This document contains an illumination calculation for an office space according to the BZ- method. It provides details on the room dimensions and area, mounting height of the luminaires, reflectance of surfaces, lamp details, desired illuminance level, and calculates the number of 36W LED luminaires needed to provide 500 lux of illuminance in the space. It determines 3 luminaires are needed along the length and 2 along the width of the room to meet the illuminance requirement. It also includes a table of depreciation factors for different luminaire types and surroundings.
This document contains an illumination calculation for an office space according to the BZ- method. It provides details on the room dimensions and area, mounting height of the luminaires, reflectance of surfaces, lamp details, desired illuminance level, and calculates the number of 36W LED luminaires needed to provide 500 lux of illuminance in the space. It determines 3 luminaires are needed along the length and 2 along the width of the room to meet the illuminance requirement. It also includes a table of depreciation factors for different luminaire types and surroundings.
This document contains an illumination calculation for an office space according to the BZ- method. It provides details on the room dimensions and area, mounting height of the luminaires, reflectance of surfaces, lamp details, desired illuminance level, and calculates the number of 36W LED luminaires needed to provide 500 lux of illuminance in the space. It determines 3 luminaires are needed along the length and 2 along the width of the room to meet the illuminance requirement. It also includes a table of depreciation factors for different luminaire types and surroundings.
ILLUMINATION CALCULATION ACCORDING TO BZ- METHOD, IES
ITEM NO. DESCRIPTION SYMBOL FORMULA/UNIT VALUES FINAL 1 ROOM WIDTH W m 3.75 2 ROOM LENGTH L m 6.2 3 ROOM AREA Af L*W 23.25 4 TOTAL HEIGHT Ht m 3 5 SUSPENSION HEIGHT Hs m 0 6 MOUNTING HEIGHT Hm Ht-Hs-0.8 2.15 7 ROOM INDEX Kr L*W / Hm(L+W) 1.09 8 REFLECTANCE CEILING Rc 0.7 WALLS Rw 0.5 FLOOR Rf 0.3 9 NO. OF LIGHTING SOURCES n 1 PER LUMINAIRE 10 UTILIZATION FACTOR Uf 0.55 11 REDUCTION FACTOR k 1 12 DEPRECIATION FACTOR f SEE TABLE 1.37 13 TYPE OF LAMP SEE LAMP DATA 36W LED 14 LUMINOUS FLUX PER LAMP Lm SEE LAMP DATA 5200 15 WANTED ILLUMINANCE E LUX 500 16 NUMBER OF LUMINAIRES N E*Af*f / Lm*n*Uf*k 5.57 6 17 NUMBER OF LUMINAIRES SQR. ROOT OF 3.03 3 ALONG (L*N / W) 18 NUMBER OF LUMINAIRES SQR. ROOT OF 1.80 2 ACROSS (W*N / L) 19 CONTROL OF ILLUMINANCE E N*Lm*n*Uf*k /Af*f 538.73
TABLE FOR DEPRECIATION FACTORS ( f )
THE LABELLED VALUES ARE FOR Rw =0.3, CLEANING ONCE A YEAR. FOR Rw = 0.5 THE VALUES MUST BE INCREASED BY 0.04 LUMINAIRE TYPE SURROUNDINGS TUBES/INCANDESCENT OFFICES OTHERS Rw =0.5 OPEN LUMINAIRE CLEAN 1.27 1.33 (+0.04) SUBURBS 1.33 1.42 (+0.04) CENTER OF TOWN 1.42 1.48 (+0.04) DIRTY 1.48 1.54 (+0.04) VENTILATED THROUGH CLEAN 1.27 1.27 (+0.04) REFLECTOR SUBURBS 1.33 1.33 (+0.04) CENTER OF TOWN 1.42 1.42 (+0.04) DIRTY 1.48 1.48 (+0.04) DUSTIGHT LUMINAIRE CLEAN 1.27 1.27 (+0.04) SUBURBS 1.33 1.33 (+0.04) CENTER OF TOWN 1.42 1.42 (+0.04) DIRTY 4.48 1.18 (+0.04) NON- VENTILATED LUMINAIRE CLEAN 1.33 1.5 (+0.04) WITH PLASTIC DIFFUSER SUBURBS 1.39 1.61 (+0.04) CENTER OF TOWN 1.54 1.69 (+0.04) DIRTY 1.61 1.78 (+0.04) VENTILATED LUMINAIRE WITH CLEAN 1.33 1.45 (+0.04) LOUVER OR PLASTIC DIFFUSER SUBURBS 1.39 1.54 (+0.04) CENTER OF TOWN 1.48 1.61 (+0.04) DIRTY 1.54 1.69 (+0.04) RECESSED LUMINAIRE WITH CLEAN 1.27 1.39 (+0.04) LOUVER OR PLASTIC DIFFUSER SUBURBS 1.33 1.48 (+0.04) CENTER OF TOWN 1.42 1.54 (+0.04) DIRTY 1.48 1.61 (+0.04)