Document Title:
Security Forces Medical Centre Riyadh, KSA
-ANALYSIS OF ANCHOR BOLT (FISCHER) based on the Site Condition - UCW
Document Number:
MI - MM - A2 - B01.00 - S0 - RT - 011 05 00 A
Proj Orig. Package Building Discipline Doc Type Sequence Phase Revision Issue
SECURITY FORCES MEDICAL CENTER
Riyadh, Kingdom of Saudi Arabia
REVISION 00
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
fischer FZE
Enquiry@fischer.ae
www.fischer.ae
Design Specifications
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 24/60 R,
stainless steel
Calculated anchorage 125 mm
depth
Design Data Anchor design in Concrete according European Technical
Assessment ETA-05/0069, Option 1,
Issued 24/04/2020
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.
Page 1
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
Input data
Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
kN kN kN kNm kNm kNm
1 -8.54 0.00 -39.55 0.72 0.00 0.00 Permanent-Transient/Static
Page 2
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
Steel failure
( NRd,s )
βN,s
Anchor no. % Group N° Decisive Beta
1 4.3 1 βN,s;1
2 4.3 2 βN,s;2
( NRd,c )
Eq. (5.2)
Eq. (5.2a)
Eq. (5.2c)
Eq. (5.2d)
Eq. (5.2e)
βN,c
Anchor no. % Group N° Decisive Beta
1, 2 16.4 1 βN,c;1
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.
Page 3
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
( VRd,s )
Eq. (5.5/a)
βVs
Anchor no. % Group N° Decisive Beta
1 75.9 1 βVs;1
2 75.9 2 βVs;2
( VRd,cp )
Eq. (5.6)
Eq. (5.2)
Eq. (5.2a)
Eq. (5.2c)
Eq. (5.2d)
Eq. (5.2e)
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.
Page 4
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
βV,cp
Anchor no. % Group N° Decisive Beta
1, 2 25.5 1 βV,cp;1
( VRd,c )
Eq. (5.7)
Eq. (5.7a)
Eq. (5.7b/c)
Eq. (5.7e)
Eq. (5.7f)
Eq. (5.7g)
Eq. (5.7h)
βV,c
Anchor no. % Group N° Decisive Beta
1, 2 67.8 1 βV,c;1
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.
Page 5
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
Eq. (5.9)
Technical remarks
All data and information in the software is based on fischer products and common engineering knowledge. Please
check all the proof results against local valid standards and approvals.
As fischer is not the design office, the attached is no guarantee for incorrect input or assumptions. Any
recommendations have to be approved by the building-authority or project engineer. Results are valid only for
anchor system calculated in the attached. If any part of the system is changed, it will invalidate this report and new
calculations would be required. The calculation was done under the assumption that a sufficient
splitting reinforcement is available. In this case the spliiting
failure can be omitted.
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must
be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the
stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.
Page 6
C-FIX 1.104.0.0
Database version
2021.10.25.12.40
Date
02/11/2021
Installation data
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 24/60 R, Art.-No. 503184
stainless steel
Installation details
Thread diameter M 24
Drill hole diameter d0 = 24 mm
Drill hole depth h2 = 219 mm
Calculated anchorage hef = 125 mm
depth
Installation depth hnom = 149 mm
Drilling method Hammer drilling
Drill hole cleaning Only blow out by hand
No borehole cleaning required in
case of using a hollow drill bit, e.g.
fischer FHD.
Installation type Push-through installation
Annular gap Annular gap not filled
Installation torque Tinst = 270.0 Nm
Socket size 36 mm
Base plate thickness t = 22 mm
Grout thickness g ≤ 30 mm
Total fixing thickness tfix ≤ 52 mm
Tfix,max tfix, max = 60 mm
Attachment
Profile type None
Anchor coordinates
x y
Anchor no. mm mm
1 -100 75
2 100 75
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.
