Created by Joseph Pascarella with Autodesk® Construction Cloud™ on Aug 10, 2023 at 10:59 AM EDT Page 1 of 3
238600 - KIPP Chart High School 75 Canal Street West #52-08 40 00-Curtain Wall - PMU Structural Calculations
Submitted
Jean Selibio
(Utopia Construction KIPP-75-13.1A-PMU
Corp. Of NY) Jul 10, 2023 Jul 16, 2023 Jul 31, 2023 Submitted Structural Calculation
Submitted by Joseph Rev. 1.pdf
Pascarella
Comments -
Joseph Pascarella
#52-08 40 00.01 Curtain
(Hunter Roberts
Jul 31, 2023 - Jul 31, 2023 Sent for review wall PMU Structural
Construction Group)
Calcs - R1.pdf
Sent by Joseph Pascarella
Comments -
Review Step 1
Rok Lee
(DeSimone Consulting Jul 31, 2023 Aug 9, 2023 -
Engineers)
Comments
Daniel Chung
(DeSimone Consulting Jul 31, 2023 Aug 9, 2023 -
Engineers)
Comments
Created by Joseph Pascarella with Autodesk® Construction Cloud™ on Aug 10, 2023 at 10:59 AM EDT Page 2 of 3
238600 - KIPP Chart High School 75 Canal Street West #52-08 40 00-Curtain Wall - PMU Structural Calculations
Cameron Madson
(DeSimone Consulting #52-08 40 00.01 Curtain
Engineers) Jul 31, 2023 Aug 9, 2023 Aug 10, 2023 Revise and resubmit wall PMU Structural
Reviewed By Cameron Calcs - R1_DCE.pdf
Madson
Comments
Review Step 2
Jesse Mallen
Aug 10, 2023 Aug 13, 2023 -
(Perkins Eastman)
Comments
Michael Messinger
Aug 10, 2023 Aug 13, 2023 -
(Perkins Eastman)
Comments
Lauren Giamundo
Aug 10, 2023 Aug 13, 2023 -
(Perkins Eastman)
Comments
Created by Joseph Pascarella with Autodesk® Construction Cloud™ on Aug 10, 2023 at 10:59 AM EDT Page 3 of 3
KIPP HS – 75 Canal St W
HRCG Project #238600
HRCG Submittal Stamp Sheet
By: jpascarella
HUNTER ROBERTS CONSTRUCTION GROUP
DDC Stamp
Architect/Engineer Stamp Consultant Stamp Stamp
Architect/Engineer
DeSimone General Comments:
DESIMONE
DDC Stamp
FACADES
Consultant Stamp
140 Broadway, 25th Floor
Revise and Resubmit:
New York, NY 10005 - Per responses to RFI 97 HSS
APPROVED
members are to be installed behind
curtain wall vision panels. Update PMU
APPROVED AS NOTED
shop drawings and calculations to
■ REVISE AND RESUBMIT
include required HSS members.
REJECTED AS NOTED
- Update wind load calculation using
NO ACTION REQUIRED
correct exposure category and building
NOT SUBJECT TO REVIEW
height.
BY Cameron.Madson DATE 8/10/2023 - Update calculation to use the zone 5
REVIEW QUALIFICATIONS:
positive and negative wind loads
Approval is for conformance with throughout.
information given and design concept
expressed in contract documents. Approval
does not authorize changes to contract
documents. Provide in resubmission for record:
Submittal review is limited as defined in the
Contract Documents, and the reviewers' - Sign and seal record submission.
responsibilities are defined in documents AIA
201 and EJCDC C-700.
Date: 07/24/2023
Design Mix Data Color Chart/Chip Sustainable Mtrl Info Test Reports
Submitted For:
Item Reference Page Location Description / Comments Comments By Response Response By Remarks Status
4 Page 1 Provide reference for structural sealant design strengths. Perkins Reference for Structural Sealant Design Strengths - ASTM C1249 now clearly referenced Peterson 1990
5 Page 3 2014 NYC BC references ASCE 7-05 Perkins ASCE 7-16 is clearely referenced and indicated in the Project Technical Specifications Peterson 1990
Per 2014 NYC BC, the design pressure for components and cladding of buildings shall not be
6 Page 3 Perkins ASCE 7-16 is clearely referenced and indicated in the Project Technical Specifications Peterson 1990
less than 20 psf acting in either direction normal to the surface.
Wind tunnel test report was wrong/Incorrect annotation, this is omitted as it should follow & comply
7 Page 4 Provide referenced wind tunnel test report. Perkins Peterson 1990
withASCE 7-16 maximum wind pressure calculated
Wind tunnel test report was wrong/Incorrect annotation, this is omitted as it should follow & comply
8 Page 6 Provide referenced wind tunnel test report. Perkins Peterson 1990
withASCE 7-16 maximum wind pressure calculated
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Specification wind pressure is more conservative than calculated wind pressure. Therefor use
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
9 Page 9 specification Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
wind pressure in calculations.
podium in compliance with ASCE 7-16 code.
Per NYC Building Code exposure category C is to be used because the building is within 2,600 ft of
Revised calculation is following ASCE 7-16 Code, Exposure B Category, refer to Technical response issued on
10 Page 9 the Perkins Peterson 1990
page 8 of 75
shoreline.
This is for the podium wind pressure caalculation hence podium level height is considered per this
11 Page 9 Wind load to be calculated using the total building height of 150' (45.72 m). Perkins Peterson 1990
calculation
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
12 Page 15 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Typical Zone 4 wind pressures are adapted since the PMU is based on and representative of Typical area of
13 Page 16 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. the façade, whereas the corner zone areas will have additional beams across
14 Page 17 Provide full STAAD analysis report to confirm inputs and outputs. Perkins STAAD Input is provided and added into the revised calculation Peterson 1990
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
15 Page 23 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
16 Page 24 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
17 Page 26 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
18 Page 27 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
19 Page 33 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
20 Page 34 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
21 Page 40 Perkins Peterson 1990
section. Use the zone 5 for both positive pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
22 Page 43 Perkins Peterson 1990
section. Use the zone 5 for both positive pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
23 Page 49 Perkins Peterson 1990
section. Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
24 Page 51 Update Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
25 Page 52 Update calculation using the zone 5 negative wind loads. Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
26 Page 53 Update Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Use is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
27 Page 54 Perkins Peterson 1990
the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
28 Page 56 Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
Update calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
29 Page 57 Update calculation using the zone 5 negative wind loads. Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
30 Page 58 Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
Update calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Use is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
31 Page 59 Perkins Peterson 1990
the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
HRCG: EOR/PEA to
review and advise as
applicable. TYP.
KIPP PROJECT
75 CANAL STREET WEST, BRONX NY, USA 10451
PERFORMANCE MOCK-UP REPORT
TITLE PAGE i
TABLE OF CONTENTS ii
__________________________________________________________________________________________
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
DESIGN INFORMATION
Page 1 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject PROJECT DESIGN INFORMATION
CN 0
1. INTRODUCTION
This report presents the analysis and design verification of panels, members and fixing of the PMU
(performance mock-up) of Unitized Curtainwall at Podium Area.
2. CODES OF PRACTICE
All design work shall comply with the appropriate current standards. Any other relevant codes of
practices shall be referenced as and when necessary. The following standards are used in the report.
3. MATERIAL PROPERTIES
ASTM C1249
Page 2 of 81
__________________________________________________________________________________________
Page 3 of 81
4. LOADS
4.1. DEAD LOADS
All elements are to support and transfer their own self-weight and other associated dead loads. The
following unit weights are considered in the analysis based on the materials.
Unit weight Wind loads calculated using ASCE 7-16 are larger
Material
Density ( lb/ft3 ) than those calculated using ASCE 7-05 as required
by 2014 NYC BC and are therefore accepted.
Glass Panel 160 However, the 2014 NYC BC requirement that the
design pressure for components and cladding of
buildings to be greater than 20 psf (0.96 KPa) acting
in either direction normal to the surface is still
4.2. WIND LOAD
applicable to wind loads calculated with ASCE 7-16.
Derived Zone (4) wind pressure for podium area, using ASCE 7-16 , are considered in this report.
__________________________________________________________________________________________
Page 4 of 81
4.3. SEISMIC LOAD
5. PERFORMANCE REQUIREMENTS
2. Deflection Parallel to Glazing Plane: Limited to 1/360 of clear span or 1/8 inch (3.2 mm), whichever is
smaller.
__________________________________________________________________________________________
Page 5 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
Page 6 of 81
HRCG: Consultant comments
below. EOR to Review and advise
as applicable.
Calc. by :
KIPP
BP
Chk. by :
PMU
YM
Rev. No. 0
TECHNICAL RESPONSE SHEET
Date: 2023-07-24
Page 1 : Revised and added the reference code: See reply in green marked up.
Page 7 of 81
HRCG: Consultant comments
below. EOR to Review and advise
as applicable.
Page 16 : PMU is located at podium typical areas, hence podium zone ( 4 ) wind pressures are adapted in the report. See reply in green marked up.
PMU to be constructed to
withstand zone 5 wind loads.
Update calculations using
zone 5 wind pressures.
Page 8 of 81
HRCG: Consultant comments
below. EOR to Review and advise
as applicable.
Page 17 : STAAD Input is provided and added in the report. See reply in green marked up.
Page 40 : PMU is located at podium typical areas, hence podium zone ( 4 ) wind pressures are adapted in the report. See reply in green marked up.
Page 51 : Revised and amended. Applied to all fixing checks of the same comment. See reply in green marked up.
Page 9 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
LOADING ANALYSIS
Page 10 of 81
Calc. by :
KIPP
BP
Chk. by :
SEISMIC LOAD - ASCE-07
YM
Rev. No. 0
PMU
Date: 2023-07-12
SEISMIC LOAD
SITE CLASS D "C" C III "D"
SEISMIC DESIGN CATEGORY "D" D IV B
PANEL DENSITY r= 25 KN / m3
WEIGHT OF COMPONENT Wp = 1g
SEISMIC LOAD
PANEL HORIZONTAL SEISMIC LOAD ; ( t * r ) * Fph + 10% accessories Vph = 0.25 KPa
PANEL VERTICAL SEISMIC LOAD ; ( t * r ) * Fpv + 10% accessories Vpv = 0.03 KPa
WIND LOAD ; See maximum ultimate wind load excerpt from project specification / see also wind load calculation Ww = 3.59 KPa
Page 11 of 81
Calc. by :
KIPP
BP
Chk. by :
MOVEMENT JOINT
YM
Rev. No. 0
PMU
Date: 2023-05-25
PARAMETERS
Mullion Length ( L ) Maximum panel height - drawing 6734 mm
TOLERANCES
Cutting tolerances (mm) E-mail confirmation 1.0 mm
INTERSTOREY DRIFT
(2) Lateral Movement ; L / 400 or 19mm ; project spec's 16.8 mm
Page 12 of 81
HORIZONTAL JOINT MOVEMENT - STACK JOINT DOWN UP
REQUIRED MINIMUM DESIGN MULLION JOINT MOVEMENT Sum Of - [ 1 + 10% of ( 2 + 3 ) + 5 ] 7.37 mm 8.76 mm
Page 13 of 81
Calc. by :
KIPP
BP
Chk. by :
WIND PRESSURE ( WALLS )
YM
Rev. No. 0
ASCE 07
Date: 2023-07-24
NYC Building
code overrules
ASCE 7-16
because it is the
local applicable
code. Therefore
exposure
category C is to
be used in wind
load calculation.
BUILDING PARAMETERS
DESIGN UNIT METRIC
RISK CATEGORY ; See Table 1.5-1 II
EXPOSURE CATEGORY ; Section 26.7 - surface roughness " B " B
ENCLOSURE CLASSIFICATION ; Section 26.13-1 ENCLOSED
BUILDING INTERNAL PRESSURE COEFFICIENT ; See Table 26.13 Gcpi ( +/- ) = 0.18
VELOCITY PRESSURE
NOMINAL HEIGHT OF ATMOSPHERIC BOUNDARY LAYER ; See Table 26.11 -1 zg = 366 m
-0.18 1.62
0.90 0.97 KPa 1.62 KPa
0.18 1.08
Zone ( 5 ) CORNER
-0.18 -2.43
-1.80 -1.78 KPa -2.97 KPa
0.18 -2.97
* NOTE: Verification of Members and fixings are based on Podium area typical zone ( 4 ) wind pressures.
Page 15 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
PANEL ANALYSIS
Page 16 of 81
Calc. by :
KIPP
BP
Chk. by :
VISION GLASS
YM
Rev. No. 0
PMU
Date: 2023-05-23
GLASS ANALYSIS
WIND LOAD SHARING ; Q * ( ti3 / ti3 + to3 ) Q= 1.37 KPa Q= 0.41 KPa
2 2
FACTORED STRESS ; ( β * QS * b ) / t j= 21.09 MPa j= 14.07 MPa
Note: Corner wind pressure ( zone 5 ) is adopted to verify our glass panel to ensure our glass composition can be used at all areas.
Page 17 of 81
Calc. by :
KIPP
BP
Chk. by :
SPANDREL GLASS
YM
Rev. No. 0
PMU
Date: 2023-05-23
GLASS ANALYSIS
WIND LOAD SHARING ; Q * ( ti3 / ti3 + to3 ) Q= 1.37 KPa Q= 0.41 KPa
2 2
FACTORED STRESS ; ( β * QS * b ) / t j= 7.08 MPa j= 4.73 MPa
Note: Corner wind pressure ( zone 5 ) is adopted to verify our glass panel to ensure our glass composition can be used at all areas.
