-ANALYSIS OF ANCHOR BOLT (FISCHER) based on the Site Condition - UCW

Document Number:
MI - MM - A2 - B01.00 - S0 - RT - 011 05 00 A
Proj Orig. Package Building Discipline Doc Type Sequence Phase Revision Issue
SECURITY FORCES MEDICAL CENTER
Riyadh, Kingdom of Saudi Arabia

ANALYSIS OF ANCHOR BOLT (FISCHER) based on the


(Site Installed Condition)

BY: AMG COMPANY

REVISION 00
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

fischer FZE

Jebel Ali Free Zone Warehouse No XB


P.O. Box 261738 Dubai

Enquiry@fischer.ae
www.fischer.ae

Design Specifications
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 24/60 R,
stainless steel
Calculated anchorage 125 mm
depth
Design Data Anchor design in Concrete according European Technical
Assessment ETA-05/0069, Option 1,
Issued 24/04/2020

Geometry / Loads / Scale units


mm, kN, kNm

Value of design actions (including

partial safety factor for the load) Static

Not drawn to scale

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 1
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

Input data

Design method TR055/ETAG 001, Annex C, Method A


Base material C45/55, EN 206
Concrete condition Cracked, dry hole
Reinforcement No or standard reinforcement. Edge reinforcement with
stirrups. With reinforcement against splitting
Drilling method Hammer drilling
Installation type Push-through installation
Annular gap Annular gap not filled
Type of loading Permanent-Transient/Static
Base plate location Base plate with non bearing layer, e.g. grout pad., g = 30 mm
calc. lever arm l = 53 mm
Degree of restraint αM = 2.0
Mortar compression strength: 60.0 N/mm²
Base plate geometry 300 mm x 270 mm x 22 mm
Profile type None

Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
kN kN kN kNm kNm kNm
1 -8.54 0.00 -39.55 0.72 0.00 0.00 Permanent-Transient/Static

*⁾ The required partial safety factors for actions are included

Resulting anchor forces


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. kN kN kN kN
1 5.28 19.78 0.00 -19.78
2 5.28 19.78 0.00 -19.78

max. concrete compressive strain : 0.05 ‰


max. concrete compressive stress : 2.0 N/mm²
Resulting tensile actions : 10.57 kN , X/Y position ( 0 / 75 )
Resulting compression actions : 19.11 kN , X/Y position ( 0 / -53 )

Resistance to tension loads

Action Capacity Utilisation βN


Proof kN kN %
Steel failure * 5.28 122.40 4.3
Concrete cone failure 10.57 64.53 16.4

* Most unfavourable anchor


The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 2
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

Steel failure

( NRd,s )

NRk,s γMs NRd,s NSd βN,s


kN kN kN %
183.60 1.50 122.40 5.28 4.3

βN,s
Anchor no. % Group N° Decisive Beta
1 4.3 1 βN,s;1
2 4.3 2 βN,s;2

Concrete cone failure

( NRd,c )

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

Eq. (5.2e)

NRk,c γMc NRd,c NSd βN,c


kN kN kN %
96.80 1.50 64.53 10.57 16.4

βN,c
Anchor no. % Group N° Decisive Beta
1, 2 16.4 1 βN,c;1

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 3
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

Resistance to shear loads

Proof Action Capacity Utilisation βV


kN kN %
Steel failure with lever arm * 19.78 26.06 75.9
Concrete pry-out failure 39.55 154.88 25.5
Concrete edge failure 39.55 58.32 67.8

* Most unfavourable anchor

Steel failure with lever arm

( VRd,s )

Eq. (5.5/a)

VRk,s γMs VRd,s VSd βVs


kN kN kN %
32.58 1.25 26.06 19.78 75.9

βVs
Anchor no. % Group N° Decisive Beta
1 75.9 1 βVs;1
2 75.9 2 βVs;2

Concrete pry-out failure

( VRd,cp )

Eq. (5.6)

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

Eq. (5.2e)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 4
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

VRk,cp γMc VRd,cp VSd βV,cp


kN kN kN %
232.33 1.50 154.88 39.55 25.5

βV,cp
Anchor no. % Group N° Decisive Beta
1, 2 25.5 1 βV,cp;1

Concrete edge failure

( VRd,c )

Eq. (5.7)

Eq. (5.7a)

Eq. (5.7b/c)

Eq. (5.7e)

Eq. (5.7f)

Eq. (5.7g)

Eq. (5.7h)

VRk,c γMc VRd,c VSd βV,c


kN kN kN %
87.49 1.50 58.32 39.55 67.8

βV,c
Anchor no. % Group N° Decisive Beta
1, 2 67.8 1 βV,c;1

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 5
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

