAZARD
B 1/2" EMT CONDUIT 30"-40" (RANGE)
MICRO SWITCH FOR ELECTRIC 1 10 ANSUL #1N 1 35"-40" (GRIDDLE)
C SHUT-DOWN AND/OR ALARM BY CADDY 15"-40" (CHARBROILER)
WIRING BY E.C. 2 2 ANSUL #2W 2
2" MECHANICAL TYPE GAS VALVE
FURNISHED BY CADDY AND INSTALLED 3 2 ANSUL #3N 3 21"-34"
PLENUM PROTECTION D
NOZZLE BY P.C. ([ ] VERIFY SIZE).
DUCT PROTECTION
NOZZLE
DETECTORS
INSTALLATION INFORMATION
DETECTION LINE ANSUL R-102 3/3 SYSTEM ALLOW SUFFICIENT AREA TO MOUNT ANSUL ON
CLOSEST STRUCTURAL WALL TO VENTILATOR
MAXIMUM ANSUL ENCLOSURE DIMENSIONS
FOR VENTILATOR ITEMS #151 & 165 26" LONG x 7 1/2" DEEP x 23 1/2" HIGH
ESTIMATED TOTAL HANGING WEIGHT: 100 LBS.
ENCLOSURE MOUNTING HEIGHT 7'-0"
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
WIRING BETWEEN COMPONENTS BY E.C. 2-21-12 AS NOTED SHT 3
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. (LOCATED IN PANEL) DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
ELECTRICAL NOTES:
GENERAL NOTES
1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED EXHAUST AIR REQUIREMENTS:
Z AND WIRED TO J-BOX D BY CADDY. RECONNECTED ON JOBSITE 1. EXHAUST C.F.M. BASED ON 400 C.F.M. PER LINEAR FOOT.
BY ELECTRICAL CONTRACTOR. 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE OPERATION AT MEAN SEA LEVEL.
BY ELECTRICAL CONTRACTOR. 3. DUCT SIZE BASED ON 1,500 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM
EXHAUST FAN REQUIREMENTS:
COOKING EQUIPMENT" 1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
NATIONAL SANITATION FOUNDATION (6) HANGER FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
BRACKETS 2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT" (SEE DETAIL A-A) D TOTAL EXHAUST : 3,000 C.F.M. WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER 1
CONTROL # 3177269 10" X 29" EXHAUST DUCT 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
1 DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
3,000 C.F.M. @ 1.60" S.P.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.
2. MAKE-UP AIR MUST BE TEMPERED-HEATED OR COOLED-CONSISTENT
THE BOCA NATIONAL MECHANICAL CODE WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND
CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT APPLICABLE CODES.
STANDARD MECHANICAL CODE (SBCCI)
INSTALLATION:
SECTION 504 - COMMERCIAL HOODS 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES.
STN./STL. ENCLOSURE PANEL
UNIFORM BUILDING CODE (ICBO) CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE
INTERNATIONAL MECHANICAL CODE (IMC)
CL Z FURNISHED BY CADDY
AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION.
AND INSTALLED BY K.E.C. SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS
SECTION 507 - COMMERCIAL KITCHEN HOODS 3'-9" RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE
EXCLUDES CODE #507.2.1.1, CONSULT FACTORY CONSTRUCTION (WALL, CEILINGS, ETC.).
FOR COMPLIANCE OPTIONS. 7'-6"
2. VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO
PLAN 3.
HANDLE ENVIRONMENTAL AIR.
ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE-OFF COLLAR TO
SCALE: 1/2"=1'-0" BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH
7'-6" JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG,
GREASE AND WATER TIGHT.
4. MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS.
3'-4" 10" 3'-4" CONSTRUCTION:
4'-6" 1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH
CADDY SPECIFICATIONS.
(2) RECESSED 2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
FLUORESCENT
(48") LIGHT FIXTURES FIRE PROTECTION:
K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING
EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY
HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION A-A (ANSUL R-102).
NOZZLES AT TIME-OF-FABRICATION IN THE FACTORY. IF EQUIPMENT 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST
IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR BE COORDINATED WITH CADDY TO PREVENT SYSTEMS
FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE 4" INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE.
