Reference: 2212828/AM/LPS/43 Zouk Mosbeh, 28/07/2023

Project: EHMIJ 3698

Concerned Mission: L + PS

Sent by mail to: eyfarhat@gmail.com Addressee: Eng. Elie Farhat

Dear Sir,

After examination of the specified documents below, please find the observations that we can formulate at present within the scope of the
mission referenced here above.

Best regards,

The Engineer: A. MOUSSA The Manager: N. MOUSSA

Abbreviation used: F: Favorable Opinion - S: Suspended Opinion - D: Unfavorable Opinion - HM: Hors Mission

Documents or Drawings Designation Opinion Observations / Notes / Comments

Structural drawings: F Our verification is based on the following assumptions:


 S100: FOUNDATION + B1  By referring to the soil investigation report issued by Mr. Kamal
 S101: GROUND FLOOR Bou Zaeineldeen on September 2022:

 S102: LEVEL 1 - The allowable soil bearing capacity is equal to 50.0 T/m2

 S103: LEVEL 2 - The modulus of subgrade is equal to 39 MPa/m

 S104: ROOF - The ground type is B (IBC 2018 Classification).

 S105: TOP OF ROOF  The nominal acceleration for seismic design is 0.25g.

 S106: ELEMENTS  The seismic analysis was carried out based on ASCE 7-16
standards (IBC 2018).
 S107: ELEMENTS 2
 Minimum 28-day compressive strength of concrete is 30 MPa
 S1001: TYP DETAILS
for all reinforced concrete structural members.
 Minimum yield stress is 500 MPa for ordinary deformed steel
reinforcement bars.
 The considered loads for the ground, first, and second floors:
- Uniform super-imposed dead load of 3.0 kPa
- Uniform live load of 4.79 kPa
 The considered loads for the roof:
- Uniform super-imposed dead load of 3.0 kPa
- Uniform live load of 2.0 kPa
 The considered loads for the top-of-roof:
- Uniform live load of 1.0 kPa