Utilization of tension and shear loads

Tension loads Utilisation βN Shear Loads Utilisation βV


% %
Steel failure * 4.3 Steel failure with lever arm * 75.9
Concrete cone failure 16.4 Concrete pry-out failure 25.5
Concrete edge failure 67.8

* Most unfavourable anchor

Resistance to combined tensile and shear loads


Eq. (5.8a)
Proof successful Eq. (5.8b)

Eq. (5.9)

Information concerning the anchor plate


Base plate details
Plate thickness specified by user without proof t = 22 mm

Profile type None

Technical remarks
All data and information in the software is based on fischer products and common engineering knowledge. Please
check all the proof results against local valid standards and approvals.
As fischer is not the design office, the attached is no guarantee for incorrect input or assumptions. Any
recommendations have to be approved by the building-authority or project engineer. Results are valid only for
anchor system calculated in the attached. If any part of the system is changed, it will invalidate this report and new
calculations would be required. The calculation was done under the assumption that a sufficient
splitting reinforcement is available. In this case the spliiting
failure can be omitted.
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must
be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the
stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 6
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021

Installation data
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 24/60 R, Art.-No. 503184
stainless steel

Accessories Blow-out pump ABG big Art.-No. 89300


SDS Plus-V II 24/400/450 Art.-No. 531854
or alternatively
FHD Max 24/400/620 Art.-No. 546604
Hammer drilling with or without
suction

Installation details
Thread diameter M 24
Drill hole diameter d0 = 24 mm
Drill hole depth h2 = 219 mm
Calculated anchorage hef = 125 mm
depth
Installation depth hnom = 149 mm
Drilling method Hammer drilling
Drill hole cleaning Only blow out by hand
No borehole cleaning required in
case of using a hollow drill bit, e.g.
fischer FHD.
Installation type Push-through installation
Annular gap Annular gap not filled
Installation torque Tinst = 270.0 Nm
Socket size 36 mm
Base plate thickness t = 22 mm
Grout thickness g ≤ 30 mm
Total fixing thickness tfix ≤ 52 mm
Tfix,max tfix, max = 60 mm

Base plate details


Base plate material S 235 (St 37)
Base plate thickness t = 22 mm
Clearance hole in base df=26 mm
plate

Attachment
Profile type None

Anchor coordinates

x y
Anchor no. mm mm
1 -100 75
2 100 75

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 7
ATTACHED DRAWING
NOTES A0

GENERAL NOTES
1- ALL DIMENSIONS ARE IN MILLIMETER

2- ALL LEVELS ARE IN METER

3- SIZES & TYPES OF BOLTS , BRACKET & ANCHORS BASE ON


THE APPROVED CALCULATION

4- ALL ELEVATION ARE VIEWED FROM EXTERNAL

5- ALUMINUM FLASHING TO VERIFY ACTUAL SITE CONDITION


AND BE INSTALLED AS NEEDED

6- ALL DIMENSION & SIZES SHALL BE VERIFIED AT SITE BEFORE


INSTALLATION OR EXECUTION OF ANY WORK

7- ALL MATERIALS TEXTURE , COLOR SHALL BE AS PER


APPROVED MATERIALS

GLASS SPECIFICATION

1.5mm THICK ALUMINUM SHEET GL2-37.5mm- THICK INSULATED


LAMINATED GLASS
POWDER COATING RAL7042 8mm-THICK SUNGUARD DS GRAY
30/22T POS.2 HS GLASS (EXTERNAL )

BY OTHER
10mm THICK SUNGUARD SOLAR 20mm AIR 100%
9.52mm STRATOPHONE 44.4(4mm
63
M10X30 STAINLESS STEEL GRAY 33T POS.2 TOUGHENED FLOAT CLEAR TOUGHENED +1.52mm
ACOUSTIC PVB CLEAR +4mm FLOAT

HEXAGONAL BOLT WITH NUT & GLASS (EXTERNAL) CLEAR TOUGHENED)


GLASS(EXTERNAL)

ALUMINUM FLOOR WASHER ASSEMBLY ALUMINUM INTERMEDIATE


TRANSOM (VU-179*N) SP1-150mm THICK SPANDREL PANEL

OUTSIDE
BRACKET (VU-237) ALUMINUM MULLION BRACKET 10mm SUNGUARD SOLAR GRAY
33T POS.2 TOUGHENED GLASS
PLATE (VU-235) #10 (∅4.8mm) X 50mm LENGTH 79 AIR GAP
1.5MM THICK ALUMINUM SHEET
ALUMINUM SERRATED WASHER 244
STAINLESS STEEL FLAT HEAD 60MM THICK ROCKWOOL
M14X60 STAINLESS STEEL INSULATION

HEXAGONAL SOCKET HEAD SELF TAPPING SCREW 1.5 THICK ALUMINUM SHEET FOR
EXPOSED AREA
94 63 43 4 24 6 10
M24X240mm STAINLESS STEEL

INSIDE
OR
ADJUSTMENT BOLT TRANSOM ALUMINUM GLAZING 1.5MM THICK GI SHEET FOR NON
HEXAGONAL BOLT WITH NUT & EXPOSED AREA/ SLAB / SHEAR

WASHER ASSEMBLY Art.-No. 503184 M16 STAINLESS STEEL ADAPTOR (VU-259) WALL SHEET.