Page 18 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
MEMBER ANALYSIS
Page 19 of 81
Calc. by :
KIPP
BP
Chk. by :
UNITIZED MULLION
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETERS :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 20 of 81
MAJOR AXIS MOMENT OF INERTIA Ixm = 3632000 mm4 Ixf = 2888000 mm4 Ix = 6520000 mm4
3 3
MAJOR AXIS PLASTIC MODULUS Zxm = 69900 mm Zxf = 53800 mm Zx = 123700 mm3
MAJOR AXIS ELASTIC MODULUS ( external ) Sxem = 53300 mm3 Sxef = 39200 mm3 Sxe = 92500 mm3
MAJOR AXIS ELASTIC MODULUS ( internal ) Sxim = 41600 mm3 Sxif = 36900 mm3 Sxi = 78500 mm3
MAJOR AXIS RADIUS OF GYRATION rxm = 56 mm rxf = 52 mm rx = 108 mm
MINOR AXIS MOMENT OF INERTIA Iym = 376000 mm4 Iyf = 176000 mm4 Iy = 552000 mm4
MINOR AXIS PLASTIC MODULUS Zym = 22800 mm3 Zyf = 12500 mm3 Zy = 35300 mm3
3 3
MINOR AXIS ELASTIC MODULUS ( external ) Syem = 19200 mm Syef = 8700 mm Sye = 27900 mm3
MINOR AXIS ELASTIC MODULUS ( internal ) Syim = 10500 mm3 Syif = 5460 mm3 Syi = 15960 mm3
MINOR AXIS RADIUS OF GYRATION rym = 18 mm ryf = 13 mm ry = 31 mm
RATIO OF SECTION PROPERTIES MALE RATIO FEMALE RATIO TOTAL SECTION PROPERTY
MAJOR AXIS INERTIA RATIO RIxm = 0.56 Ixm / Ixt RIxf = 0.44 Ixf / Ixt Ixt = 6520000 mm4
MINOR AXIS INERTIA RATIO RIym = 0.68 Iym / Iyt RIyf = 0.32 Iyf / Iyt Iyt = 552000 mm4
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
PMU to be constructed to
TOTAL THICKNESS OF PANEL withstand zone 5 wind loads. t= 20 mm
PANEL DENSITY
zone 5 wind pressures. rg = 25 KN / m3
Page 21 of 81
APPLIED BENDING STRESSES POSSITIVE WL NEGATIVE WL
STRONG AXIS MOMENT ; SEE STAAD RESULT Mx+ = 6.30 KN-m Mx- = 4.10 KN-m
POSSITIVE WL BENDING STRESS ; Mx+ * RIx / Sxe Fbxm ' = 65.84 Mpa Fbxf' = 46.33 Mpa
NEGATIVE WL BENDING STRESS ; Mx- * RIx / Sxi Fbxm ' = 54.90 Mpa Fbxf' = 49.22 Mpa
Page 22 of 81
YIELDING ( l > l1 ) ; Fcy Fc1 = 170.00 Mpa Fc1 = 170.00 Mpa
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fc2 = 153.11 Mpa Fc2 = 153.11 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fc3 = 171.66 Mpa Fc3 = 171.66 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fc1 / W Fcm = 92.79 Mpa Fcm = 92.79 Mpa
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fc2 = 142.77 Mpa Fc2 = 162.76 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fc3 = 146.48 Mpa Fc3 = 204.49 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fc1 / W Fcf = 86.53 Mpa Fcf = 98.64 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 229.33 Mpa Fb2 = 229.33 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 325.18 Mpa Fb3 = 325.18 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 197.08 Mpa Fbm = 197.08 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 229.62 Mpa Fb2 = 229.62 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 326.30 Mpa Fb3 = 326.30 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbf = 197.76 Mpa Fbf = 197.76 Mpa
Page 23 of 81
LATERAL TORSIONAL BUCKLING STRESS - F.4.2.5
NOMINAL BENDING COEFFICIENT ; ( 12.5 Mmax ) / ( 2.5Mmax + 3MA + 4MB + 3MC ) - F.1.1.1 Cbn = 1.25
DISTANCE OF FLANGE CENTROID FROM SECTION CENTROID cfem = 28.78 mm cfef = 3.85 mm
EXTERNAL BENDING COEFFICIENT; IF - 0.10 < RIye < 0.9 = Cbn ; Others = 1 Cbem = 1.25 Cbef = 1.00
DISTANCE OF FLANGE CENTROID FROM SECTION CENTROID cfim = 28.78 mm cfif = 5.35 mm
INTERNAL BENDING COEFFICIENT ; IF - 0.10 < RIye < 0.9 = Cbn ; Others = 1 Cbim = 1.25 Cbif = 1.00
DISTANCE OF SHEAR CENTER TO POINT OF LOAD ( External Flange ) goe = 109.32 mm goe = 97.57 mm
DISTANCE OF SHEAR CENTER TO POINT OF LOAD ( Internal Flange ) goi = 85.12 mm goi = 96.87 mm
EXTERNAL CRITICAL MOMENT PARAMETER ; C1 * go+ - C2 * βce / 2 Uem = 87.72 Uef = 91.44
NOMINAL FLEXURAL STRENGTH FOR YIELDING ; Min ( Zx * Fcy ) , ( 1.5 Sxe * Fcy ) Mnpm = 11.88 KN-M Mnpf = 9.15 KN-M
2 2 2 2
TORSIONAL BUCKLING ; ( Cb * π * E * Iy / Lb )[U + U + 0.038*J*Lb / Iy + Cw/Iy ] Mem = 66.23 KN-M Mef = 14.37 KN-M
LTB BUCKLING STRENGTH ; IF l < Cc = Mnmb1 / W, l > Cc = Mnmb2 / W Mmbem = 6.12 Mpa Mmbef = 3.94 Mpa
ALLOWABLE LTB STRESS ; Mmbe / Sxe Fbem = 114.77 Mpa Fbef = 100.50 Mpa
Page 24 of 81
INTERNAL FLANGE ALLOWABLE LTB STRESS MALE MULLION FEMALE MULLION
2
INTERNAL COEFFICIENT OF MONOSYMMETRY ; 0.9df * [( 2Iyi/Iy )-1][1-( Iy/Ix ) ] βcim = -132.23 βcif = -165.14
INTERNAL CRITICAL MOMENT PARAMETER ; C1 * go- - C2 * βci / 2 Uim = 75.62 Uif = 89.72
NOMINAL FLEXURAL STRENGTH FOR YIELDING ; Min ( Zx * Fcy ) , ( 1.5 Sxi * Fcy ) Mnpm = 10.61 KN-M Mnpf = 9.15 KN-M
TORSIONAL BUCKLING ; ( Cb * π2 * E * Iy / Lb2 )[U + U2 + 0.038*J*Lb2 / Iy + Cw/Iy ] Mem = 64.09 KN-M Mef = 14.17 KN-M
LTB BUCKLING STRENGTH ; IF l < Cc = Mnmb1 / W, l > Cc = Mnmb2 / Wb Mmbim = 5.45 Mpa Mmbif = 3.89 Mpa
ALLOWABLE LTB STRESS ; Mmbi / Sxi Fbim = 131.08 Mpa Fbif = 105.53 Mpa
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
MINOR AXIS MOMENT OF INERTIA Iy = 376000 mm4 376000 mm4 176000 mm4 176000 mm4
TORSION CONTANT J= 556000 mm4 556000 mm4 6990 mm4 6990 mm4
BUCKLING CONSTANT INTERSECTION Cc = 79.16 Mpa 79.16 Mpa 79.16 Mpa 79.16 Mpa
NOMINAL FLEXURAL STRENGTH Mnmb = 10.09 KN-M 9.00 KN-M 6.50 KN-M 6.42 KN-M
ALLOWABLE LTB STRENGTH Mmb = 6.12 KN-M 5.45 KN-M 3.94 KN-M 3.89 KN-M
ALLOWABLE LTB STRENGTH STRESS Fb = 114.77 MPa 131.08 MPa 100.50 MPa 105.53 MPa
Page 25 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.1 ( FLANGES - UNSUPPORTED ELEMENT )
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
BUCKLING CONSTANT INTERCEPT Bp = 213.24 Mpa 213.24 Mpa 213.24 Mpa 213.24 Mpa
BUCKLING CONSTANT SLOPE Dp = 1.18 Mpa 1.18 Mpa 1.18 Mpa 1.18 Mpa
BUCKLING CONSTANT INTERSECTION Cp = 74.28 Mpa 74.28 Mpa 74.28 Mpa 74.28 Mpa
NOMINAL COMPRESSIVE STRENGTH Fc1 = 153.11 MPa 153.11 MPa 142.77 MPa 162.76 MPa
ALLOWABLE COMPRESSIVE STRESS Fc = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
BUCKLING CONSTANT INTERCEPT Bbr = 313.19 Mpa 313.19 Mpa 313.19 Mpa 313.19 Mpa
BUCKLING CONSTANT SLOPE Dbr = 2.57 Mpa 2.57 Mpa 2.57 Mpa 2.57 Mpa
BUCKLING CONSTANT INTERSECTION Cbr = 81.38 Mpa 81.38 Mpa 81.38 Mpa 81.38 Mpa
NOMINAL BUCKLING STRENGTH Fb1 = 325.18 MPa 325.18 MPa 326.30 MPa 326.30 MPa
ALLOWABLE BUCKLING STRESS Fb = 197.08 MPa 197.08 MPa 197.76 MPa 197.76 MPa
COMPRESSIVE STRESS - B.5.4.1 Fc = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
LOCAL BUCKLING - B.5.5.1 Fb = 197.08 MPa 197.08 MPa 197.76 MPa 197.76 MPa
LATERAL TORSIONAL BUCKLING - F.4.2.5 Fb = 114.77 MPa 131.08 MPa 100.50 MPa 105.53 MPa
APPLIED STRESS Fb' = 65.84 MPa 54.90 MPa 46.33 MPa 49.22 MPa
GOVERNING ALLOWABLE STRESS Fb = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
RESULT OK OK OK OK
Page 26 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 25.90 mm
Page 27 of 81
Calc. by :
KIPP
BP
Chk. by :
MID - DUMMY MULLION
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETERS :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 28 of 81
SECTION PROPERTIES -SECTION WIZARD
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
PANEL DENSITY rg = 25 KN / m3
Page 29 of 81
INTERNAL ELEMENT UNDER UNIFORM COMPRESSION - WEB - ( B.5.4.2 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 1.6 * Dp * l Fbxen2 = 195.49 Mpa Fbxin2 = 163.12 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 1.6 * l Fbxen3 = 581.52 Mpa Fbxin3 = 205.93 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 103.03 Mpa Fbxi = 98.86 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 264.70 Mpa Fb2 = 264.70 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 562.39 Mpa Fb3 = 562.39 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 340.84 Mpa Fbm = 340.84 Mpa
Page 30 of 81
SUMMARY OF LOCAL BUCKLING STRESS - B.5.5.1 ( WEB - SUPPORTED ELEMENT )
RESULT OK OK
WL DEFLECTION dx = 15.88 mm
Page 31 of 81
Calc. by :
KIPP
BP
Chk. by :
STACK JOINT TRANSOM
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETER :
MECHANICAL PROPERTIES :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
MEMBER BUCKLING
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 32 of 81
SECTION PROPERTIES -SECTION WIZARD HEAD TRANSOM SILL TRANSOM
RATIO OF SECTION HEAD TRANSOM RATIO SILL TRANSOM RATIO TOTAL SECTION PROPERTY
MAJOR AXIS NERTIA RATIO R1 = 0.53 Ix1 / IxT R2 = 0.47 Ix2 / IxT IxT = 9439375 mm4
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
SB POINT LOAD AT SILL TRANSOM ; 1.25 * t * r * da * Lm / 2 - With 25% Accesories Py= 0.40 KN
TOTAL WL MOMENT ; Mxa + Mxb Mx+ = 0.31 KN-m Mx- = -0.21 KN-m
HEAD WL BENDING STRESS ; Mx+ R / Sx Fbxf' = 2.79 Mpa Fbxf' = -1.78 Mpa
SILL WL BENDING STRESS ; Mx+ R / Sx Fbxf' = 3.22 Mpa Fbxf' = -1.60 Mpa
Page 33 of 81
SECTION ELEMENT OF FLANGES
OUTSTAND ELEMENT UNDER UNIFORM COMPRESSION - FLANGE - ( B.5.4.1 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fbxen2 = 141.46 Mpa Fbxin2 = 123.14 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fbxen3 = 143.80 Mpa Fbxin3 = 114.56 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 85.73 Mpa Fbxi = 69.43 Mpa
Page 34 of 81
SLENDERNESS OF ELEMENT ;d/t le = 26.26 li = 26.26
LOWER SLENDERNES LIMIT ; ( Bbr -1.5 Fcy ) / ( m*Dbr ) le1 = 14.08 li1 = 14.08
YIELDING ( l > l1 ) ; 1.5 * Fcy Fbxen1 = 255.00 Mpa Fbxin1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr * l ] Fbxen2 = 204.66 Mpa Fbxin2 = 204.66 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * l ] Fbxen3 = 604.15 Mpa Fbxin3 = 604.15 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 124.04 Mpa Fbxi = 124.04 Mpa
LOWER SLENDERNES LIMIT ; ( Bbr -1.5 Fcy ) / ( m*Dbr ) le1 = 14.96 li1 = 14.96
YIELDING ( l > l1 ) ; 1.5 * Fcy Fbxen1 = 255.00 Mpa Fbxin1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr * l ] Fbxen2 = 150.32 Mpa Fbxin2 = 150.32 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * l ] Fbxen3 = 378.90 Mpa Fbxin3 = 378.90 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 229.64 Mpa Fbxi = 229.64 Mpa
WL DISPLACEMENT ABOVE ; (PWLsxa L4)/(1920 E IxT )*(25 - 40(aa/L)2 + 16(aa/L)4) dxa = 0.06 mm
4
WL DISPLACEMENT BELOW ; (PWLsxb L )/(1920 E IxT )*(25 - 40(ab/L)2 + 16(ab/L)4) dxb = 0.09 mm
Page 35 of 81
DESIGN OF MEMBER FOR FLEXURE
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.44 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.44 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.40 KN-M
APPLIED LOADS
Page 36 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.1 ( FLANGES - OUTSTAND ELEMENT )
RESULT OK OK
Page 37 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 0.15 mm
DL DEFLECTION dy = 0.60 mm
Page 38 of 81
Calc. by :
KIPP
BP
Chk. by :
INTERMEDIATE TRANSOM
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETER :
BUCKLING CONSTANTS
MEMBER BUCKLING
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 39 of 81
SECTION PROPERTIES -SECTION WIZARD
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
SB POINT LOAD AT SILL TRANSOM ; 1.25 * t * r * da * Lm / 2 - With 25% Accesories Py= 2.04 KN
Page 40 of 81
TOTAL WL MOMENT ; Mxa + Mxb Mx+ = 0.41 KN-m Mx- = -0.28 KN-m
INTERNAL ELEMENT UNDER UNIFORM COMPRESSION - WEB - ( B.5.4.2 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 1.6 * Dp * l Fbxen2 = 195.49 Mpa Fbxin2 = 163.12 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 1.6 * l Fbxen3 = 581.52 Mpa Fbxin3 = 205.93 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 103.03 Mpa Fbxi = 98.86 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 197.13 Mpa Fb2 = 197.13 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 562.39 Mpa Fb3 = 562.39 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 340.84 Mpa Fbm = 340.84 Mpa
Page 41 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.2 ( WEB - SUPPORTED ELEMENT )
RESULT OK OK
Page 42 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 0.18 mm
DL DEFLECTION dy = 1.25 mm
Page 43 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
FIXING ANALYSIS
Page 44 of 81
CHECK FOR ALUMINUM PRESSURE PLATE
+ / - Fz
SECTION PROPERTIES
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 84.00 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = -62.61 KN-M
Page 45 of 81
STRONG AXIS YIELDING AND RUPTURE
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 1.44 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.16 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.16 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.16 KN-M
PMU to be constructed to
APPLIED LOADS
withstand zone 5 wind loads. POSSITIVE WL NEGATIVE WL
Update calculations using
TYPICAL ZONE SERVICE WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
zone 5 wind pressures.
SPACING OF SCREW L= 1000 mm L= 1000 mm
Page 46 of 81
CHECK FOR ALUMINUM GLASS CHAIR Fy
22.3m
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
SECTION PROPERTIES
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 5.51 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = -1.64 KN-M
Page 47 of 81
STRONG AXIS YIELDING AND RUPTURE
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.21 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.06 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.06 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.05 KN-M
Page 48 of 81
CHECK FOR ALUMINUM HOOK BRACKET PLATE
Fy
+ / - Fz
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
PMU to be constructed to
APPLIED LOADS withstand zone 5 wind loads. POSSITIVE WL NEGATIVE WL
Update calculations using
TYPICAL ZONE SERVICE WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
zone 5 wind pressures.
MULLION LENGTH L= 6733.5 mm L= 6733.5 mm
CHECK SECTION 1
SECTION PROPERTIES
Page 49 of 81
STRONG AXIS ELASTIC MODULUS ; t * b2 / 6 Sx = 621 mm3
2
WEAK AXIS ELASTIC MODULUS ;b*t /6 Sy = 322 mm3
-1
WEAK AXIS RADIUS OF GYRATION ; Iy * A ry = 1.45 mm
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 0.22 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = 0.12 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 0.85 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.12 KN-M
Page 50 of 81
WEAK AXIS YIELDING AND RUPTURE
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.07 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.07 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.06 KN-M
TENSION LOADS
SHEAR LOAD
Page 51 of 81
CHECK SECTION 2
Fy
+/- Fz
SECTION PROPERTIES
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
TENSION COEFFICIENT kt = 1
Page 52 of 81
LATERAL TORSIONAL BUCKLING
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 0.60 KN-M
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π2 * E * lb * Sx ) / ( Cc3 * Wby ) Mnpx1 = 0.33 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 4.50 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.33 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.23 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.23 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.21 KN-M
APPLIED LOADS
TENSION LOADS
SHEAR LOAD
Page 53 of 81
CHECK FOR ALUMINUM FLOOR BRACKET
Fy
+/- Fz
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
SECTION PROPERTIES
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
Page 54 of 81
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 50.17 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = 20.70 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 41.17 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 20.70 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 2.13 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 2.13 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 1.95 KN-M
PMU to be constructed to
APPLIED LOADS withstand zone 5 wind loads. POSSITIVE WL NEGATIVE WL
TYPICAL ZONE SERVICE WIND PRESSURE Update calculations using Q= 0.97 kPa Q= -0.65 kPa
zone 5 wind pressures.
MULLION LENGTH L= 6733.5 mm L= 6733.5 mm
Page 55 of 81
HORIZONTAL FORCE DUE TO POSITIVE WL Fz+ = 11.46 KN
TENSION LOADS
SHEAR LOAD
DIRECT SHEAR
Page 56 of 81
CHECK #12 SS A4-70 PRESSURE PLATE SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.18 inch 4.60 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.19 inch 4.70 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.21 inch 5.28 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.19 inch 4.90 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.01 inch2 14.96 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.02 inch 2
22.79 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 57 of 81
ALLOWABLE SHEAR STRESS ; 0.75 Fy /3 ; ( with 1.33 safety factor ) Fv1 = 47.63 Mpa
ALLOWABLE SHEAR STRESS ; 0.4 Fu / ; ( with 2.5 safety factor ) Fv1 = 36.95 Mpa
ALLOWABLE SHEAR STRESS ; Fy /3 ; ( with out safety factor ) Fv = 63.51 Mpa
PMU to be constructed to
APPLIED LOAD withstand zone 5 wind loads.