EXPENSE OF OTHERS. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT.
3. IMPORTANT NOTE: NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC
COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE
PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON
ACTIVATION OF THE SYSTEM.
ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO 2'-0"
SERVICE COMPONENTS AND UTILITIES ELECTRICAL REQUIREMENTS:
1
1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY OTHERS.
13'-0"
FIN. CLG.
AIR TEMPERATURE SHOULD RANGE FROM 60 ° TO 65°F, HEIGHT
BUT MAY BE AS LOW AS 50 ° F DEPENDING ON AIR
STN./STL. ENCLOSURE PANEL [ x] VERIFY
VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD FURNISHED BY CADDY
HIGH VELOCITY
AND INSTALLED BY K.E.C.
GREASE EXTRACTOR
2'-6" REMOVABLE
STN./STL.
GREASE CUP
STN.\STL.
GREASE CUPS 8'-6"
TOP OF JADE
VENTILATOR JMRHE-2-2
RANGE
1/2" DIA. BY 6'-0" LONG PLATED 1'-3" 1'-0" 1'-0" ITEM #189
STEEL HANGER RODS AND BOLTS 2'-3"
6'-6"
FURNISHED BY K.E.C.
JADE A.F.F.
1'-6"* 1'-6"*
JMRHE-2-2
RANGE
JADE ITEM #189
9/16" HOLE FOR 1/2" 12 GA. STN. STL.
JMRH-18B JADE
THREADED ROD HANGER BRACKETS
CHARBROILER JMRH-12G
(RODS AND HARDWARE FULLY WELDED TO VENTILATOR JADE
ITEM #190 GRIDDLE
BY K.E.C.) BY CADDY ITEM #188 JRLH-02S-T-48
REFRIGERATED
JADE BASE
JRLH-02S-T-48 ITEM #191
REFRIG. BASE
ITEM #191
CM
SYM QTY DESCRIPTION A 4-18-12 DRA ADDED MUA, INCREASED HOOD 6" AND INCREASED 12"
CHARBROILER TO A 18"
EQUIPMENT SCHEDULE
K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA REMOVED CEILING SUPPLY PLENUMS
* - MINIMUM OVERHANG FROM EDGE OF COOKING D 1 120V, 60HZ, 1PH, 0.16 K.W. CONNECTED LOAD C
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER 11-2-12 DRA REVISED PER RECEIVED P.O.
SHBC-C-II-84-ND-84
E 01/14/13 DRA REVISED FOR FABRICATION PER "APPROVED
AND TO NOTIFY CADDY OF ANY CHANGES. AS NOTED" DRAWING RECEIVED ON 01/14/13.
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 4
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
2
1
1
450°
1 1 1 1
JADE
A
JMRHE-2-2
B RANGE
JADE ITEM #189
JMRH-18B JADE
CHARBROILER JMRH-12G
ITEM #190 GRIDDLE
ITEM #188
JADE
JRLH-02S-T-48
ELECTRIC REFRIG. BASE
SNAP-ACTION B
ITEM #191
SWITCH
BY CADDY B
C
3.0 GALLON
TANK
ELEVATION
SCALE: 1/2"=1'-0"
REMOTE PULL
STATION
TANK/ENCLOSURE
ASSEMBLY
SINGLE TANK
NITROGEN CARTRIDGE
ANSUL ROUGH-IN
SYM DESCRIPTION ANSUL NOZZLE DATA
3/8" SCH 40 BLACK IRON PIPE. ALL EXPOSED MIN.-MAX.