NOTE: ANY ACCESSIBLE AREA GLASS WALL BE TOUGHENED


HEXAGONAL BOLT WITH NUT & IF NOT GLASS WILL BE HEAT STRENGTHENED

WASHER ASSEMBLY 74 126 SILICONE GASKET


ALUMINUM COMPOSED PANEL
ALUMINUM HOOK BRACKET 300 ACP 1- 5mm THICK ALUMINIUM
COMPOSITE PANEL (RAL9003)
(VU-236)
ALUMINUM FLOOR STRUCTURAL BONDING
BRACKET (VU-237) SEALANT
DOUBLE SIDED ADHESIVE TAPE
9

1 % F A L L

90
110 ACP2- 5mm THICK ALUMINIUM

22
COMPOSITE PANEL (RAL7043)

30 STRUCTURAL BONDING ACP3 - 5mm THICK ALUMINIUM

45
COMPOSITE PANEL (RAL7042)GRAY
235
150 SEALANT

140
280
#12 (∅5.5mm) X 19mm LENGTH

45
IFC DRAWING REF
STAINLESS STEEL PAN HEAD
138

FACADE MATERIAL:
SELF TAPPING SCREW

25
12- ALUMINUM CURTAIN WALL SYSTEM
21- ALUMINUM COMPOSITE PANEL
22- ALUMINUM LOUVRE SYSTEM
25- ALUMINUM PERFORATED SCREEN
280 WITH CUSTOM PATTERN
110 26- 50% PERFORATED ALUMINUM
SEPARATOR SHIMMING ALUMINUM ANGLE PANEL.
44 6 40
150
SIZE 40*40*4
ALUMINUM SERRATED WASHER 110
ACP1-ALUM COMPOSIDE PANEL

40
5mm THICK

50

40
6mm THICK ALUMINUM
BRACKET PLATE
85
∅5.5X50MM SELF TAPING
SCREW WITH PLASTIC ALUMINUM TUBE
PLUG SIZE 40*25*3

#12 (∅5.5mm) X 20mm FOR APPROVAL


00 28-06-2021 MM
LENGTH STAINLESS STEEL Rev. Date Orig. Signature ABV App. Signature Revision Description

HEX. HEAD SELF DRILLING Keyplan

NO E
H
NORTH TRU
RT
ZONE 1-10

PROJECT
SCREW

MAKKAH
M8X25 STAINLESS STEEL
HEXAGONAL BOLT WITH
NUT & WASHER
1.5mm GI SHEET ASSEMBLY
SMOKE FLASHING
GI ANGLE
SIZE 100x60mm THICK 2mm
Rock Wool 100mm FIRE STOP SUPPORT Owner
Thickness
Kingdom of Saudi Arabia
/Density120/m³ ALUM TUBE STIFFENER Ministry of Interior
63
20X20MM THICK 2MM
1.5mm THICK ALUMINUM SHEET (EACH 800MM WHEREVER
POWDER COATING RAL7042 PANEL HAVE MORE 2M HEIGHT ) SECURITY FORCES MEDICAL CENTER PROJECT AT RIYADH AND JEDDAH

Engineer / Owner's Representative


60mm THICK ROCKWOOL
INSULATION WITH
DENSITY: 128 KG/m3

36 VERTICAL SECTION DETAIL GI SHEET Contractor: ABV Rock Group Co. Ltd.

037 SCALE 1:2


THICK 1.5mm

ABV Rock Group Co. Ltd. Designer / Consultant

P&T Architects and Engineers Ltd.


5/F, Unit 510 Block B, Sheikh Hamdan Awards
Complex Bldg. Mina Rashid/ Jumeirah 1 Road
P.O.Box 112025, Dubai, UAE
TEL: +971 4 363 5430 FAX: +971 4 363 5429
www.p-t-group.com

Sub Consultant

CAD/BIM Filename: Scale: Floor:

MI-MM-A2-B01.00-01-A0-90-(030-040)-08-00-A
1:2 L04-L11
Drawing Title:

SECURITY FORCES MEDICAL CENTER RIYADH, KSA


Vertical Section Detail (36)
BLOCK 01

Drawing No.
MI MM A2 B01.02 A0 90 037 08 00 A

Project Orig. Package Building Discipline Type Sequence Phase Revision Issue Code

You might also like