TYPICAL ZONE SERVICE WIND PRESSURE Update calculations using Pux = 0.97 Kpa
TENSILE LOAD
Page 58 of 81
ANALYSIS OF BRACKETRY FIXINGS
CHECK M12 STAINLESS STEEL BOLT MULLION FASTENER
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.43 inch 11.02 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.44 inch 11.28 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.49 inch 12.40 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.46 inch 11.61 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.06 inch2 38.91 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.11 inch2 68.88 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 59 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION SLIDE BRACKET
PMU to be constructed to
APPLIED LOADS withstand zone 5 wind loads. POSSITIVE WL NEGATIVE WL
SHEAR LOAD
ECCENTRICITY OF DL x= 44 mm
Page 60 of 81
SHEAR REACTION / BOLT ; Fy / n Vy = 3.8 KN
BEARING
Page 61 of 81
CHECK 1/4 SS A4-70 STACK JOINT HEAD TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 62 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
PMU to be constructed to
APPLIED SHEAR LOAD AT HEAD TRANSOM withstand zone 5 wind loads.
TYPICAL ZONE SERVICE WIND PRESSURE
Update calculations using Pux = 0.97 Kpa
zone 5 wind pressures.
TRIBUTARY LOADED WIDTH tw = 1755 mm
WL ECCENTRICITY ex = 50 mm
BEARING
Page 63 of 81
CHECK 1/4 SS A4-70 STACK JOINT SILL TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 64 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL SHEAR ; ww * H / 2 * n Vw = 0.30 KN
GLASS DENSITY r= 25 KN / m3
NUMBER OF SB n= 2 nos
WL ECCENTRICITY ex = 11 mm
DL ECCENTRICITY ey = 82 mm
Page 65 of 81
BEARING
Page 66 of 81
CHECK 1/4 SS A4-70 INTERMEDIATE TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 67 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
PMU to be constructed to
APPLIED SHEAR LOAD AT INTERMEDIATE TRANSOM withstand zone 5 wind loads.
Update calculations using Pux =
TYPICAL ZONE SERVICE WIND PRESSURE 0.97 Kpa
zone 5 wind pressures.
TRIBUTARY LOADED HEIGHT ; 3627 + 705 tw = 4332 mm
WL SHEAR ; ww * H / 2 * n Vw = 1.84 KN
GLASS DENSITY r= 25 KN / m3
NUMBER OF SB n= 2 nos
DL ECCENTRICITY ey = 82 mm
Page 68 of 81
BEARING
Page 69 of 81
CHECK M16 STAINLESS STEE LHEX BOLT SOCKET COUNTERSUNK HEAD
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.55 inch 13.87 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.56 inch 14.20 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.61 inch 15.52 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.57 inch 14.55 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.09 inch2 50.87 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.16 inch 2
94.10 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 70 of 81
ALLOWABLE TENSILE AND SHEAR LOADS OF FASTENER
Page 71 of 81
PMU to be constructed to
withstand zone 5 wind loads.
Update calculations using
zone 5 wind pressures.
APPLIED LOADS POSSITIVE WL NEGATIVE WL
WL ECCENTRICITY ex = 42 mm
SHEAR LOAD
TENSILE LOAD
BEARING
Page 72 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
SECTION PROPERTIES
Page 73 of 81
z
y MALE MULLION
v u
Geometric properties of the cross-section
A Sectional area
Parameter Value
1.43e+3 mm^2
Av,y Conventional shearing area along Y-axis 3.03e+2 mm^2
Av,z Conventional shearing area along Z-axis 5.45e+2 mm^2
Angle between Y-Z and U-V axes 0.542 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 4.54e+6 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 4.7e+5 mm^4
It Torsional moment of inertia (St. Venant) 5.56e+5 mm^4
Iw Warping constant 1.01e+9 mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 5.64e+1 mm
iz Radius of gyration about axis parallel to Z passing through centroid 1.81e+1 mm
Wu+ Elastic modulus about U-axis (+ve extreme) 5.33e+4 mm^3
Wu- Elastic modulus about U-axis (-ve extreme) 4.16e+4 mm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 1.92e+4 mm^3
Wv- Elastic modulus about V-axis (-ve extreme) 1.05e+4 mm^3
Wpl,u Plastic modulus about axis parallel to U-axis 6.99e+4 mm^3
Wpl,v Plastic modulus about axis parallel to V-axis 2.28e+4 mm^3
Iu Moment of inertia about U-axis 4.54e+6 mm^4
Iv Moment of inertia about V-axis 4.7e+5 mm^4
iu Radius of gyration about U-axis 5.64e+1 mm
iv Radius of gyration about V-axis 1.81e+1 mm
au+ Centroid to edge of compression zone along +ve U-axis 1.35e+1 mm
au- Centroid to edge of compression zone along -ve U-axis 7.39 mm
av+ Centroid to edge of compression zone along +ve V-axis 3.73e+1 mm
av- Centroid to edge of compression zone along -ve V-axis 2.92e+1 mm
yM Distance to centroid along Y-axis -4.78e+1 mm
zM Distance to centroid along Z-axis -1.19e+2 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis -2.49e+1 mm
Zb Distance to shear centre along Z-axis -9.14e+1 mm
P Perimeter 9.2e+2 mm
Pi Internal perimeter 2.49e+2 mm
Pe External perimeter 6.7e+2 mm
I1 Moment of inertia about Y-axis 4.54e+6 mm^4
I2 Moment of inertia about Z-axis 4.7e+5 mm^4
I12 Product of inertia about the centroid -3.85e+4 mm^4
Ip Polar moment of inertia about centroid 5.01e+6 mm^4
ip Polar radius of gyration about centroid 5.93e+1 mm
Wp Polar elastic modulus about centroid 4.57e+4 mm^3
yp Distance to equal area axis along Y-axis -5.13 mm
zp Distance to equal area axis along Z-axis -1.07e+1 mm
up Distance to equal area axis along U-axis -5.27 mm
vp Distance to equal area axis along V-axis 8.66e-1 mm
Page 74 of 81
z
y FEMALE MULLION
vu
Geometric properties of the cross-section
A Sectional area
Parameter Value
1.08e+3 mm^2
Av,y Conventional shearing area along Y-axis 2.09e+2 mm^2
Av,z Conventional shearing area along Z-axis 4.13e+2 mm^2
Angle between Y-Z and U-V axes 5.748 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 3.61e+6 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 2.2e+5 mm^4
It Torsional moment of inertia (St. Venant) 6.99e+3 mm^4
Iw Warping constant 4.94e+8 mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 5.77e+1 mm
iz Radius of gyration about axis parallel to Z passing through centroid 1.42e+1 mm
Wu+ Elastic modulus about U-axis (+ve extreme) 3.72e+4 mm^3
Wu- Elastic modulus about U-axis (-ve extreme) 3.69e+4 mm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 8.7e+3 mm^3
Wv- Elastic modulus about V-axis (-ve extreme) 5.46e+3 mm^3
Wpl,u Plastic modulus about axis parallel to U-axis 5.38e+4 mm^3
Wpl,v Plastic modulus about axis parallel to V-axis 1.25e+4 mm^3
Iu Moment of inertia about U-axis 3.65e+6 mm^4
Iv Moment of inertia about V-axis 1.85e+5 mm^4
iu Radius of gyration about U-axis 5.8e+1 mm
iv Radius of gyration about V-axis 1.31e+1 mm
au+ Centroid to edge of compression zone along +ve U-axis 8.03 mm
au- Centroid to edge of compression zone along -ve U-axis 5.04 mm
av+ Centroid to edge of compression zone along +ve V-axis 3.43e+1 mm
av- Centroid to edge of compression zone along -ve V-axis 3.41e+1 mm
yM Distance to centroid along Y-axis -1.85e+1 mm
zM Distance to centroid along Z-axis -1.07e+2 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis -4.73e+1 mm
Zb Distance to shear centre along Z-axis -9.05e+1 mm
P Perimeter 6.85e+2 mm
Pi Internal perimeter 0 mm
Pe External perimeter 6.85e+2 mm
I1 Moment of inertia about Y-axis 3.61e+6 mm^4
I2 Moment of inertia about Z-axis 2.2e+5 mm^4
I12 Product of inertia about the centroid -3.45e+5 mm^4
Ip Polar moment of inertia about centroid 3.83e+6 mm^4
ip Polar radius of gyration about centroid 5.95e+1 mm
Wp Polar elastic modulus about centroid 3.84e+4 mm^3
yp Distance to equal area axis along Y-axis -2.21 mm
zp Distance to equal area axis along Z-axis -5.43 mm
up Distance to equal area axis along U-axis -1.09 mm
vp Distance to equal area axis along V-axis -4.03 mm
Page 75 of 81
z
y DUMMY MULLION / INTERMEDIATE
TRANSOM
Geometric properties of the cross-section
Parameter Value
A Cross sectional area 1682.15 mm^2
Av,y Conventional shearing area along Y-axis 422.46 mm^2
Av,z Conventional shearing area along Z-axis 699.29 mm^2
Angle between Y-Z and U-V axes -0.003 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 5126299.54 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 2354988.96 mm^4
It Torsional moment of inertia (St. Venant) 4433686.19 mm^4
Iw Warping constant 317782308.3mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 55.2 mm
iz Radius of gyration about axis parallel to Z passing through centroid 37.42 mm
Wu+ Max elastic modulus about U-axis 66493.88 mm^3
Wu- Min elastic modulus about U-axis 70630.14 mm^3
Wv+ Max elastic modulus about V-axis 51903.03 mm^3
Wv- Min elastic modulus about V-axis 51905.23 mm^3
Wpl,u Plastic modulus about U-axis 84677.18 mm^3
Wpl,v Plastic modulus about V-axis 58934.7 mm^3
Iu Moment of inertia about U-axis 5126299.55 mm^4
Iv Moment of inertia about V-axis 2354988.95 mm^4
iu Radius of gyration about U-axis 55.2 mm
iv Radius of gyration about V-axis 37.42 mm
au+ Centroid to edge of compression zone along +ve U-axis 30.86 mm
au- Centroid to edge of compression zone along -ve U-axis 30.86 mm
av+ Centroid to edge of compression zone along +ve V-axis 39.53 mm
av- Centroid to edge of compression zone along -ve V-axis 41.99 mm
yM Distance to centroid along Y-axis 0 mm
zM Distance to centroid along Z-axis 0.01 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis 0.01 mm
Zb Distance to shear centre along Z-axis 2.53 mm
P Perimeter 1088.3 mm
Pi Internal perimeter 540.43 mm
Pe External perimeter 547.88 mm
I1 Moment of inertia about Y-axis 5126299.63 mm^4
I2 Moment of inertia about Z-axis 2354988.97 mm^4
I12 Product of inertia about the centroid 147.02 mm^4
Ip Polar moment of inertia about centroid 7481288.5 mm^4
ip Polar radius of gyration about centroid 66.69 mm
Wp Polar elastic modulus about centroid 0.93 mm
Page 76 of 81
z
Page 77 of 81
z
Page 78 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
Page 79 of 81
Job Title:
Client:
Engineer:
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 20-Apr-23
END JOB INFORMATION
INPUT WIDTH 79
UNIT MMS NEWTON
JOINT COORDINATES
1 25000 0 0; 2 25000 720 0; 4 25000 5270 0; 5 25000 6005 0; 6 25000 6250 0;
7 25000 12983.5 0; 10 25000 12015 0; 11 25000 12748.5 0;
MEMBER INCIDENCES
1 1 2; 3 2 4; 4 4 5; 5 5 6; 6 6 10; 9 10 11; 10 11 7;
DEFINE MATERIAL START
ISOTROPIC ALUMINUM
E 68947.6
POISSON 0.33
DENSITY 2.66018e-05
ALPHA 2.3e-05
DAMP 0.03
ISOTROPIC STEEL
E 205000
POISSON 0.3
DENSITY 7.68195e-05
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH RY 1.5 RT 1.2
ISOTROPIC STEEL_275_NMM2
E 205000
POISSON 0.3
DENSITY 7.7e-05
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH FY 275 FU 410 RY 1.5 RT 1.2
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
1 3 TO 6 9 10 PRIS AX 2510 IX 562990 IY 552000 IZ 6.52e+06
CONSTANTS
BETA 90 ALL
MATERIAL ALUMINUM ALL
SUPPORTS
5 11 FIXED BUT MX MZ
1 4 10 FIXED BUT FY MX MZ
MEMBER RELEASE
6 START FX MY MZ
LOAD 1 LOADTYPE Dead TITLE DL
MEMBER LOAD
Page 80 of 81
Job Title:
Client:
Engineer:
1 3 TO 6 9 10 UNI GY -1.16
SELFWEIGHT Y -1
LOAD 2 LOADTYPE Wind TITLE WL - SERVICE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y 1.1
LOAD 3 LOADTYPE Wind TITLE WL +SERVICE
MEMBER LOAD
1 3 TO 6 9 10 UNI GZ -1.7
LOAD 4 LOADTYPE Wind TITLE WL - ULTIIMATE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y 1.9
LOAD 5 LOADTYPE Wind TITLE WL + ULTIMATE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y -2.8
PERFORM ANALYSIS
FINISH
Page 81 of 81
Submittal Cover Sheet NO KIPP75_013.1A
Date: 07/24/2023
Design Mix Data Color Chart/Chip Sustainable Mtrl Info Test Reports
Submitted For:
Item Reference Page Location Description / Comments Comments By Response Response By Remarks Status
4 Page 1 Provide reference for structural sealant design strengths. Perkins Reference for Structural Sealant Design Strengths - ASTM C1249 now clearly referenced Peterson 1990
5 Page 3 2014 NYC BC references ASCE 7-05 Perkins ASCE 7-16 is clearely referenced and indicated in the Project Technical Specifications Peterson 1990
Per 2014 NYC BC, the design pressure for components and cladding of buildings shall not be
6 Page 3 Perkins ASCE 7-16 is clearely referenced and indicated in the Project Technical Specifications Peterson 1990
less than 20 psf acting in either direction normal to the surface.
Wind tunnel test report was wrong/Incorrect annotation, this is omitted as it should follow & comply
7 Page 4 Provide referenced wind tunnel test report. Perkins Peterson 1990
withASCE 7-16 maximum wind pressure calculated
Wind tunnel test report was wrong/Incorrect annotation, this is omitted as it should follow & comply
8 Page 6 Provide referenced wind tunnel test report. Perkins Peterson 1990
withASCE 7-16 maximum wind pressure calculated
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Specification wind pressure is more conservative than calculated wind pressure. Therefor use
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
9 Page 9 specification Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
wind pressure in calculations.
podium in compliance with ASCE 7-16 code.
Per NYC Building Code exposure category C is to be used because the building is within 2,600 ft of
Revised calculation is following ASCE 7-16 Code, Exposure B Category, refer to Technical response issued on
10 Page 9 the Perkins Peterson 1990
page 8 of 75
shoreline.
This is for the podium wind pressure caalculation hence podium level height is considered per this
11 Page 9 Wind load to be calculated using the total building height of 150' (45.72 m). Perkins Peterson 1990
calculation
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
12 Page 15 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Typical Zone 4 wind pressures are adapted since the PMU is based on and representative of Typical area of
13 Page 16 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. the façade, whereas the corner zone areas will have additional beams across
14 Page 17 Provide full STAAD analysis report to confirm inputs and outputs. Perkins STAAD Input is provided and added into the revised calculation Peterson 1990
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
15 Page 23 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
16 Page 24 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
17 Page 26 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
18 Page 27 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
19 Page 33 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
20 Page 34 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
21 Page 40 Perkins Peterson 1990
section. Use the zone 5 for both positive pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
22 Page 43 Perkins Peterson 1990
section. Use the zone 5 for both positive pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
23 Page 49 Perkins Peterson 1990
section. Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
24 Page 51 Update Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
25 Page 52 Update calculation using the zone 5 negative wind loads. Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
26 Page 53 Update Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Use is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
27 Page 54 Perkins Peterson 1990
the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
28 Page 56 Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
Update calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
29 Page 57 Update calculation using the zone 5 negative wind loads. Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
30 Page 58 Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
Update calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Use is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
31 Page 59 Perkins Peterson 1990
the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
KIPP PROJECT
75 CANAL STREET WEST, BRONX NY, USA 10451
PERFORMANCE MOCK-UP REPORT
TITLE PAGE i
TABLE OF CONTENTS ii
__________________________________________________________________________________________
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
DESIGN INFORMATION
Page 1 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject PROJECT DESIGN INFORMATION
CN 0
1. INTRODUCTION
This report presents the analysis and design verification of panels, members and fixing of the PMU
(performance mock-up) of Unitized Curtainwall at Podium Area.
2. CODES OF PRACTICE
All design work shall comply with the appropriate current standards. Any other relevant codes of
practices shall be referenced as and when necessary. The following standards are used in the report.