A FLOW POINTS
PIPING TO BE CHROME PLATED OR STN./STL. SYM QTY DESCRIPTION HEIGHT
EACH
B 1/2" EMT CONDUIT ABOVE HAZARD
30"-40" (RANGE)
MICRO SWITCH FOR ELECTRIC
1 6 ANSUL #1N 1 35"-40" (GRIDDLE)
C SHUT-DOWN AND/OR ALARM BY CADDY
WIRING BY E.C. 15"-40" (CHARBROILER)
DUCT PROTECTION
NOZZLE
DETECTORS
INSTALLATION INFORMATION
DETECTION LINE ANSUL R-102 3 SYSTEM ALLOW SUFFICIENT AREA TO MOUNT ANSUL ON
CLOSEST STRUCTURAL WALL TO VENTILATOR
MAXIMUM ANSUL ENCLOSURE DIMENSIONS
FOR VENTILATOR ITEMS #196 16 1/2" LONG x 7 1/2" DEEP x 23 1/2" HIGH
ESTIMATED TOTAL HANGING WEIGHT: 75 LBS.
ENCLOSURE MOUNTING HEIGHT 7'-0"
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
WIRING BETWEEN COMPONENTS BY E.C. 2-21-12 AS NOTED SHT 5
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. (LOCATED IN PANEL) DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
GENERAL NOTES
EXHAUST AIR REQUIREMENTS:
FLUE DUCT BY K.E.C. 1. EXHAUST C.F.M. BASED ON 200 C.F.M. PER LINEAR FOOT.
6" FLUE 2. EXHAUST STATIC PRESSURE IS 1.60" W.G. AT DUCT TAKE-OFF
OR OTHER PRESCRIBED
COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON
CONTRACTOR.
OPERATION AT MEAN SEA LEVEL.
3. DUCT SIZE BASED ON 1,800 F.P.M.
NATIONAL FIRE PROTECTION ASSOCIATION
IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE
PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM
1 1/2" X 1 1/2" STN./STL. EXHAUST FAN REQUIREMENTS:
COOKING EQUIPMENT" Z MOUNTING ANGLE BY
CADDY. SEE DETAIL
1. TYPE - INDUCED DRAFT, SQUIRREL CAGE, BACKWARD INCLINED
BLADES, EXHAUST FAN DISCHARGE SHOULD BE VERTICAL, AWAY
NATIONAL SANITATION FOUNDATION FROM AIR INTAKES. FAN FURNISHED BY OTHERS.
2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER
STANDARD #2 - "FOOD SERVICE EQUIPMENT"
WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS.
ETL, INTERTEK 1
TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR MAKE-UP AIR REQUIREMENTS:
COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER 2'-6"
CONTROL # 3177269 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH
DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN.
UNIFORM MECHANICAL CODE VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR
SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION
VENTILATION SYSTEMS SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES.
6'-2"
A.F.F.
[X] VERIFY BAKERS
PRIDE
FC-516/DS-805
PIZZA OVEN
ITEM #174
BAKERS PRIDE
FC-516/DS-805
ATTACHING PIZZA OVEN
HARDWARE ITEM #174
BY K.E.C.
VENTILATOR TO
KITCHEN EQUIPMENT
R
R
Intertek
REVISIONS
REV DATE BY REMARKS
MOUNTING ANGLE DETAIL A-A A 4-18-12 DRA REVISED HOOD TO 5'-0" LONG AND ADDED
SCALE: 3/4"=1'-0" K.E.C. TO VERIFY ALL MAKES AND MODELS OF B 5-31-12 DRA
FLUE CONNECTION
NO CHANGES
EQUIPMENT SCHEDULE
COOKING EQUIPMENT, REVIEW PLAN FOR PROPER C 11-2-12 DRA REVISED PER RECEIVED P.O.
D 1-7-13 DRA
LINE-UP PRIOR TO FABRICATION OF VENTILATORS, ADDED DIMENSION AND REVISED NOTE TO
CLARIFY 2" X 6" DIA. DUCT CONNECTION. SHBC-BK-I-60-ND-30
AND TO NOTIFY CADDY OF ANY CHANGES. E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 6
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
2
360°
A
B
TANK/ENCLOSURE
ASSEMBLY
SINGLE TANK
NITROGEN CARTRIDGE
ANSUL ROUGH-IN
SYM DESCRIPTION ANSUL NOZZLE DATA
3/8" SCH 40 BLACK IRON PIPE. ALL EXPOSED MIN.-MAX.
