LOCATION: OFFICE

ILLUMINATION CALCULATION ACCORDING TO BZ- METHOD, IES


ITEM NO. DESCRIPTION SYMBOL FORMULA/UNIT VALUES FINAL
1 ROOM WIDTH W m 3.75
2 ROOM LENGTH L m 6.2
3 ROOM AREA Af L*W 23.25
4 TOTAL HEIGHT Ht m 3
5 SUSPENSION HEIGHT Hs m 0
6 MOUNTING HEIGHT Hm Ht-Hs-0.8 2.15
7 ROOM INDEX Kr L*W / Hm(L+W) 1.09
8 REFLECTANCE CEILING Rc 0.7
WALLS Rw 0.5
FLOOR Rf 0.3
9 NO. OF LIGHTING SOURCES n 1
PER LUMINAIRE
10 UTILIZATION FACTOR Uf 0.55
11 REDUCTION FACTOR k 1
12 DEPRECIATION FACTOR f SEE TABLE 1.37
13 TYPE OF LAMP SEE LAMP DATA 36W LED
14 LUMINOUS FLUX PER LAMP Lm SEE LAMP DATA 5200
15 WANTED ILLUMINANCE E LUX 500
16 NUMBER OF LUMINAIRES N E*Af*f / Lm*n*Uf*k 5.57 6
17 NUMBER OF LUMINAIRES SQR. ROOT OF 3.03 3
ALONG (L*N / W)
18 NUMBER OF LUMINAIRES SQR. ROOT OF 1.80 2
ACROSS (W*N / L)
19 CONTROL OF ILLUMINANCE E N*Lm*n*Uf*k /Af*f 538.73

TABLE FOR DEPRECIATION FACTORS ( f )


THE LABELLED VALUES ARE FOR Rw =0.3, CLEANING ONCE A YEAR.
FOR Rw = 0.5 THE VALUES MUST BE INCREASED BY 0.04
LUMINAIRE TYPE SURROUNDINGS TUBES/INCANDESCENT
OFFICES OTHERS Rw =0.5
OPEN LUMINAIRE CLEAN 1.27 1.33 (+0.04)
SUBURBS 1.33 1.42 (+0.04)
CENTER OF TOWN 1.42 1.48 (+0.04)
DIRTY 1.48 1.54 (+0.04)
VENTILATED THROUGH CLEAN 1.27 1.27 (+0.04)
REFLECTOR SUBURBS 1.33 1.33 (+0.04)
CENTER OF TOWN 1.42 1.42 (+0.04)
DIRTY 1.48 1.48 (+0.04)
DUSTIGHT LUMINAIRE CLEAN 1.27 1.27 (+0.04)
SUBURBS 1.33 1.33 (+0.04)
CENTER OF TOWN 1.42 1.42 (+0.04)
DIRTY 4.48 1.18 (+0.04)
NON- VENTILATED LUMINAIRE CLEAN 1.33 1.5 (+0.04)
WITH PLASTIC DIFFUSER SUBURBS 1.39 1.61 (+0.04)
CENTER OF TOWN 1.54 1.69 (+0.04)
DIRTY 1.61 1.78 (+0.04)
VENTILATED LUMINAIRE WITH CLEAN 1.33 1.45 (+0.04)
LOUVER OR PLASTIC DIFFUSER SUBURBS 1.39 1.54 (+0.04)
CENTER OF TOWN 1.48 1.61 (+0.04)
DIRTY 1.54 1.69 (+0.04)
RECESSED LUMINAIRE WITH CLEAN 1.27 1.39 (+0.04)
LOUVER OR PLASTIC DIFFUSER SUBURBS 1.33 1.48 (+0.04)
CENTER OF TOWN 1.42 1.54 (+0.04)
DIRTY 1.48 1.61 (+0.04)