3. MATERIAL PROPERTIES
ASTM C1249
Page 2 of 81
__________________________________________________________________________________________
Page 3 of 81
4. LOADS
4.1. DEAD LOADS
All elements are to support and transfer their own self-weight and other associated dead loads. The
following unit weights are considered in the analysis based on the materials.
Unit weight
Material
Density ( lb/ft3 )
Derived Zone (4) wind pressure for podium area, using ASCE 7-16 , are considered in this report.
__________________________________________________________________________________________
Page 4 of 81
4.3. SEISMIC LOAD
5. PERFORMANCE REQUIREMENTS
2. Deflection Parallel to Glazing Plane: Limited to 1/360 of clear span or 1/8 inch (3.2 mm), whichever is
smaller.
__________________________________________________________________________________________
Page 5 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
Page 6 of 81
Calc. by :
KIPP
BP
Chk. by :
PMU
YM
Rev. No. 0
TECHNICAL RESPONSE SHEET
Date: 2023-07-24
Page 1 : Revised and added the reference code: See reply in green marked up.
Page 7 of 81
Page 15 : Revised and followed ASD method. Applied to all member and fixing checks of the same comment. See reply in green marked up.
Page 16 : PMU is located at podium typical areas, hence podium zone ( 4 ) wind pressures are adapted in the report. See reply in green marked up.
Page 8 of 81
Page 17 : STAAD Input is provided and added in the report. See reply in green marked up.
Page 40 : PMU is located at podium typical areas, hence podium zone ( 4 ) wind pressures are adapted in the report. See reply in green marked up.
Page 51 : Revised and amended. Applied to all fixing checks of the same comment. See reply in green marked up.
Page 9 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
LOADING ANALYSIS
Page 10 of 81
Calc. by :
KIPP
BP
Chk. by :
SEISMIC LOAD - ASCE-07
YM
Rev. No. 0
PMU
Date: 2023-07-12
SEISMIC LOAD
SITE CLASS D "C" C III "D"
SEISMIC DESIGN CATEGORY "D" D IV B
PANEL DENSITY r= 25 KN / m3
WEIGHT OF COMPONENT Wp = 1g
SEISMIC LOAD
PANEL HORIZONTAL SEISMIC LOAD ; ( t * r ) * Fph + 10% accessories Vph = 0.25 KPa
PANEL VERTICAL SEISMIC LOAD ; ( t * r ) * Fpv + 10% accessories Vpv = 0.03 KPa
WIND LOAD ; See maximum ultimate wind load excerpt from project specification / see also wind load calculation Ww = 3.59 KPa
Page 11 of 81
Calc. by :
KIPP
BP
Chk. by :
MOVEMENT JOINT
YM
Rev. No. 0
PMU
Date: 2023-05-25
PARAMETERS
Mullion Length ( L ) Maximum panel height - drawing 6734 mm
TOLERANCES
Cutting tolerances (mm) E-mail confirmation 1.0 mm
INTERSTOREY DRIFT
(2) Lateral Movement ; L / 400 or 19mm ; project spec's 16.8 mm
Page 12 of 81
HORIZONTAL JOINT MOVEMENT - STACK JOINT DOWN UP
REQUIRED MINIMUM DESIGN MULLION JOINT MOVEMENT Sum Of - [ 1 + 10% of ( 2 + 3 ) + 5 ] 7.37 mm 8.76 mm
Page 13 of 81
Calc. by :
KIPP
BP
Chk. by :
WIND PRESSURE ( WALLS )
YM
Rev. No. 0
ASCE 07
Date: 2023-07-24
BUILDING PARAMETERS
DESIGN UNIT METRIC
RISK CATEGORY ; See Table 1.5-1 II
EXPOSURE CATEGORY ; Section 26.7 - surface roughness " B " B
ENCLOSURE CLASSIFICATION ; Section 26.13-1 ENCLOSED
Page 14 of 81
WIND DIRECTIONALITY FACTOR ; BUILDINGS ; See Table 26.6-1 kd = 0.85
BUILDING INTERNAL PRESSURE COEFFICIENT ; See Table 26.13 Gcpi ( +/- ) = 0.18
VELOCITY PRESSURE
NOMINAL HEIGHT OF ATMOSPHERIC BOUNDARY LAYER ; See Table 26.11 -1 zg = 366 m
-0.18 1.62
0.90 0.97 KPa 1.62 KPa
0.18 1.08
Zone ( 5 ) CORNER
-0.18 -2.43
-1.80 -1.78 KPa -2.97 KPa
0.18 -2.97
* NOTE: Verification of Members and fixings are based on Podium area typical zone ( 4 ) wind pressures.
Page 15 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
PANEL ANALYSIS
Page 16 of 81
Calc. by :
KIPP
BP
Chk. by :
VISION GLASS
YM
Rev. No. 0
PMU
Date: 2023-05-23
GLASS ANALYSIS
WIND LOAD SHARING ; Q * ( ti3 / ti3 + to3 ) Q= 1.37 KPa Q= 0.41 KPa
2 2
FACTORED STRESS ; ( β * QS * b ) / t j= 21.09 MPa j= 14.07 MPa
Note: Corner wind pressure ( zone 5 ) is adopted to verify our glass panel to ensure our glass composition can be used at all areas.
Page 17 of 81
Calc. by :
KIPP
BP
Chk. by :
SPANDREL GLASS
YM
Rev. No. 0
PMU
Date: 2023-05-23
GLASS ANALYSIS
WIND LOAD SHARING ; Q * ( ti3 / ti3 + to3 ) Q= 1.37 KPa Q= 0.41 KPa
2 2
FACTORED STRESS ; ( β * QS * b ) / t j= 7.08 MPa j= 4.73 MPa
Note: Corner wind pressure ( zone 5 ) is adopted to verify our glass panel to ensure our glass composition can be used at all areas.
Page 18 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
MEMBER ANALYSIS
Page 19 of 81
Calc. by :
KIPP
BP
Chk. by :
UNITIZED MULLION
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETERS :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 20 of 81
MAJOR AXIS MOMENT OF INERTIA Ixm = 3632000 mm4 Ixf = 2888000 mm4 Ix = 6520000 mm4
3 3
MAJOR AXIS PLASTIC MODULUS Zxm = 69900 mm Zxf = 53800 mm Zx = 123700 mm3
MAJOR AXIS ELASTIC MODULUS ( external ) Sxem = 53300 mm3 Sxef = 39200 mm3 Sxe = 92500 mm3
MAJOR AXIS ELASTIC MODULUS ( internal ) Sxim = 41600 mm3 Sxif = 36900 mm3 Sxi = 78500 mm3
MAJOR AXIS RADIUS OF GYRATION rxm = 56 mm rxf = 52 mm rx = 108 mm
MINOR AXIS MOMENT OF INERTIA Iym = 376000 mm4 Iyf = 176000 mm4 Iy = 552000 mm4
MINOR AXIS PLASTIC MODULUS Zym = 22800 mm3 Zyf = 12500 mm3 Zy = 35300 mm3
3 3
MINOR AXIS ELASTIC MODULUS ( external ) Syem = 19200 mm Syef = 8700 mm Sye = 27900 mm3
MINOR AXIS ELASTIC MODULUS ( internal ) Syim = 10500 mm3 Syif = 5460 mm3 Syi = 15960 mm3
MINOR AXIS RADIUS OF GYRATION rym = 18 mm ryf = 13 mm ry = 31 mm
RATIO OF SECTION PROPERTIES MALE RATIO FEMALE RATIO TOTAL SECTION PROPERTY
MAJOR AXIS INERTIA RATIO RIxm = 0.56 Ixm / Ixt RIxf = 0.44 Ixf / Ixt Ixt = 6520000 mm4
MINOR AXIS INERTIA RATIO RIym = 0.68 Iym / Iyt RIyf = 0.32 Iyf / Iyt Iyt = 552000 mm4
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
PANEL DENSITY rg = 25 KN / m3
Page 21 of 81
APPLIED BENDING STRESSES POSSITIVE WL NEGATIVE WL
STRONG AXIS MOMENT ; SEE STAAD RESULT Mx+ = 6.30 KN-m Mx- = 4.10 KN-m
POSSITIVE WL BENDING STRESS ; Mx+ * RIx / Sxe Fbxm ' = 65.84 Mpa Fbxf' = 46.33 Mpa
NEGATIVE WL BENDING STRESS ; Mx- * RIx / Sxi Fbxm ' = 54.90 Mpa Fbxf' = 49.22 Mpa
Page 22 of 81
YIELDING ( l > l1 ) ; Fcy Fc1 = 170.00 Mpa Fc1 = 170.00 Mpa
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fc2 = 153.11 Mpa Fc2 = 153.11 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fc3 = 171.66 Mpa Fc3 = 171.66 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fc1 / W Fcm = 92.79 Mpa Fcm = 92.79 Mpa
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fc2 = 142.77 Mpa Fc2 = 162.76 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fc3 = 146.48 Mpa Fc3 = 204.49 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fc1 / W Fcf = 86.53 Mpa Fcf = 98.64 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 229.33 Mpa Fb2 = 229.33 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 325.18 Mpa Fb3 = 325.18 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 197.08 Mpa Fbm = 197.08 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 229.62 Mpa Fb2 = 229.62 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 326.30 Mpa Fb3 = 326.30 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbf = 197.76 Mpa Fbf = 197.76 Mpa
Page 23 of 81
LATERAL TORSIONAL BUCKLING STRESS - F.4.2.5
NOMINAL BENDING COEFFICIENT ; ( 12.5 Mmax ) / ( 2.5Mmax + 3MA + 4MB + 3MC ) - F.1.1.1 Cbn = 1.25
DISTANCE OF FLANGE CENTROID FROM SECTION CENTROID cfem = 28.78 mm cfef = 3.85 mm
EXTERNAL BENDING COEFFICIENT; IF - 0.10 < RIye < 0.9 = Cbn ; Others = 1 Cbem = 1.25 Cbef = 1.00
DISTANCE OF FLANGE CENTROID FROM SECTION CENTROID cfim = 28.78 mm cfif = 5.35 mm
INTERNAL BENDING COEFFICIENT ; IF - 0.10 < RIye < 0.9 = Cbn ; Others = 1 Cbim = 1.25 Cbif = 1.00
DISTANCE OF SHEAR CENTER TO POINT OF LOAD ( External Flange ) goe = 109.32 mm goe = 97.57 mm
DISTANCE OF SHEAR CENTER TO POINT OF LOAD ( Internal Flange ) goi = 85.12 mm goi = 96.87 mm
EXTERNAL CRITICAL MOMENT PARAMETER ; C1 * go+ - C2 * βce / 2 Uem = 87.72 Uef = 91.44
NOMINAL FLEXURAL STRENGTH FOR YIELDING ; Min ( Zx * Fcy ) , ( 1.5 Sxe * Fcy ) Mnpm = 11.88 KN-M Mnpf = 9.15 KN-M
2 2 2 2
TORSIONAL BUCKLING ; ( Cb * π * E * Iy / Lb )[U + U + 0.038*J*Lb / Iy + Cw/Iy ] Mem = 66.23 KN-M Mef = 14.37 KN-M
LTB BUCKLING STRENGTH ; IF l < Cc = Mnmb1 / W, l > Cc = Mnmb2 / W Mmbem = 6.12 Mpa Mmbef = 3.94 Mpa
ALLOWABLE LTB STRESS ; Mmbe / Sxe Fbem = 114.77 Mpa Fbef = 100.50 Mpa
Page 24 of 81
INTERNAL FLANGE ALLOWABLE LTB STRESS MALE MULLION FEMALE MULLION
2
INTERNAL COEFFICIENT OF MONOSYMMETRY ; 0.9df * [( 2Iyi/Iy )-1][1-( Iy/Ix ) ] βcim = -132.23 βcif = -165.14
INTERNAL CRITICAL MOMENT PARAMETER ; C1 * go- - C2 * βci / 2 Uim = 75.62 Uif = 89.72
NOMINAL FLEXURAL STRENGTH FOR YIELDING ; Min ( Zx * Fcy ) , ( 1.5 Sxi * Fcy ) Mnpm = 10.61 KN-M Mnpf = 9.15 KN-M
TORSIONAL BUCKLING ; ( Cb * π2 * E * Iy / Lb2 )[U + U2 + 0.038*J*Lb2 / Iy + Cw/Iy ] Mem = 64.09 KN-M Mef = 14.17 KN-M
LTB BUCKLING STRENGTH ; IF l < Cc = Mnmb1 / W, l > Cc = Mnmb2 / Wb Mmbim = 5.45 Mpa Mmbif = 3.89 Mpa
ALLOWABLE LTB STRESS ; Mmbi / Sxi Fbim = 131.08 Mpa Fbif = 105.53 Mpa
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
MINOR AXIS MOMENT OF INERTIA Iy = 376000 mm4 376000 mm4 176000 mm4 176000 mm4
TORSION CONTANT J= 556000 mm4 556000 mm4 6990 mm4 6990 mm4
BUCKLING CONSTANT INTERSECTION Cc = 79.16 Mpa 79.16 Mpa 79.16 Mpa 79.16 Mpa
NOMINAL FLEXURAL STRENGTH Mnmb = 10.09 KN-M 9.00 KN-M 6.50 KN-M 6.42 KN-M
ALLOWABLE LTB STRENGTH Mmb = 6.12 KN-M 5.45 KN-M 3.94 KN-M 3.89 KN-M
ALLOWABLE LTB STRENGTH STRESS Fb = 114.77 MPa 131.08 MPa 100.50 MPa 105.53 MPa
Page 25 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.1 ( FLANGES - UNSUPPORTED ELEMENT )
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
BUCKLING CONSTANT INTERCEPT Bp = 213.24 Mpa 213.24 Mpa 213.24 Mpa 213.24 Mpa
BUCKLING CONSTANT SLOPE Dp = 1.18 Mpa 1.18 Mpa 1.18 Mpa 1.18 Mpa
BUCKLING CONSTANT INTERSECTION Cp = 74.28 Mpa 74.28 Mpa 74.28 Mpa 74.28 Mpa
NOMINAL COMPRESSIVE STRENGTH Fc1 = 153.11 MPa 153.11 MPa 142.77 MPa 162.76 MPa
ALLOWABLE COMPRESSIVE STRESS Fc = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
BUCKLING CONSTANT INTERCEPT Bbr = 313.19 Mpa 313.19 Mpa 313.19 Mpa 313.19 Mpa
BUCKLING CONSTANT SLOPE Dbr = 2.57 Mpa 2.57 Mpa 2.57 Mpa 2.57 Mpa
BUCKLING CONSTANT INTERSECTION Cbr = 81.38 Mpa 81.38 Mpa 81.38 Mpa 81.38 Mpa
NOMINAL BUCKLING STRENGTH Fb1 = 325.18 MPa 325.18 MPa 326.30 MPa 326.30 MPa
ALLOWABLE BUCKLING STRESS Fb = 197.08 MPa 197.08 MPa 197.76 MPa 197.76 MPa
COMPRESSIVE STRESS - B.5.4.1 Fc = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
LOCAL BUCKLING - B.5.5.1 Fb = 197.08 MPa 197.08 MPa 197.76 MPa 197.76 MPa
LATERAL TORSIONAL BUCKLING - F.4.2.5 Fb = 114.77 MPa 131.08 MPa 100.50 MPa 105.53 MPa
APPLIED STRESS Fb' = 65.84 MPa 54.90 MPa 46.33 MPa 49.22 MPa
GOVERNING ALLOWABLE STRESS Fb = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
RESULT OK OK OK OK
Page 26 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 25.90 mm
Page 27 of 81
Calc. by :
KIPP
BP
Chk. by :
MID - DUMMY MULLION
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETERS :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 28 of 81
SECTION PROPERTIES -SECTION WIZARD
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
PANEL DENSITY rg = 25 KN / m3
Page 29 of 81
INTERNAL ELEMENT UNDER UNIFORM COMPRESSION - WEB - ( B.5.4.2 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 1.6 * Dp * l Fbxen2 = 195.49 Mpa Fbxin2 = 163.12 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 1.6 * l Fbxen3 = 581.52 Mpa Fbxin3 = 205.93 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 103.03 Mpa Fbxi = 98.86 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 264.70 Mpa Fb2 = 264.70 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 562.39 Mpa Fb3 = 562.39 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 340.84 Mpa Fbm = 340.84 Mpa
Page 30 of 81
SUMMARY OF LOCAL BUCKLING STRESS - B.5.5.1 ( WEB - SUPPORTED ELEMENT )
RESULT OK OK
WL DEFLECTION dx = 15.88 mm
Page 31 of 81
Calc. by :
KIPP
BP
Chk. by :
STACK JOINT TRANSOM
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETER :
MECHANICAL PROPERTIES :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
MEMBER BUCKLING
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 32 of 81
SECTION PROPERTIES -SECTION WIZARD HEAD TRANSOM SILL TRANSOM
RATIO OF SECTION HEAD TRANSOM RATIO SILL TRANSOM RATIO TOTAL SECTION PROPERTY
MAJOR AXIS NERTIA RATIO R1 = 0.53 Ix1 / IxT R2 = 0.47 Ix2 / IxT IxT = 9439375 mm4
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
SB POINT LOAD AT SILL TRANSOM ; 1.25 * t * r * da * Lm / 2 - With 25% Accesories Py= 0.40 KN
TOTAL WL MOMENT ; Mxa + Mxb Mx+ = 0.31 KN-m Mx- = -0.21 KN-m
HEAD WL BENDING STRESS ; Mx+ R / Sx Fbxf' = 2.79 Mpa Fbxf' = -1.78 Mpa
SILL WL BENDING STRESS ; Mx+ R / Sx Fbxf' = 3.22 Mpa Fbxf' = -1.60 Mpa
Page 33 of 81
SECTION ELEMENT OF FLANGES
OUTSTAND ELEMENT UNDER UNIFORM COMPRESSION - FLANGE - ( B.5.4.1 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fbxen2 = 141.46 Mpa Fbxin2 = 123.14 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fbxen3 = 143.80 Mpa Fbxin3 = 114.56 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 85.73 Mpa Fbxi = 69.43 Mpa
Page 34 of 81
SLENDERNESS OF ELEMENT ;d/t le = 26.26 li = 26.26
LOWER SLENDERNES LIMIT ; ( Bbr -1.5 Fcy ) / ( m*Dbr ) le1 = 14.08 li1 = 14.08
YIELDING ( l > l1 ) ; 1.5 * Fcy Fbxen1 = 255.00 Mpa Fbxin1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr * l ] Fbxen2 = 204.66 Mpa Fbxin2 = 204.66 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * l ] Fbxen3 = 604.15 Mpa Fbxin3 = 604.15 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 124.04 Mpa Fbxi = 124.04 Mpa
LOWER SLENDERNES LIMIT ; ( Bbr -1.5 Fcy ) / ( m*Dbr ) le1 = 14.96 li1 = 14.96
YIELDING ( l > l1 ) ; 1.5 * Fcy Fbxen1 = 255.00 Mpa Fbxin1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr * l ] Fbxen2 = 150.32 Mpa Fbxin2 = 150.32 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * l ] Fbxen3 = 378.90 Mpa Fbxin3 = 378.90 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 229.64 Mpa Fbxi = 229.64 Mpa
WL DISPLACEMENT ABOVE ; (PWLsxa L4)/(1920 E IxT )*(25 - 40(aa/L)2 + 16(aa/L)4) dxa = 0.06 mm
4
WL DISPLACEMENT BELOW ; (PWLsxb L )/(1920 E IxT )*(25 - 40(ab/L)2 + 16(ab/L)4) dxb = 0.09 mm
Page 35 of 81
DESIGN OF MEMBER FOR FLEXURE
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.44 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.44 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.40 KN-M
APPLIED LOADS
Page 36 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.1 ( FLANGES - OUTSTAND ELEMENT )
RESULT OK OK
Page 37 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 0.15 mm
DL DEFLECTION dy = 0.60 mm
Page 38 of 81
Calc. by :
KIPP
BP
Chk. by :
INTERMEDIATE TRANSOM
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETER :
BUCKLING CONSTANTS
MEMBER BUCKLING
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 39 of 81
SECTION PROPERTIES -SECTION WIZARD
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
SB POINT LOAD AT SILL TRANSOM ; 1.25 * t * r * da * Lm / 2 - With 25% Accesories Py= 2.04 KN
Page 40 of 81
TOTAL WL MOMENT ; Mxa + Mxb Mx+ = 0.41 KN-m Mx- = -0.28 KN-m
INTERNAL ELEMENT UNDER UNIFORM COMPRESSION - WEB - ( B.5.4.2 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 1.6 * Dp * l Fbxen2 = 195.49 Mpa Fbxin2 = 163.12 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 1.6 * l Fbxen3 = 581.52 Mpa Fbxin3 = 205.93 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 103.03 Mpa Fbxi = 98.86 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 197.13 Mpa Fb2 = 197.13 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 562.39 Mpa Fb3 = 562.39 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 340.84 Mpa Fbm = 340.84 Mpa
Page 41 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.2 ( WEB - SUPPORTED ELEMENT )