A FLOW POINTS
PIPING TO BE CHROME PLATED OR STN./STL. SYM QTY DESCRIPTION HEIGHT
EACH
B 1/2" EMT CONDUIT ABOVE HAZARD
1 1 ANSUL #1N 1
MICRO SWITCH FOR ELECTRIC
C SHUT-DOWN AND/OR ALARM BY CADDY 2 1 ANSUL #2W 2
WIRING BY E.C.
2" MECHANICAL TYPE GAS VALVE
PLENUM PROTECTION D FURNISHED BY CADDY AND INSTALLED
NOZZLE BY P.C. ([ ] VERIFY SIZE).
DUCT PROTECTION
NOZZLE
DETECTORS
INSTALLATION INFORMATION
DETECTION LINE ANSUL R-102 3 SYSTEM ALLOW SUFFICIENT AREA TO MOUNT ANSUL ON
CLOSEST STRUCTURAL WALL TO VENTILATOR
MAXIMUM ANSUL ENCLOSURE DIMENSIONS
FOR VENTILATOR ITEMS #174.1 16 1/2" LONG x 7 1/2" DEEP x 23 1/2" HIGH
ESTIMATED TOTAL HANGING WEIGHT: 75 LBS.
ENCLOSURE MOUNTING HEIGHT 7'-0"
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
WIRING BETWEEN COMPONENTS BY E.C. 2-21-12 AS NOTED SHT 7
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. (LOCATED IN PANEL) DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
20'-6"
[X] VERIFY WALL OPENING
Z 1/2" Ø DRAIN
1 1
5'-0"
1'-6"
(20) HANGER
BRACKETS
(SEE DETAIL A-A)
2'-6"
[X] VERIFY
1'-6" 2 2 2 2
2'-6 11/16"
5'-1 3/8" 10'-2 3/4" Z 1. LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED
(TYP.) (TYP.) 3" 11" 1'-2" 2'-11" AND WIRED TO J-BOX D BY CADDY. DISCONNECTED FOR SHIPPING AT
20'-5 1/2" 1'-0" J-BOX C . RECONNECTED ON JOBSITE BY ELECTRICAL CONTRACTOR.
2. LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE BY
PLAN ELECTRICAL CONTRACTOR.
SCALE: 1/2"=1'-0" 4"
2 1 2 2 1 2
A-A
1'-0"
1/2" DIA. BY 6'-0" LONG PLATED
4"
STEEL HANGER RODS AND BOLTS
FURNISHED BY K.E.C.
20'-6"
SLIDING
10'-3" 10'-2 3/4" DAMPER
2'-0" 9/16" HOLE FOR 1/2" 12 GA. STN. STL.
(4) RECESSED FULL PERIMETER
4'-6 3/8" 1'-2" 4'-6 3/8" 4'-6 3/8" 1'-2" 4'-6 3/8" THREADED ROD HANGER BRACKETS
FLUORESCENT GUTTER
(36") LIGHT FIXTURES (RODS AND HARDWARE FULLY WELDED TO VENTILATOR
BY K.E.C.) BY CADDY
1/2" Ø DRAIN
(INDIRECT WASTE)
8'-6"
FIN. CLG.
HEIGHT
1/2" Ø DRAIN
[X] VERIFY HANGER BRACKET DETAIL A-A
6'-6" SCALE: 1/4"=1"
A.F.F.
NOTES REVISIONS
REV DATE BY REMARKS
INSTALLATION INFORMATION
1. AIR SYSTEMS SHALL NOT BE LIABLE FOR IMPROPER FUNCTION DUE TO CHANGE IN
ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR TO BE SHIPPED IN (2) UNITS. STATIC PRESSURE OR AIR VOLUMES SPECIFIED. A 4-18-12 DRA ADDED MUA
VENTILATOR INTO KITCHEN AREA ALL PLUMBING AND ELECTRICAL DISCONNECT- 2. ALL DIMENSIONS TO BE VERIFIED IN FIELD BY OTHERS BEFORE VENTILATORS B 5-31-12 DRA NO CHANGES
EQUIPMENT SCHEDULE
MAXIMUM VENTILATOR DIMENSIONS TED FOR SHIPMENT. RECONNECTED IN FIELD ARE RELEASED FOR MANUFACTURE.