Page 7
ATTACHED DRAWING
NOTES A0
GENERAL NOTES
1- ALL DIMENSIONS ARE IN MILLIMETER
GLASS SPECIFICATION
BY OTHER
10mm THICK SUNGUARD SOLAR 20mm AIR 100%
9.52mm STRATOPHONE 44.4(4mm
63
M10X30 STAINLESS STEEL GRAY 33T POS.2 TOUGHENED FLOAT CLEAR TOUGHENED +1.52mm
ACOUSTIC PVB CLEAR +4mm FLOAT
OUTSIDE
BRACKET (VU-237) ALUMINUM MULLION BRACKET 10mm SUNGUARD SOLAR GRAY
33T POS.2 TOUGHENED GLASS
PLATE (VU-235) #10 (∅4.8mm) X 50mm LENGTH 79 AIR GAP
1.5MM THICK ALUMINUM SHEET
ALUMINUM SERRATED WASHER 244
STAINLESS STEEL FLAT HEAD 60MM THICK ROCKWOOL
M14X60 STAINLESS STEEL INSULATION
HEXAGONAL SOCKET HEAD SELF TAPPING SCREW 1.5 THICK ALUMINUM SHEET FOR
EXPOSED AREA
94 63 43 4 24 6 10
M24X240mm STAINLESS STEEL
INSIDE
OR
ADJUSTMENT BOLT TRANSOM ALUMINUM GLAZING 1.5MM THICK GI SHEET FOR NON
HEXAGONAL BOLT WITH NUT & EXPOSED AREA/ SLAB / SHEAR
WASHER ASSEMBLY Art.-No. 503184 M16 STAINLESS STEEL ADAPTOR (VU-259) WALL SHEET.
1 % F A L L
90
110 ACP2- 5mm THICK ALUMINIUM
22
COMPOSITE PANEL (RAL7043)
45
COMPOSITE PANEL (RAL7042)GRAY
235
150 SEALANT
140
280
#12 (∅5.5mm) X 19mm LENGTH
45
IFC DRAWING REF
STAINLESS STEEL PAN HEAD
138
FACADE MATERIAL:
SELF TAPPING SCREW
25
12- ALUMINUM CURTAIN WALL SYSTEM
21- ALUMINUM COMPOSITE PANEL
22- ALUMINUM LOUVRE SYSTEM
25- ALUMINUM PERFORATED SCREEN
280 WITH CUSTOM PATTERN
110 26- 50% PERFORATED ALUMINUM
SEPARATOR SHIMMING ALUMINUM ANGLE PANEL.
44 6 40
150
SIZE 40*40*4
ALUMINUM SERRATED WASHER 110
ACP1-ALUM COMPOSIDE PANEL
40
5mm THICK
50
40
6mm THICK ALUMINUM
BRACKET PLATE
85
∅5.5X50MM SELF TAPING
SCREW WITH PLASTIC ALUMINUM TUBE
PLUG SIZE 40*25*3
NO E
H
NORTH TRU
RT
ZONE 1-10
PROJECT
SCREW
MAKKAH
M8X25 STAINLESS STEEL
HEXAGONAL BOLT WITH
NUT & WASHER
1.5mm GI SHEET ASSEMBLY
SMOKE FLASHING
GI ANGLE
SIZE 100x60mm THICK 2mm
Rock Wool 100mm FIRE STOP SUPPORT Owner
Thickness
Kingdom of Saudi Arabia
/Density120/m³ ALUM TUBE STIFFENER Ministry of Interior
63
20X20MM THICK 2MM
1.5mm THICK ALUMINUM SHEET (EACH 800MM WHEREVER
POWDER COATING RAL7042 PANEL HAVE MORE 2M HEIGHT ) SECURITY FORCES MEDICAL CENTER PROJECT AT RIYADH AND JEDDAH
36 VERTICAL SECTION DETAIL GI SHEET Contractor: ABV Rock Group Co. Ltd.
Sub Consultant
MI-MM-A2-B01.00-01-A0-90-(030-040)-08-00-A
1:2 L04-L11
Drawing Title:
Drawing No.
MI MM A2 B01.02 A0 90 037 08 00 A
Project Orig. Package Building Discipline Type Sequence Phase Revision Issue Code