RESULT OK OK
Page 42 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 0.18 mm
DL DEFLECTION dy = 1.25 mm
Page 43 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
FIXING ANALYSIS
Page 44 of 81
CHECK FOR ALUMINUM PRESSURE PLATE
+ / - Fz
SECTION PROPERTIES
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 84.00 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = -62.61 KN-M
Page 45 of 81
STRONG AXIS YIELDING AND RUPTURE
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 1.44 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.16 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.16 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.16 KN-M
Page 46 of 81
CHECK FOR ALUMINUM GLASS CHAIR Fy
22.3m
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
SECTION PROPERTIES
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 5.51 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = -1.64 KN-M
Page 47 of 81
STRONG AXIS YIELDING AND RUPTURE
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.21 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.06 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.06 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.05 KN-M
Page 48 of 81
CHECK FOR ALUMINUM HOOK BRACKET PLATE
Fy
+ / - Fz
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
CHECK SECTION 1
SECTION PROPERTIES
Page 49 of 81
STRONG AXIS ELASTIC MODULUS ; t * b2 / 6 Sx = 621 mm3
2
WEAK AXIS ELASTIC MODULUS ;b*t /6 Sy = 322 mm3
-1
WEAK AXIS RADIUS OF GYRATION ; Iy * A ry = 1.45 mm
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 0.22 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = 0.12 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 0.85 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.12 KN-M
Page 50 of 81
WEAK AXIS YIELDING AND RUPTURE
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.07 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.07 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.06 KN-M
TENSION LOADS
SHEAR LOAD
Page 51 of 81
CHECK SECTION 2
Fy
+/- Fz
SECTION PROPERTIES
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
TENSION COEFFICIENT kt = 1
Page 52 of 81
LATERAL TORSIONAL BUCKLING
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 0.60 KN-M
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π2 * E * lb * Sx ) / ( Cc3 * Wby ) Mnpx1 = 0.33 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 4.50 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.33 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.23 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.23 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.21 KN-M
APPLIED LOADS
TENSION LOADS
SHEAR LOAD
Page 53 of 81
CHECK FOR ALUMINUM FLOOR BRACKET
Fy
+/- Fz
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
SECTION PROPERTIES
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
Page 54 of 81
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 50.17 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = 20.70 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 41.17 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 20.70 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 2.13 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 2.13 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 1.95 KN-M
Page 55 of 81
HORIZONTAL FORCE DUE TO POSITIVE WL Fz+ = 11.46 KN
TENSION LOADS
SHEAR LOAD
DIRECT SHEAR
Page 56 of 81
CHECK #12 SS A4-70 PRESSURE PLATE SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.18 inch 4.60 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.19 inch 4.70 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.21 inch 5.28 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.19 inch 4.90 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.01 inch2 14.96 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.02 inch 2
22.79 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 57 of 81
ALLOWABLE SHEAR STRESS ; 0.75 Fy /3 ; ( with 1.33 safety factor ) Fv1 = 47.63 Mpa
ALLOWABLE SHEAR STRESS ; 0.4 Fu / ; ( with 2.5 safety factor ) Fv1 = 36.95 Mpa
ALLOWABLE SHEAR STRESS ; Fy /3 ; ( with out safety factor ) Fv = 63.51 Mpa
APPLIED LOAD
TENSILE LOAD
Page 58 of 81
ANALYSIS OF BRACKETRY FIXINGS
CHECK M12 STAINLESS STEEL BOLT MULLION FASTENER
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.43 inch 11.02 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.44 inch 11.28 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.49 inch 12.40 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.46 inch 11.61 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.06 inch2 38.91 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.11 inch2 68.88 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 59 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION SLIDE BRACKET
SHEAR LOAD
ECCENTRICITY OF DL x= 44 mm
Page 60 of 81
SHEAR REACTION / BOLT ; Fy / n Vy = 3.8 KN
BEARING
Page 61 of 81
CHECK 1/4 SS A4-70 STACK JOINT HEAD TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 62 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL ECCENTRICITY ex = 50 mm
BEARING
Page 63 of 81
CHECK 1/4 SS A4-70 STACK JOINT SILL TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 64 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL SHEAR ; ww * H / 2 * n Vw = 0.30 KN
GLASS DENSITY r= 25 KN / m3
NUMBER OF SB n= 2 nos
WL ECCENTRICITY ex = 11 mm
DL ECCENTRICITY ey = 82 mm
Page 65 of 81
BEARING
Page 66 of 81
CHECK 1/4 SS A4-70 INTERMEDIATE TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 67 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL SHEAR ; ww * H / 2 * n Vw = 1.84 KN
GLASS DENSITY r= 25 KN / m3
NUMBER OF SB n= 2 nos
DL ECCENTRICITY ey = 82 mm
Page 68 of 81
BEARING
Page 69 of 81
CHECK M16 STAINLESS STEE LHEX BOLT SOCKET COUNTERSUNK HEAD
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.55 inch 13.87 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.56 inch 14.20 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.61 inch 15.52 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.57 inch 14.55 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.09 inch2 50.87 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.16 inch 2
94.10 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 70 of 81
ALLOWABLE TENSILE AND SHEAR LOADS OF FASTENER
Page 71 of 81
APPLIED LOADS POSSITIVE WL NEGATIVE WL
WL ECCENTRICITY ex = 42 mm
SHEAR LOAD
TENSILE LOAD
BEARING
Page 72 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
SECTION PROPERTIES
Page 73 of 81
z
y MALE MULLION
v u
Geometric properties of the cross-section
A Sectional area
Parameter Value
1.43e+3 mm^2
Av,y Conventional shearing area along Y-axis 3.03e+2 mm^2
Av,z Conventional shearing area along Z-axis 5.45e+2 mm^2
Angle between Y-Z and U-V axes 0.542 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 4.54e+6 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 4.7e+5 mm^4
It Torsional moment of inertia (St. Venant) 5.56e+5 mm^4
Iw Warping constant 1.01e+9 mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 5.64e+1 mm
iz Radius of gyration about axis parallel to Z passing through centroid 1.81e+1 mm
Wu+ Elastic modulus about U-axis (+ve extreme) 5.33e+4 mm^3
Wu- Elastic modulus about U-axis (-ve extreme) 4.16e+4 mm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 1.92e+4 mm^3
Wv- Elastic modulus about V-axis (-ve extreme) 1.05e+4 mm^3
Wpl,u Plastic modulus about axis parallel to U-axis 6.99e+4 mm^3
Wpl,v Plastic modulus about axis parallel to V-axis 2.28e+4 mm^3
Iu Moment of inertia about U-axis 4.54e+6 mm^4
Iv Moment of inertia about V-axis 4.7e+5 mm^4
iu Radius of gyration about U-axis 5.64e+1 mm
iv Radius of gyration about V-axis 1.81e+1 mm
au+ Centroid to edge of compression zone along +ve U-axis 1.35e+1 mm
au- Centroid to edge of compression zone along -ve U-axis 7.39 mm
av+ Centroid to edge of compression zone along +ve V-axis 3.73e+1 mm
av- Centroid to edge of compression zone along -ve V-axis 2.92e+1 mm
yM Distance to centroid along Y-axis -4.78e+1 mm
zM Distance to centroid along Z-axis -1.19e+2 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis -2.49e+1 mm
Zb Distance to shear centre along Z-axis -9.14e+1 mm
P Perimeter 9.2e+2 mm
Pi Internal perimeter 2.49e+2 mm
Pe External perimeter 6.7e+2 mm
I1 Moment of inertia about Y-axis 4.54e+6 mm^4
I2 Moment of inertia about Z-axis 4.7e+5 mm^4
I12 Product of inertia about the centroid -3.85e+4 mm^4
Ip Polar moment of inertia about centroid 5.01e+6 mm^4
ip Polar radius of gyration about centroid 5.93e+1 mm
Wp Polar elastic modulus about centroid 4.57e+4 mm^3
yp Distance to equal area axis along Y-axis -5.13 mm
zp Distance to equal area axis along Z-axis -1.07e+1 mm
up Distance to equal area axis along U-axis -5.27 mm
vp Distance to equal area axis along V-axis 8.66e-1 mm
Page 74 of 81
z
y FEMALE MULLION
vu
Geometric properties of the cross-section
A Sectional area
Parameter Value
1.08e+3 mm^2
Av,y Conventional shearing area along Y-axis 2.09e+2 mm^2
Av,z Conventional shearing area along Z-axis 4.13e+2 mm^2
Angle between Y-Z and U-V axes 5.748 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 3.61e+6 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 2.2e+5 mm^4
It Torsional moment of inertia (St. Venant) 6.99e+3 mm^4
Iw Warping constant 4.94e+8 mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 5.77e+1 mm
iz Radius of gyration about axis parallel to Z passing through centroid 1.42e+1 mm
Wu+ Elastic modulus about U-axis (+ve extreme) 3.72e+4 mm^3
Wu- Elastic modulus about U-axis (-ve extreme) 3.69e+4 mm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 8.7e+3 mm^3
Wv- Elastic modulus about V-axis (-ve extreme) 5.46e+3 mm^3
Wpl,u Plastic modulus about axis parallel to U-axis 5.38e+4 mm^3
Wpl,v Plastic modulus about axis parallel to V-axis 1.25e+4 mm^3
Iu Moment of inertia about U-axis 3.65e+6 mm^4
Iv Moment of inertia about V-axis 1.85e+5 mm^4
iu Radius of gyration about U-axis 5.8e+1 mm
iv Radius of gyration about V-axis 1.31e+1 mm
au+ Centroid to edge of compression zone along +ve U-axis 8.03 mm
au- Centroid to edge of compression zone along -ve U-axis 5.04 mm
av+ Centroid to edge of compression zone along +ve V-axis 3.43e+1 mm
av- Centroid to edge of compression zone along -ve V-axis 3.41e+1 mm
yM Distance to centroid along Y-axis -1.85e+1 mm
zM Distance to centroid along Z-axis -1.07e+2 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis -4.73e+1 mm
Zb Distance to shear centre along Z-axis -9.05e+1 mm
P Perimeter 6.85e+2 mm
Pi Internal perimeter 0 mm
Pe External perimeter 6.85e+2 mm
I1 Moment of inertia about Y-axis 3.61e+6 mm^4
I2 Moment of inertia about Z-axis 2.2e+5 mm^4
I12 Product of inertia about the centroid -3.45e+5 mm^4
Ip Polar moment of inertia about centroid 3.83e+6 mm^4
ip Polar radius of gyration about centroid 5.95e+1 mm
Wp Polar elastic modulus about centroid 3.84e+4 mm^3
yp Distance to equal area axis along Y-axis -2.21 mm
zp Distance to equal area axis along Z-axis -5.43 mm
up Distance to equal area axis along U-axis -1.09 mm
vp Distance to equal area axis along V-axis -4.03 mm
Page 75 of 81
z
y DUMMY MULLION / INTERMEDIATE
TRANSOM
Geometric properties of the cross-section
Parameter Value
A Cross sectional area 1682.15 mm^2
Av,y Conventional shearing area along Y-axis 422.46 mm^2
Av,z Conventional shearing area along Z-axis 699.29 mm^2
Angle between Y-Z and U-V axes -0.003 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 5126299.54 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 2354988.96 mm^4
It Torsional moment of inertia (St. Venant) 4433686.19 mm^4
Iw Warping constant 317782308.3mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 55.2 mm
iz Radius of gyration about axis parallel to Z passing through centroid 37.42 mm
Wu+ Max elastic modulus about U-axis 66493.88 mm^3
Wu- Min elastic modulus about U-axis 70630.14 mm^3
Wv+ Max elastic modulus about V-axis 51903.03 mm^3
Wv- Min elastic modulus about V-axis 51905.23 mm^3
Wpl,u Plastic modulus about U-axis 84677.18 mm^3
Wpl,v Plastic modulus about V-axis 58934.7 mm^3
Iu Moment of inertia about U-axis 5126299.55 mm^4
Iv Moment of inertia about V-axis 2354988.95 mm^4
iu Radius of gyration about U-axis 55.2 mm
iv Radius of gyration about V-axis 37.42 mm
au+ Centroid to edge of compression zone along +ve U-axis 30.86 mm
au- Centroid to edge of compression zone along -ve U-axis 30.86 mm
av+ Centroid to edge of compression zone along +ve V-axis 39.53 mm
av- Centroid to edge of compression zone along -ve V-axis 41.99 mm
yM Distance to centroid along Y-axis 0 mm
zM Distance to centroid along Z-axis 0.01 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis 0.01 mm
Zb Distance to shear centre along Z-axis 2.53 mm
P Perimeter 1088.3 mm
Pi Internal perimeter 540.43 mm
Pe External perimeter 547.88 mm
I1 Moment of inertia about Y-axis 5126299.63 mm^4
I2 Moment of inertia about Z-axis 2354988.97 mm^4
I12 Product of inertia about the centroid 147.02 mm^4
Ip Polar moment of inertia about centroid 7481288.5 mm^4
ip Polar radius of gyration about centroid 66.69 mm
Wp Polar elastic modulus about centroid 0.93 mm
Page 76 of 81
z
Page 77 of 81
z
Page 78 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
Page 79 of 81
Job Title:
Client:
Engineer:
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 20-Apr-23
END JOB INFORMATION
INPUT WIDTH 79
UNIT MMS NEWTON
JOINT COORDINATES
1 25000 0 0; 2 25000 720 0; 4 25000 5270 0; 5 25000 6005 0; 6 25000 6250 0;
7 25000 12983.5 0; 10 25000 12015 0; 11 25000 12748.5 0;
MEMBER INCIDENCES
1 1 2; 3 2 4; 4 4 5; 5 5 6; 6 6 10; 9 10 11; 10 11 7;
DEFINE MATERIAL START
ISOTROPIC ALUMINUM
E 68947.6
POISSON 0.33
DENSITY 2.66018e-05
ALPHA 2.3e-05
DAMP 0.03
ISOTROPIC STEEL
E 205000
POISSON 0.3
DENSITY 7.68195e-05
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH RY 1.5 RT 1.2
ISOTROPIC STEEL_275_NMM2
E 205000
POISSON 0.3
DENSITY 7.7e-05
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH FY 275 FU 410 RY 1.5 RT 1.2
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
1 3 TO 6 9 10 PRIS AX 2510 IX 562990 IY 552000 IZ 6.52e+06
CONSTANTS
BETA 90 ALL
MATERIAL ALUMINUM ALL
SUPPORTS
5 11 FIXED BUT MX MZ
1 4 10 FIXED BUT FY MX MZ
MEMBER RELEASE
6 START FX MY MZ
LOAD 1 LOADTYPE Dead TITLE DL
MEMBER LOAD
Page 80 of 81
Job Title:
Client:
Engineer:
1 3 TO 6 9 10 UNI GY -1.16
SELFWEIGHT Y -1
LOAD 2 LOADTYPE Wind TITLE WL - SERVICE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y 1.1
LOAD 3 LOADTYPE Wind TITLE WL +SERVICE
MEMBER LOAD
1 3 TO 6 9 10 UNI GZ -1.7
LOAD 4 LOADTYPE Wind TITLE WL - ULTIIMATE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y 1.9
LOAD 5 LOADTYPE Wind TITLE WL + ULTIMATE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y -2.8
PERFORM ANALYSIS
FINISH
Page 81 of 81
KIPP HS – 75 Canal St W
HRCG Project #238600
HRCG Submittal Stamp Sheet
By: jpascarella
HUNTER ROBERTS CONSTRUCTION GROUP
DDC Stamp
Architect/Engineer Stamp Consultant Stamp Stamp
Architect/Engineer
Date: 07/24/2023
Design Mix Data Color Chart/Chip Sustainable Mtrl Info Test Reports
Submitted For:
Item Reference Page Location Description / Comments Comments By Response Response By Remarks Status
4 Page 1 Provide reference for structural sealant design strengths. Perkins Reference for Structural Sealant Design Strengths - ASTM C1249 now clearly referenced Peterson 1990
5 Page 3 2014 NYC BC references ASCE 7-05 Perkins ASCE 7-16 is clearely referenced and indicated in the Project Technical Specifications Peterson 1990
Per 2014 NYC BC, the design pressure for components and cladding of buildings shall not be
6 Page 3 Perkins ASCE 7-16 is clearely referenced and indicated in the Project Technical Specifications Peterson 1990
less than 20 psf acting in either direction normal to the surface.