10'-8" LONG x 5'-0" WIDE x 28 1/2" HIGH C 11-2-12 DRA REVISED PER RECEIVED P.O.
BY PLUMBING AND ELECTRICAL CONTRACTORS. 3. INDICATE ALL BEAMS, COLUMNS, ETC. WHICH MAY CONFLICT WITH VENTILATOR
ESTIMATED HANGING WEIGHT: 1,173 LBS. OR EXHAUST OUTLET COLLAR(S) (INDICATE SIZE, LOCATION, AND HEIGHT ABOVE D 1-7-13 DRA REVISED TO FLUORESCENT LIGHTS AND
FINISHED FLOOR.) UPDATED EQUIPMENT UNDER HOOD CH-C-W-122.75-SD-60
4. INSTALLING CONTRACTOR SHALL CHECK ALL BUILDING ACCESS, ENTRANCE AND FIELD E 01/14/13 DME REVISED FOR FABRICATION PER "APPROVED
AS NOTED" DRAWING RECEIVED ON 01/14/13.
CONDITIONS TO ENSURE SUFFICIENT CLEARANCE TO ALLOW VENTILATOR SECTION(S)
ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH
ROUGH-IN SCHEDULE (SIZE(S) AS DIMENSIONED ON THIS DRAWING) TO BE BROUGHT INTO BUILDING AND
STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE,
INSTALLED ACCORDING TO AIR SYSTEMS RECOMMENDATIONS. CADDY NO. 10710 -A ITEM NO. B1
AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES 5. ALL EXHAUST DUCT COLLARS ARE INSIDE DIMENSIONS.
NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL SYM QTY DESCRIPTION 6. ALL DUCTWORK BEYOND THE VENTILATOR OR EXHAUST DUCT COLLAR(S) TO BE PROVIDED
AND INSTALLED BY OTHERS IN ACCORDANCE WITH JURISDICTIONAL CODES, AND MUST
JOB: READING HOSPITAL
CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. LOC: READING, PA
ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET D 1 120V, 60HZ, 1PH, 0.32 K.W. CONNECTED LOAD BE MECHANICALLY STRONG, AND GREASE AND WATER TIGHT.
REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES 7. VENTILATOR(S) SHALL BE N.S.F. APPROVED AND SHALL BEAR N.S.F. LABELS VISIBLY CUST: SINGER EQUIPMENT
TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR AFFIXED TO EXTERIOR. CUST#: 03304717
ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. 8. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL.
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO DATE SCALE
2-21-12 AS NOTED SHT 8
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
Z
1/2" DIA. BY 6'-0" LONG PLATED
STEEL HANGER RODS AND BOLTS
FURNISHED BY K.E.C.
1'-6" 1 1 1 1 1 1 1 1
A-A
1'-6" MIN.
4'-0" MAX. 4" 4"
1'-0" 1'-0"
1'-6" 2 2 2 2 2 2 2 2
PLAN
SCALE: 1/2"=1'-0"
2 2 2 2 2 2 2 2
8'-6"
FIN. CLG.
HEIGHT
[ ] VERIFY
6'-6"
A.F.F.
SECTION Z-Z
MAKE-UP AIR CONNECTION SIZES AND VOLUMES SCALE: 3/4"=1'-0"
TO BE CONFIRMED PRIOR TO FABRICATION.
[ ] VERIFY
REVISIONS
REV DATE BY REMARKS
18820E
BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO 10'-6" LONG x 1'-6" WIDE x 16" HIGH BY PLUMBING AND ELECTRICAL CONTRACTORS. DATE SCALE
ESTIMATED HANGING WEIGHT: 1,260 LBS. 2-21-12 AS NOTED SHT 9
FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND
ACKNOWLEDGED ON OUR STANDARD FORM. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10
RESTRAINT
ELECTRICAL CONNECTIONS
FIRE-FUEL
SHUT-OFF
COILED
DEVICE
CONN. ITEM
EQUIPMENT DESCRIPTION
NO. NO. BREAKER CONNECTION CONN. CONN.