Wind tunnel test report was wrong/Incorrect annotation, this is omitted as it should follow & comply
7 Page 4 Provide referenced wind tunnel test report. Perkins Peterson 1990
withASCE 7-16 maximum wind pressure calculated
Wind tunnel test report was wrong/Incorrect annotation, this is omitted as it should follow & comply
8 Page 6 Provide referenced wind tunnel test report. Perkins Peterson 1990
withASCE 7-16 maximum wind pressure calculated
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Specification wind pressure is more conservative than calculated wind pressure. Therefor use
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
9 Page 9 specification Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
wind pressure in calculations.
podium in compliance with ASCE 7-16 code.
Per NYC Building Code exposure category C is to be used because the building is within 2,600 ft of
Revised calculation is following ASCE 7-16 Code, Exposure B Category, refer to Technical response issued on
10 Page 9 the Perkins Peterson 1990
page 8 of 75
shoreline.
This is for the podium wind pressure caalculation hence podium level height is considered per this
11 Page 9 Wind load to be calculated using the total building height of 150' (45.72 m). Perkins Peterson 1990
calculation
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
12 Page 15 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Typical Zone 4 wind pressures are adapted since the PMU is based on and representative of Typical area of
13 Page 16 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. the façade, whereas the corner zone areas will have additional beams across
14 Page 17 Provide full STAAD analysis report to confirm inputs and outputs. Perkins STAAD Input is provided and added into the revised calculation Peterson 1990
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
15 Page 23 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
16 Page 24 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
17 Page 26 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation to use only ASD or LRFD.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
18 Page 27 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Resistance Factor is for LRFD and Safety Factor is for ASD. Both are used for in this section, but
19 Page 33 only one Perkins Revised following the ASD Method, applied to all members and fixing checks of the same comment Peterson 1990
calculation method should be used. Update calculation
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
20 Page 34 Perkins Peterson 1990
Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
21 Page 40 Perkins Peterson 1990
section. Use the zone 5 for both positive pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
22 Page 43 Perkins Peterson 1990
section. Use the zone 5 for both positive pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
23 Page 49 Perkins Peterson 1990
section. Use the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
24 Page 51 Update Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
25 Page 52 Update calculation using the zone 5 negative wind loads. Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
26 Page 53 Update Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Use is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
27 Page 54 Perkins Peterson 1990
the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
28 Page 56 Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
Update calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
29 Page 57 Update calculation using the zone 5 negative wind loads. Perkins Peterson 1990
pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
Per AAMA TIR A9-14 ultimate tensile strength is 100,000 and allowable tensile stress is 40,000 psi.
30 Page 58 Perkins Revised accordingly, see as attached AAMA TIR A9-14, Table 11 Peterson 1990
Update calculation with correct values.
Project specification wind pressure provided is for the total Height of the tower, However the PMU location
Positive wind load from zone 5 and negative wind load from zone 4 are used in this section. Use is located at the typical Podium areas of the building. For Podium wind pressure since no detailed wind
31 Page 59 Perkins Peterson 1990
the zone 5 for both positive and negative wind loads. pressure for a particular height or area of the building, we have calculated based on relevant height of the
podium in compliance with ASCE 7-16 code.
HRCG: EOR/PEA to
review and advise as
applicable. TYP.
KIPP PROJECT
75 CANAL STREET WEST, BRONX NY, USA 10451
PERFORMANCE MOCK-UP REPORT
TITLE PAGE i
TABLE OF CONTENTS ii
__________________________________________________________________________________________
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
DESIGN INFORMATION
Page 1 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject PROJECT DESIGN INFORMATION
CN 0
1. INTRODUCTION
This report presents the analysis and design verification of panels, members and fixing of the PMU
(performance mock-up) of Unitized Curtainwall at Podium Area.
2. CODES OF PRACTICE
All design work shall comply with the appropriate current standards. Any other relevant codes of
practices shall be referenced as and when necessary. The following standards are used in the report.
3. MATERIAL PROPERTIES
ASTM C1249
Page 2 of 81
__________________________________________________________________________________________
Page 3 of 81
4. LOADS
4.1. DEAD LOADS
All elements are to support and transfer their own self-weight and other associated dead loads. The
following unit weights are considered in the analysis based on the materials.
Unit weight
Material
Density ( lb/ft3 )
Derived Zone (4) wind pressure for podium area, using ASCE 7-16 , are considered in this report.
__________________________________________________________________________________________
Page 4 of 81
4.3. SEISMIC LOAD
5. PERFORMANCE REQUIREMENTS
2. Deflection Parallel to Glazing Plane: Limited to 1/360 of clear span or 1/8 inch (3.2 mm), whichever is
smaller.
__________________________________________________________________________________________
Page 5 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
Page 6 of 81
HRCG: Consultant comments
below. EOR to Review and advise
as applicable.
Calc. by :
KIPP
BP
Chk. by :
PMU
YM
Rev. No. 0
TECHNICAL RESPONSE SHEET
Date: 2023-07-24
Page 1 : Revised and added the reference code: See reply in green marked up.
Page 7 of 81
HRCG: Consultant comments
below. EOR to Review and advise
as applicable.
Page 15 : Revised and followed ASD method. Applied to all member and fixing checks of the same comment. See reply in green marked up.
Page 16 : PMU is located at podium typical areas, hence podium zone ( 4 ) wind pressures are adapted in the report. See reply in green marked up.
Page 8 of 81
HRCG: Consultant comments
below. EOR to Review and advise
as applicable.
Page 17 : STAAD Input is provided and added in the report. See reply in green marked up.
Page 40 : PMU is located at podium typical areas, hence podium zone ( 4 ) wind pressures are adapted in the report. See reply in green marked up.
Page 51 : Revised and amended. Applied to all fixing checks of the same comment. See reply in green marked up.
Page 9 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
LOADING ANALYSIS
Page 10 of 81
Calc. by :
KIPP
BP
Chk. by :
SEISMIC LOAD - ASCE-07
YM
Rev. No. 0
PMU
Date: 2023-07-12
SEISMIC LOAD
SITE CLASS D "C" C III "D"
SEISMIC DESIGN CATEGORY "D" D IV B
PANEL DENSITY r= 25 KN / m3
WEIGHT OF COMPONENT Wp = 1g
SEISMIC LOAD
PANEL HORIZONTAL SEISMIC LOAD ; ( t * r ) * Fph + 10% accessories Vph = 0.25 KPa
PANEL VERTICAL SEISMIC LOAD ; ( t * r ) * Fpv + 10% accessories Vpv = 0.03 KPa
WIND LOAD ; See maximum ultimate wind load excerpt from project specification / see also wind load calculation Ww = 3.59 KPa
Page 11 of 81
Calc. by :
KIPP
BP
Chk. by :
MOVEMENT JOINT
YM
Rev. No. 0
PMU
Date: 2023-05-25
PARAMETERS
Mullion Length ( L ) Maximum panel height - drawing 6734 mm
TOLERANCES
Cutting tolerances (mm) E-mail confirmation 1.0 mm
INTERSTOREY DRIFT
(2) Lateral Movement ; L / 400 or 19mm ; project spec's 16.8 mm
Page 12 of 81
HORIZONTAL JOINT MOVEMENT - STACK JOINT DOWN UP
REQUIRED MINIMUM DESIGN MULLION JOINT MOVEMENT Sum Of - [ 1 + 10% of ( 2 + 3 ) + 5 ] 7.37 mm 8.76 mm
Page 13 of 81
Calc. by :
KIPP
BP
Chk. by :
WIND PRESSURE ( WALLS )
YM
Rev. No. 0
ASCE 07
Date: 2023-07-24
BUILDING PARAMETERS
DESIGN UNIT METRIC
RISK CATEGORY ; See Table 1.5-1 II
EXPOSURE CATEGORY ; Section 26.7 - surface roughness " B " B
ENCLOSURE CLASSIFICATION ; Section 26.13-1 ENCLOSED
Page 14 of 81
WIND DIRECTIONALITY FACTOR ; BUILDINGS ; See Table 26.6-1 kd = 0.85
BUILDING INTERNAL PRESSURE COEFFICIENT ; See Table 26.13 Gcpi ( +/- ) = 0.18
VELOCITY PRESSURE
NOMINAL HEIGHT OF ATMOSPHERIC BOUNDARY LAYER ; See Table 26.11 -1 zg = 366 m
-0.18 1.62
0.90 0.97 KPa 1.62 KPa
0.18 1.08
Zone ( 5 ) CORNER
-0.18 -2.43
-1.80 -1.78 KPa -2.97 KPa
0.18 -2.97
* NOTE: Verification of Members and fixings are based on Podium area typical zone ( 4 ) wind pressures.
Page 15 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
PANEL ANALYSIS
Page 16 of 81
Calc. by :
KIPP
BP
Chk. by :
VISION GLASS
YM
Rev. No. 0
PMU
Date: 2023-05-23
GLASS ANALYSIS
WIND LOAD SHARING ; Q * ( ti3 / ti3 + to3 ) Q= 1.37 KPa Q= 0.41 KPa
2 2
FACTORED STRESS ; ( β * QS * b ) / t j= 21.09 MPa j= 14.07 MPa
Note: Corner wind pressure ( zone 5 ) is adopted to verify our glass panel to ensure our glass composition can be used at all areas.
Page 17 of 81
Calc. by :
KIPP
BP
Chk. by :
SPANDREL GLASS
YM
Rev. No. 0
PMU
Date: 2023-05-23
GLASS ANALYSIS
WIND LOAD SHARING ; Q * ( ti3 / ti3 + to3 ) Q= 1.37 KPa Q= 0.41 KPa
2 2
FACTORED STRESS ; ( β * QS * b ) / t j= 7.08 MPa j= 4.73 MPa
Note: Corner wind pressure ( zone 5 ) is adopted to verify our glass panel to ensure our glass composition can be used at all areas.