KW AMPS VOLTS NEMA NO. OUTLET NO. ACTUATOR KNOB
AMPS TYPE LENGTH STYLE
1E TRAULSEN RAC39 REFRIGERATOR 1.7 14.3 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X PILOT LIGHT
2E FUTURE EQUIPMENT 1.9 16 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X NEMA RECEPTACLE
3E TRAULSEN RAC39 REFRIGERATOR 1.7 14.3 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X
4E FUTURE EQUIPMENT 5.0 24 208 1 30 L6-30R 2620A CORD & PLUG 2'-0" X
5E TRAULSEN RAC39 REFRIGERATOR 1.7 14.3 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X
6E FUTURE EQUIPMENT 1.9 16 120 1 20 L5-20R 2310A CORD & PLUG 2'-0" X
CONNECTION LEGEND
Y
D
E=ELECTRICAL G=GAS SS=SUPERSWIVEL CF=CIMFAST
AD
C
S=STEAM SUPPLY R=STEAM RETURN DS=DOUBLE SUPERSWIVEL GF=GROUND FAULT
H=HOT WATER C=COLD WATER QD=QUICK DISCONNET HC=HARD CONN.
3"
TYPICAL CADDY CONNECTION PLATE
PLATE ASSEMBLY HOUSING INCLUDES POINT OF USE CIRCUIT BREAKER WITH
ACTUATOR KNOB, PILOT LIGHT AND NEMA RECEPTACLE. SHALL BE 5" x 9"
AND MOUNTED AS SHOWN.(RECEPTACLE COVER NOT SHOWN.)
10'-0" BOLTED
6" 6" FIELD JOINT
10'-0" MAIN CIRCUIT BREAKER TO BE
3" FINISHED CEILING HANGER
CEILING RODS BY K.E.C. FURNISHED AND INSTALLED BY E.C.
6"
IN REMOTE LOCATION
1E 2E 3E 4E 5E 6E 1'-2"
PLAN VIEW
SCALE: 1/2"=1'-0"
5'-9"
4'-7"
ACCESS PANEL ACCESS PANEL
6"
(2) UNITS REQUIRED
14'-0"
BOLTED FIELD JOINT BOLTED FIELD JOINT A.F.F.
[ ] VERIFY
NOTE: PLEASE SPECIFY MAKE, MODEL NUMBER,
1'-2"
ELECTRICAL AND PLUMBING CHARACTERISTICS
ACCESS OF ALL ITEMS PLUGGING INTO RACEWAY.
PANEL
ACCESS PANEL
1E 2E 3E 4E 5E 6E
CADDY WILL PROVIDE 2'-0" LONG DROP CORDS. (5) WITH A
NEMA # 2311 LOCKING PLUG AND A NEMA # HBL5369C
6" RECEPTACLE AND (1) WITH A NEMA # 2621 LOCKING PLUG AND
2'-0" DROP A NEMA # 2623 RECEPTACLE.
CORDS BY
14'-0"
CADDY
FIN. CLG.
6" 6" 6"
HEIGHT 8'-6"
[ ] VERIFY A.F.F.
[ ] VERIFY EQUIPMENT CORD AND PLUG'S WILL BE
RISER DETAIL INSTALLED AND FURNISHED BY E.C.
SCALE: 1" = 1'-0"
NOTE:
ALL UDS COMPONENTS AND CONNECTION
POINTS ARE DESIGNED FOR COPPER WIRE.
Intertek
18820E
ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL BE CONSTRUCTED IN SANITATION FOUNDATION (NSF), AND OCCUPATIONAL SAFETY AND HEALTH DATE SCALE
ADMINISTRATION (OSHA) USING ONLY U.L. LISTED, BUREAU OF MINES RATES, AGA 2-21-12 AS NOTED SHT 10
ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED
MUST BE SUBMITTED TO US IN WRITING AND ACKNOWLEDGED ON OUR STANDARD FORM. CERTIFIED AND CGA CERTIFIED COMPONENTS. DR BY
BJW
APP'D BY
BJW DWG# D-1-10710 OF 10