Page 18 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
MEMBER ANALYSIS
Page 19 of 81
Calc. by :
KIPP
BP
Chk. by :
UNITIZED MULLION
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETERS :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 20 of 81
MAJOR AXIS MOMENT OF INERTIA Ixm = 3632000 mm4 Ixf = 2888000 mm4 Ix = 6520000 mm4
3 3
MAJOR AXIS PLASTIC MODULUS Zxm = 69900 mm Zxf = 53800 mm Zx = 123700 mm3
MAJOR AXIS ELASTIC MODULUS ( external ) Sxem = 53300 mm3 Sxef = 39200 mm3 Sxe = 92500 mm3
MAJOR AXIS ELASTIC MODULUS ( internal ) Sxim = 41600 mm3 Sxif = 36900 mm3 Sxi = 78500 mm3
MAJOR AXIS RADIUS OF GYRATION rxm = 56 mm rxf = 52 mm rx = 108 mm
MINOR AXIS MOMENT OF INERTIA Iym = 376000 mm4 Iyf = 176000 mm4 Iy = 552000 mm4
MINOR AXIS PLASTIC MODULUS Zym = 22800 mm3 Zyf = 12500 mm3 Zy = 35300 mm3
3 3
MINOR AXIS ELASTIC MODULUS ( external ) Syem = 19200 mm Syef = 8700 mm Sye = 27900 mm3
MINOR AXIS ELASTIC MODULUS ( internal ) Syim = 10500 mm3 Syif = 5460 mm3 Syi = 15960 mm3
MINOR AXIS RADIUS OF GYRATION rym = 18 mm ryf = 13 mm ry = 31 mm
RATIO OF SECTION PROPERTIES MALE RATIO FEMALE RATIO TOTAL SECTION PROPERTY
MAJOR AXIS INERTIA RATIO RIxm = 0.56 Ixm / Ixt RIxf = 0.44 Ixf / Ixt Ixt = 6520000 mm4
MINOR AXIS INERTIA RATIO RIym = 0.68 Iym / Iyt RIyf = 0.32 Iyf / Iyt Iyt = 552000 mm4
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
PANEL DENSITY rg = 25 KN / m3
Page 21 of 81
APPLIED BENDING STRESSES POSSITIVE WL NEGATIVE WL
STRONG AXIS MOMENT ; SEE STAAD RESULT Mx+ = 6.30 KN-m Mx- = 4.10 KN-m
POSSITIVE WL BENDING STRESS ; Mx+ * RIx / Sxe Fbxm ' = 65.84 Mpa Fbxf' = 46.33 Mpa
NEGATIVE WL BENDING STRESS ; Mx- * RIx / Sxi Fbxm ' = 54.90 Mpa Fbxf' = 49.22 Mpa
Page 22 of 81
YIELDING ( l > l1 ) ; Fcy Fc1 = 170.00 Mpa Fc1 = 170.00 Mpa
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fc2 = 153.11 Mpa Fc2 = 153.11 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fc3 = 171.66 Mpa Fc3 = 171.66 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fc1 / W Fcm = 92.79 Mpa Fcm = 92.79 Mpa
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fc2 = 142.77 Mpa Fc2 = 162.76 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fc3 = 146.48 Mpa Fc3 = 204.49 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fc1 / W Fcf = 86.53 Mpa Fcf = 98.64 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 229.33 Mpa Fb2 = 229.33 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 325.18 Mpa Fb3 = 325.18 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 197.08 Mpa Fbm = 197.08 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 229.62 Mpa Fb2 = 229.62 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 326.30 Mpa Fb3 = 326.30 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbf = 197.76 Mpa Fbf = 197.76 Mpa
Page 23 of 81
LATERAL TORSIONAL BUCKLING STRESS - F.4.2.5
NOMINAL BENDING COEFFICIENT ; ( 12.5 Mmax ) / ( 2.5Mmax + 3MA + 4MB + 3MC ) - F.1.1.1 Cbn = 1.25
DISTANCE OF FLANGE CENTROID FROM SECTION CENTROID cfem = 28.78 mm cfef = 3.85 mm
EXTERNAL BENDING COEFFICIENT; IF - 0.10 < RIye < 0.9 = Cbn ; Others = 1 Cbem = 1.25 Cbef = 1.00
DISTANCE OF FLANGE CENTROID FROM SECTION CENTROID cfim = 28.78 mm cfif = 5.35 mm
INTERNAL BENDING COEFFICIENT ; IF - 0.10 < RIye < 0.9 = Cbn ; Others = 1 Cbim = 1.25 Cbif = 1.00
DISTANCE OF SHEAR CENTER TO POINT OF LOAD ( External Flange ) goe = 109.32 mm goe = 97.57 mm
DISTANCE OF SHEAR CENTER TO POINT OF LOAD ( Internal Flange ) goi = 85.12 mm goi = 96.87 mm
EXTERNAL CRITICAL MOMENT PARAMETER ; C1 * go+ - C2 * βce / 2 Uem = 87.72 Uef = 91.44
NOMINAL FLEXURAL STRENGTH FOR YIELDING ; Min ( Zx * Fcy ) , ( 1.5 Sxe * Fcy ) Mnpm = 11.88 KN-M Mnpf = 9.15 KN-M
2 2 2 2
TORSIONAL BUCKLING ; ( Cb * π * E * Iy / Lb )[U + U + 0.038*J*Lb / Iy + Cw/Iy ] Mem = 66.23 KN-M Mef = 14.37 KN-M
LTB BUCKLING STRENGTH ; IF l < Cc = Mnmb1 / W, l > Cc = Mnmb2 / W Mmbem = 6.12 Mpa Mmbef = 3.94 Mpa
ALLOWABLE LTB STRESS ; Mmbe / Sxe Fbem = 114.77 Mpa Fbef = 100.50 Mpa
Page 24 of 81
INTERNAL FLANGE ALLOWABLE LTB STRESS MALE MULLION FEMALE MULLION
2
INTERNAL COEFFICIENT OF MONOSYMMETRY ; 0.9df * [( 2Iyi/Iy )-1][1-( Iy/Ix ) ] βcim = -132.23 βcif = -165.14
INTERNAL CRITICAL MOMENT PARAMETER ; C1 * go- - C2 * βci / 2 Uim = 75.62 Uif = 89.72
NOMINAL FLEXURAL STRENGTH FOR YIELDING ; Min ( Zx * Fcy ) , ( 1.5 Sxi * Fcy ) Mnpm = 10.61 KN-M Mnpf = 9.15 KN-M
TORSIONAL BUCKLING ; ( Cb * π2 * E * Iy / Lb2 )[U + U2 + 0.038*J*Lb2 / Iy + Cw/Iy ] Mem = 64.09 KN-M Mef = 14.17 KN-M
LTB BUCKLING STRENGTH ; IF l < Cc = Mnmb1 / W, l > Cc = Mnmb2 / Wb Mmbim = 5.45 Mpa Mmbif = 3.89 Mpa
ALLOWABLE LTB STRESS ; Mmbi / Sxi Fbim = 131.08 Mpa Fbif = 105.53 Mpa
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
MINOR AXIS MOMENT OF INERTIA Iy = 376000 mm4 376000 mm4 176000 mm4 176000 mm4
TORSION CONTANT J= 556000 mm4 556000 mm4 6990 mm4 6990 mm4
BUCKLING CONSTANT INTERSECTION Cc = 79.16 Mpa 79.16 Mpa 79.16 Mpa 79.16 Mpa
NOMINAL FLEXURAL STRENGTH Mnmb = 10.09 KN-M 9.00 KN-M 6.50 KN-M 6.42 KN-M
ALLOWABLE LTB STRENGTH Mmb = 6.12 KN-M 5.45 KN-M 3.94 KN-M 3.89 KN-M
ALLOWABLE LTB STRENGTH STRESS Fb = 114.77 MPa 131.08 MPa 100.50 MPa 105.53 MPa
Page 25 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.1 ( FLANGES - UNSUPPORTED ELEMENT )
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
BUCKLING CONSTANT INTERCEPT Bp = 213.24 Mpa 213.24 Mpa 213.24 Mpa 213.24 Mpa
BUCKLING CONSTANT SLOPE Dp = 1.18 Mpa 1.18 Mpa 1.18 Mpa 1.18 Mpa
BUCKLING CONSTANT INTERSECTION Cp = 74.28 Mpa 74.28 Mpa 74.28 Mpa 74.28 Mpa
NOMINAL COMPRESSIVE STRENGTH Fc1 = 153.11 MPa 153.11 MPa 142.77 MPa 162.76 MPa
ALLOWABLE COMPRESSIVE STRESS Fc = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
SAFETY FACTOR FOR OTHER FLEXURAL LIMIT STATES Wb = 1.65 1.65 1.65 1.65
MODULUS OF ELASTICITY E= 70000 Mpa 70000 Mpa 70000 Mpa 70000 Mpa
BUCKLING CONSTANT INTERCEPT Bbr = 313.19 Mpa 313.19 Mpa 313.19 Mpa 313.19 Mpa
BUCKLING CONSTANT SLOPE Dbr = 2.57 Mpa 2.57 Mpa 2.57 Mpa 2.57 Mpa
BUCKLING CONSTANT INTERSECTION Cbr = 81.38 Mpa 81.38 Mpa 81.38 Mpa 81.38 Mpa
NOMINAL BUCKLING STRENGTH Fb1 = 325.18 MPa 325.18 MPa 326.30 MPa 326.30 MPa
ALLOWABLE BUCKLING STRESS Fb = 197.08 MPa 197.08 MPa 197.76 MPa 197.76 MPa
COMPRESSIVE STRESS - B.5.4.1 Fc = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
LOCAL BUCKLING - B.5.5.1 Fb = 197.08 MPa 197.08 MPa 197.76 MPa 197.76 MPa
LATERAL TORSIONAL BUCKLING - F.4.2.5 Fb = 114.77 MPa 131.08 MPa 100.50 MPa 105.53 MPa
APPLIED STRESS Fb' = 65.84 MPa 54.90 MPa 46.33 MPa 49.22 MPa
GOVERNING ALLOWABLE STRESS Fb = 92.79 MPa 92.79 MPa 86.53 MPa 98.64 MPa
RESULT OK OK OK OK
Page 26 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 25.90 mm
Page 27 of 81
Calc. by :
KIPP
BP
Chk. by :
MID - DUMMY MULLION
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETERS :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 28 of 81
SECTION PROPERTIES -SECTION WIZARD
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
PANEL DENSITY rg = 25 KN / m3
Page 29 of 81
INTERNAL ELEMENT UNDER UNIFORM COMPRESSION - WEB - ( B.5.4.2 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 1.6 * Dp * l Fbxen2 = 195.49 Mpa Fbxin2 = 163.12 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 1.6 * l Fbxen3 = 581.52 Mpa Fbxin3 = 205.93 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 103.03 Mpa Fbxi = 98.86 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 264.70 Mpa Fb2 = 264.70 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 562.39 Mpa Fb3 = 562.39 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 340.84 Mpa Fbm = 340.84 Mpa
Page 30 of 81
SUMMARY OF LOCAL BUCKLING STRESS - B.5.5.1 ( WEB - SUPPORTED ELEMENT )
RESULT OK OK
WL DEFLECTION dx = 15.88 mm
Page 31 of 81
Calc. by :
KIPP
BP
Chk. by :
STACK JOINT TRANSOM
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETER :
MECHANICAL PROPERTIES :
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 102 Mpa
TENSION COEFFICIENT kt = 1
BUCKLING CONSTANTS
MEMBER BUCKLING
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 32 of 81
SECTION PROPERTIES -SECTION WIZARD HEAD TRANSOM SILL TRANSOM
RATIO OF SECTION HEAD TRANSOM RATIO SILL TRANSOM RATIO TOTAL SECTION PROPERTY
MAJOR AXIS NERTIA RATIO R1 = 0.53 Ix1 / IxT R2 = 0.47 Ix2 / IxT IxT = 9439375 mm4
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
SB POINT LOAD AT SILL TRANSOM ; 1.25 * t * r * da * Lm / 2 - With 25% Accesories Py= 0.40 KN
TOTAL WL MOMENT ; Mxa + Mxb Mx+ = 0.31 KN-m Mx- = -0.21 KN-m
HEAD WL BENDING STRESS ; Mx+ R / Sx Fbxf' = 2.79 Mpa Fbxf' = -1.78 Mpa
SILL WL BENDING STRESS ; Mx+ R / Sx Fbxf' = 3.22 Mpa Fbxf' = -1.60 Mpa
Page 33 of 81
SECTION ELEMENT OF FLANGES
OUTSTAND ELEMENT UNDER UNIFORM COMPRESSION - FLANGE - ( B.5.4.1 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 5.0 * Dp * l Fbxen2 = 141.46 Mpa Fbxin2 = 123.14 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 5.0 * l Fbxen3 = 143.80 Mpa Fbxin3 = 114.56 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 85.73 Mpa Fbxi = 69.43 Mpa
Page 34 of 81
SLENDERNESS OF ELEMENT ;d/t le = 26.26 li = 26.26
LOWER SLENDERNES LIMIT ; ( Bbr -1.5 Fcy ) / ( m*Dbr ) le1 = 14.08 li1 = 14.08
YIELDING ( l > l1 ) ; 1.5 * Fcy Fbxen1 = 255.00 Mpa Fbxin1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr * l ] Fbxen2 = 204.66 Mpa Fbxin2 = 204.66 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * l ] Fbxen3 = 604.15 Mpa Fbxin3 = 604.15 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 124.04 Mpa Fbxi = 124.04 Mpa
LOWER SLENDERNES LIMIT ; ( Bbr -1.5 Fcy ) / ( m*Dbr ) le1 = 14.96 li1 = 14.96
YIELDING ( l > l1 ) ; 1.5 * Fcy Fbxen1 = 255.00 Mpa Fbxin1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr * l ] Fbxen2 = 150.32 Mpa Fbxin2 = 150.32 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * l ] Fbxen3 = 378.90 Mpa Fbxin3 = 378.90 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 229.64 Mpa Fbxi = 229.64 Mpa
WL DISPLACEMENT ABOVE ; (PWLsxa L4)/(1920 E IxT )*(25 - 40(aa/L)2 + 16(aa/L)4) dxa = 0.06 mm
4
WL DISPLACEMENT BELOW ; (PWLsxb L )/(1920 E IxT )*(25 - 40(ab/L)2 + 16(ab/L)4) dxb = 0.09 mm
Page 35 of 81
DESIGN OF MEMBER FOR FLEXURE
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.44 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.44 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.40 KN-M
APPLIED LOADS
Page 36 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.1 ( FLANGES - OUTSTAND ELEMENT )
RESULT OK OK
Page 37 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 0.15 mm
DL DEFLECTION dy = 0.60 mm
Page 38 of 81
Calc. by :
KIPP
BP
Chk. by :
INTERMEDIATE TRANSOM
YM
Rev. No. 0
PMU
Date: 2023-07-21
PARAMETER :
BUCKLING CONSTANTS
MEMBER BUCKLING
BUCKLING CONSTANT INTERCEPT ; 1.3 * Fcy [ 1 + ( Fcy / 340 * k )1/3 ] Bbr= 313.19 Mpa
Page 39 of 81
SECTION PROPERTIES -SECTION WIZARD
LOADING ANALYSIS
TYPICAL ZONE SERVICE DESIGN WIND PRESSURE Q= 0.97 kPa Q= -0.65 kPa
DEAD LOAD
SB POINT LOAD AT SILL TRANSOM ; 1.25 * t * r * da * Lm / 2 - With 25% Accesories Py= 2.04 KN
Page 40 of 81
TOTAL WL MOMENT ; Mxa + Mxb Mx+ = 0.41 KN-m Mx- = -0.28 KN-m
INTERNAL ELEMENT UNDER UNIFORM COMPRESSION - WEB - ( B.5.4.2 ) EXTERNAL FLANGE INTERNAL FLANGE
ELASTIC BUCKLING ( l1 > l > l2 ) ; Bp - 1.6 * Dp * l Fbxen2 = 195.49 Mpa Fbxin2 = 163.12 Mpa
POST BUCKLING ( l < l2 ) ; K2 * Bp * E / 1.6 * l Fbxen3 = 581.52 Mpa Fbxin3 = 205.93 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fbx / W Fbxe = 103.03 Mpa Fbxi = 98.86 Mpa
YIELDING ( l > l1 ) ; 1.5 * Fcy Fb1 = 255.00 Mpa Fb1 = 255.00 Mpa
INELASTIC BUCKLING ( l1 > l > l2 ) ; [ Bbr - m * Dbr ( b / t ) ] Fb2 = 197.13 Mpa Fb2 = 197.13 Mpa
ELASTIC BUCKLING ( l < l2 ) ; [ k2 (Bbr E) ] / [ 0.67 * (h / t) ] Fb3 = 562.39 Mpa Fb3 = 562.39 Mpa
ALLOWABLE LOCAL BUCKLING STRESS ; Fb2 / W Fbm = 340.84 Mpa Fbm = 340.84 Mpa
Page 41 of 81
SUMMARY OF COMPRESSIVE STRESS - B.5.4.2 ( WEB - SUPPORTED ELEMENT )
RESULT OK OK
Page 42 of 81
DEFLECTION SUMMARY DEFLECTION RESULT
WL DEFLECTION dx = 0.18 mm
DL DEFLECTION dy = 1.25 mm
Page 43 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
FIXING ANALYSIS
Page 44 of 81
CHECK FOR ALUMINUM PRESSURE PLATE
+ / - Fz
SECTION PROPERTIES
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 84.00 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = -62.61 KN-M
Page 45 of 81
STRONG AXIS YIELDING AND RUPTURE
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 1.44 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.16 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.16 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.16 KN-M
Page 46 of 81
CHECK FOR ALUMINUM GLASS CHAIR Fy
22.3m
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
SECTION PROPERTIES
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 5.51 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = -1.64 KN-M
Page 47 of 81
STRONG AXIS YIELDING AND RUPTURE
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.21 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.06 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.06 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.05 KN-M
Page 48 of 81
CHECK FOR ALUMINUM HOOK BRACKET PLATE
Fy
+ / - Fz
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
CHECK SECTION 1
SECTION PROPERTIES
Page 49 of 81
STRONG AXIS ELASTIC MODULUS ; t * b2 / 6 Sx = 621 mm3
2
WEAK AXIS ELASTIC MODULUS ;b*t /6 Sy = 322 mm3
-1
WEAK AXIS RADIUS OF GYRATION ; Iy * A ry = 1.45 mm
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 0.22 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = 0.12 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 0.85 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.12 KN-M
Page 50 of 81
WEAK AXIS YIELDING AND RUPTURE
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.07 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.07 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.06 KN-M
TENSION LOADS
SHEAR LOAD
Page 51 of 81
CHECK SECTION 2
Fy
+/- Fz
SECTION PROPERTIES
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
TENSION COEFFICIENT kt = 1
Page 52 of 81
LATERAL TORSIONAL BUCKLING
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 0.60 KN-M
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π2 * E * lb * Sx ) / ( Cc3 * Wby ) Mnpx1 = 0.33 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 4.50 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 0.33 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 0.23 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 0.23 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 0.21 KN-M
APPLIED LOADS
TENSION LOADS
SHEAR LOAD
Page 53 of 81
CHECK FOR ALUMINUM FLOOR BRACKET
Fy
+/- Fz
SHEAR ULTIMATE STRENGTH ; table A.3.1 - 0.6 * Ftu Fsu = 156 Mpa
SHEAR YIELD STRENGTH ; table A.3.1 - 0.6 * Fty Fsy = 144 Mpa
SECTION PROPERTIES
TENSION COEFFICIENT kt = 1
TENSION COEFFICIENT kt = 1
Page 54 of 81
ALLOWABLE SHEAR STRENGTH FOR YIELDING ; Fsy / Wvy Rvy = 96.00 Mpa
ALLOWABLE SHEAR STRENGTH FOR RUPTURE ; Fsu / Wvr * kt Rvr = 80.00 Mpa
GOVERNING ALLOWABLE SHEAR STRESS ; MIN ( Rvy , Rvr ) Rvall = 80.00 Mpa
BENDING COEFFICIENT Cb = 1
TENSION COEFFICIENT kt = 1
NOMINAL FLEXURAL YIELDING STRENGTH ; MIN ( Zx * Fcy, 1.5 * Sx * Fty, 1.5 * Sx * Fcy ) Mnpx = 50.17 KN-M
2 3
INELASTIC BUCKLING STRENGTH ; Mnpx * ( 1 - lby / Cc ) + ( π * E * lb * Sx ) / ( Cc * Wby ) Mnpx1 = 20.70 KN-M
2 2
ELASTIC BUCKLING STRENGTH ; π * E * Sx / l Mnpx2 = 41.17 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( MbxLT, Mbxy, Mbxr ) Mbx = 20.70 KN-M
ALLOWABLE COMPRESSIVE YIELDING STRENGTH ; 1.5 * Fcy * Sy / Wby Mbyc = 2.13 KN-M
ALLOWABLE TENSILE YIELDING STRENGTH ; 1.5 * Fty * Sy / Wby Mbyt = 2.13 KN-M
GOVERNING ALLOWABLE STRESS ; MIN ( Mbyy, Mbyr, Mbcy, Mbyt ) Mby = 1.95 KN-M
Page 55 of 81
HORIZONTAL FORCE DUE TO POSITIVE WL Fz+ = 11.46 KN
TENSION LOADS
SHEAR LOAD
DIRECT SHEAR
Page 56 of 81
CHECK #12 SS A4-70 PRESSURE PLATE SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.18 inch 4.60 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.19 inch 4.70 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.21 inch 5.28 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.19 inch 4.90 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.01 inch2 14.96 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.02 inch 2
22.79 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 57 of 81
ALLOWABLE SHEAR STRESS ; 0.75 Fy /3 ; ( with 1.33 safety factor ) Fv1 = 47.63 Mpa
ALLOWABLE SHEAR STRESS ; 0.4 Fu / ; ( with 2.5 safety factor ) Fv1 = 36.95 Mpa
ALLOWABLE SHEAR STRESS ; Fy /3 ; ( with out safety factor ) Fv = 63.51 Mpa
APPLIED LOAD
TENSILE LOAD
Page 58 of 81
ANALYSIS OF BRACKETRY FIXINGS
CHECK M12 STAINLESS STEEL BOLT MULLION FASTENER
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.43 inch 11.02 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.44 inch 11.28 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.49 inch 12.40 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.46 inch 11.61 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.06 inch2 38.91 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.11 inch2 68.88 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 59 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION SLIDE BRACKET
SHEAR LOAD
ECCENTRICITY OF DL x= 44 mm
Page 60 of 81
SHEAR REACTION / BOLT ; Fy / n Vy = 3.8 KN
BEARING
Page 61 of 81
CHECK 1/4 SS A4-70 STACK JOINT HEAD TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 62 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL ECCENTRICITY ex = 50 mm
BEARING
Page 63 of 81
CHECK 1/4 SS A4-70 STACK JOINT SILL TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 64 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL SHEAR ; ww * H / 2 * n Vw = 0.30 KN
GLASS DENSITY r= 25 KN / m3
NUMBER OF SB n= 2 nos
WL ECCENTRICITY ex = 11 mm
DL ECCENTRICITY ey = 82 mm
Page 65 of 81
BEARING
Page 66 of 81
CHECK 1/4 SS A4-70 INTERMEDIATE TRANSOM SCREW FIXING
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.21 inch 5.26 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.21 inch 5.41 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.24 inch 6.12 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.22 inch 5.64 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.02 inch2 17.59 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.03 inch2 28.38 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 67 of 81
ALLOWABLE BEARING LOAD OF CONNECTED PLY MULLION
WL SHEAR ; ww * H / 2 * n Vw = 1.84 KN
GLASS DENSITY r= 25 KN / m3
NUMBER OF SB n= 2 nos
DL ECCENTRICITY ey = 82 mm
Page 68 of 81
BEARING
Page 69 of 81
CHECK M16 STAINLESS STEE LHEX BOLT SOCKET COUNTERSUNK HEAD
FASTENER PROPERTY
MAXIMUM MINOR Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 KNMAX = 0.55 inch 13.87 mm
MINIMUM PITCH Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ESMIN = 0.56 inch 14.20 mm
MINIMUM MAJOR Փ OF EXTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 DSMIN = 0.61 inch 15.52 mm
MAXIMUM PITCH Փ OF INTERNAL THREAD ; TABLE 4 AAMA TIR A9 - 14 ENMAX = 0.57 inch 14.55 mm
EXTERNAL THREAD STRIPPING AREA ; π * ( KNMAX ) * [ 1/2N + 3 * ( ( ESMIN ) - ( KNMAX ) ] TSA ( E ) = 0.09 inch2 50.87 mm2
INTERNAL THREAD STRIPPING AREA ; π * ( DSMIN ) * [ 1/2N + 3 * ( ( DSMIN ) - ( KNMAX ) ] TSA ( I ) = 0.16 inch 2
94.10 mm2
MINIMUM ULTIMATE TENSILE STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fu = 100000 psi 690 Mpa
MINIMUM TENSILE YIELD STRENGTH ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fy = 65000 psi 448 Mpa
ALLOWABLE TENSILE STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Ft = 40000 psi 276 Mpa
ALLOWABLE SHEAR STRESS ; TABLE 11 - Alloy 1,2 & 3 - Condition CW Fv = 27745 psi 191 Mpa
Page 70 of 81
ALLOWABLE TENSILE AND SHEAR LOADS OF FASTENER
Page 71 of 81
APPLIED LOADS POSSITIVE WL NEGATIVE WL
WL ECCENTRICITY ex = 42 mm
SHEAR LOAD
TENSILE LOAD
BEARING
Page 72 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 23/5/2023
Checked by Revision Job No
Subject COVER
CN 0
SECTION PROPERTIES
Page 73 of 81
z
y MALE MULLION
v u
Geometric properties of the cross-section
A Sectional area
Parameter Value
1.43e+3 mm^2
Av,y Conventional shearing area along Y-axis 3.03e+2 mm^2
Av,z Conventional shearing area along Z-axis 5.45e+2 mm^2
Angle between Y-Z and U-V axes 0.542 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 4.54e+6 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 4.7e+5 mm^4
It Torsional moment of inertia (St. Venant) 5.56e+5 mm^4
Iw Warping constant 1.01e+9 mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 5.64e+1 mm
iz Radius of gyration about axis parallel to Z passing through centroid 1.81e+1 mm
Wu+ Elastic modulus about U-axis (+ve extreme) 5.33e+4 mm^3
Wu- Elastic modulus about U-axis (-ve extreme) 4.16e+4 mm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 1.92e+4 mm^3
Wv- Elastic modulus about V-axis (-ve extreme) 1.05e+4 mm^3
Wpl,u Plastic modulus about axis parallel to U-axis 6.99e+4 mm^3
Wpl,v Plastic modulus about axis parallel to V-axis 2.28e+4 mm^3
Iu Moment of inertia about U-axis 4.54e+6 mm^4
Iv Moment of inertia about V-axis 4.7e+5 mm^4
iu Radius of gyration about U-axis 5.64e+1 mm
iv Radius of gyration about V-axis 1.81e+1 mm
au+ Centroid to edge of compression zone along +ve U-axis 1.35e+1 mm
au- Centroid to edge of compression zone along -ve U-axis 7.39 mm
av+ Centroid to edge of compression zone along +ve V-axis 3.73e+1 mm
av- Centroid to edge of compression zone along -ve V-axis 2.92e+1 mm
yM Distance to centroid along Y-axis -4.78e+1 mm
zM Distance to centroid along Z-axis -1.19e+2 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis -2.49e+1 mm
Zb Distance to shear centre along Z-axis -9.14e+1 mm
P Perimeter 9.2e+2 mm
Pi Internal perimeter 2.49e+2 mm
Pe External perimeter 6.7e+2 mm
I1 Moment of inertia about Y-axis 4.54e+6 mm^4
I2 Moment of inertia about Z-axis 4.7e+5 mm^4
I12 Product of inertia about the centroid -3.85e+4 mm^4
Ip Polar moment of inertia about centroid 5.01e+6 mm^4
ip Polar radius of gyration about centroid 5.93e+1 mm
Wp Polar elastic modulus about centroid 4.57e+4 mm^3
yp Distance to equal area axis along Y-axis -5.13 mm
zp Distance to equal area axis along Z-axis -1.07e+1 mm
up Distance to equal area axis along U-axis -5.27 mm
vp Distance to equal area axis along V-axis 8.66e-1 mm
Page 74 of 81
z
y FEMALE MULLION
vu
Geometric properties of the cross-section
A Sectional area
Parameter Value
1.08e+3 mm^2
Av,y Conventional shearing area along Y-axis 2.09e+2 mm^2
Av,z Conventional shearing area along Z-axis 4.13e+2 mm^2
Angle between Y-Z and U-V axes 5.748 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 3.61e+6 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 2.2e+5 mm^4
It Torsional moment of inertia (St. Venant) 6.99e+3 mm^4
Iw Warping constant 4.94e+8 mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 5.77e+1 mm
iz Radius of gyration about axis parallel to Z passing through centroid 1.42e+1 mm
Wu+ Elastic modulus about U-axis (+ve extreme) 3.72e+4 mm^3
Wu- Elastic modulus about U-axis (-ve extreme) 3.69e+4 mm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 8.7e+3 mm^3
Wv- Elastic modulus about V-axis (-ve extreme) 5.46e+3 mm^3
Wpl,u Plastic modulus about axis parallel to U-axis 5.38e+4 mm^3
Wpl,v Plastic modulus about axis parallel to V-axis 1.25e+4 mm^3
Iu Moment of inertia about U-axis 3.65e+6 mm^4
Iv Moment of inertia about V-axis 1.85e+5 mm^4
iu Radius of gyration about U-axis 5.8e+1 mm
iv Radius of gyration about V-axis 1.31e+1 mm
au+ Centroid to edge of compression zone along +ve U-axis 8.03 mm
au- Centroid to edge of compression zone along -ve U-axis 5.04 mm
av+ Centroid to edge of compression zone along +ve V-axis 3.43e+1 mm
av- Centroid to edge of compression zone along -ve V-axis 3.41e+1 mm
yM Distance to centroid along Y-axis -1.85e+1 mm
zM Distance to centroid along Z-axis -1.07e+2 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis -4.73e+1 mm
Zb Distance to shear centre along Z-axis -9.05e+1 mm
P Perimeter 6.85e+2 mm
Pi Internal perimeter 0 mm
Pe External perimeter 6.85e+2 mm
I1 Moment of inertia about Y-axis 3.61e+6 mm^4
I2 Moment of inertia about Z-axis 2.2e+5 mm^4
I12 Product of inertia about the centroid -3.45e+5 mm^4
Ip Polar moment of inertia about centroid 3.83e+6 mm^4
ip Polar radius of gyration about centroid 5.95e+1 mm
Wp Polar elastic modulus about centroid 3.84e+4 mm^3
yp Distance to equal area axis along Y-axis -2.21 mm
zp Distance to equal area axis along Z-axis -5.43 mm
up Distance to equal area axis along U-axis -1.09 mm
vp Distance to equal area axis along V-axis -4.03 mm
Page 75 of 81
z
y DUMMY MULLION / INTERMEDIATE
TRANSOM
Geometric properties of the cross-section
Parameter Value
A Cross sectional area 1682.15 mm^2
Av,y Conventional shearing area along Y-axis 422.46 mm^2
Av,z Conventional shearing area along Z-axis 699.29 mm^2
Angle between Y-Z and U-V axes -0.003 deg
Iy Moment of inertia about axis parallel to Y passing through centroid 5126299.54 mm^4
Iz Moment of inertia about axis parallel to Z passing through centroid 2354988.96 mm^4
It Torsional moment of inertia (St. Venant) 4433686.19 mm^4
Iw Warping constant 317782308.3mm^6
iy Radius of gyration about axis parallel to Y passing through centroid 55.2 mm
iz Radius of gyration about axis parallel to Z passing through centroid 37.42 mm
Wu+ Max elastic modulus about U-axis 66493.88 mm^3
Wu- Min elastic modulus about U-axis 70630.14 mm^3
Wv+ Max elastic modulus about V-axis 51903.03 mm^3
Wv- Min elastic modulus about V-axis 51905.23 mm^3
Wpl,u Plastic modulus about U-axis 84677.18 mm^3
Wpl,v Plastic modulus about V-axis 58934.7 mm^3
Iu Moment of inertia about U-axis 5126299.55 mm^4
Iv Moment of inertia about V-axis 2354988.95 mm^4
iu Radius of gyration about U-axis 55.2 mm
iv Radius of gyration about V-axis 37.42 mm
au+ Centroid to edge of compression zone along +ve U-axis 30.86 mm
au- Centroid to edge of compression zone along -ve U-axis 30.86 mm
av+ Centroid to edge of compression zone along +ve V-axis 39.53 mm
av- Centroid to edge of compression zone along -ve V-axis 41.99 mm
yM Distance to centroid along Y-axis 0 mm
zM Distance to centroid along Z-axis 0.01 mm
Sw Sectorial static moment 0 mm^4
Yb Distance to shear centre along Y-axis 0.01 mm
Zb Distance to shear centre along Z-axis 2.53 mm
P Perimeter 1088.3 mm
Pi Internal perimeter 540.43 mm
Pe External perimeter 547.88 mm
I1 Moment of inertia about Y-axis 5126299.63 mm^4
I2 Moment of inertia about Z-axis 2354988.97 mm^4
I12 Product of inertia about the centroid 147.02 mm^4
Ip Polar moment of inertia about centroid 7481288.5 mm^4
ip Polar radius of gyration about centroid 66.69 mm
Wp Polar elastic modulus about centroid 0.93 mm
Page 76 of 81
z
Page 77 of 81
z
Page 78 of 81
Project KIPP PROJECT INHABIT
Made by Date Page
Location 75 CANAL STREET WEST, BRONX NY, USA 10451
BP 12/7/2023
Checked by Revision Job No
Subject COVER
CN 0
Page 79 of 81
Job Title:
Client:
Engineer:
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 20-Apr-23
END JOB INFORMATION
INPUT WIDTH 79
UNIT MMS NEWTON
JOINT COORDINATES
1 25000 0 0; 2 25000 720 0; 4 25000 5270 0; 5 25000 6005 0; 6 25000 6250 0;
7 25000 12983.5 0; 10 25000 12015 0; 11 25000 12748.5 0;
MEMBER INCIDENCES
1 1 2; 3 2 4; 4 4 5; 5 5 6; 6 6 10; 9 10 11; 10 11 7;
DEFINE MATERIAL START
ISOTROPIC ALUMINUM
E 68947.6
POISSON 0.33
DENSITY 2.66018e-05
ALPHA 2.3e-05
DAMP 0.03
ISOTROPIC STEEL
E 205000
POISSON 0.3
DENSITY 7.68195e-05
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH RY 1.5 RT 1.2
ISOTROPIC STEEL_275_NMM2
E 205000
POISSON 0.3
DENSITY 7.7e-05
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH FY 275 FU 410 RY 1.5 RT 1.2
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
1 3 TO 6 9 10 PRIS AX 2510 IX 562990 IY 552000 IZ 6.52e+06
CONSTANTS
BETA 90 ALL
MATERIAL ALUMINUM ALL
SUPPORTS
5 11 FIXED BUT MX MZ
1 4 10 FIXED BUT FY MX MZ
MEMBER RELEASE
6 START FX MY MZ
LOAD 1 LOADTYPE Dead TITLE DL
MEMBER LOAD
Page 80 of 81
Job Title:
Client:
Engineer:
1 3 TO 6 9 10 UNI GY -1.16
SELFWEIGHT Y -1
LOAD 2 LOADTYPE Wind TITLE WL - SERVICE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y 1.1
LOAD 3 LOADTYPE Wind TITLE WL +SERVICE
MEMBER LOAD
1 3 TO 6 9 10 UNI GZ -1.7
LOAD 4 LOADTYPE Wind TITLE WL - ULTIIMATE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y 1.9
LOAD 5 LOADTYPE Wind TITLE WL + ULTIMATE
MEMBER LOAD
1 3 TO 6 9 10 UNI Y -2.8
PERFORM ANALYSIS
FINISH
Page 81 of 81