TECHNICAL SCHEDULES

REF. DESCRIPTION PARTICULARS


UNITS
As specified As offered

1.00 Floor Distribution board,


Distribution Boards

1.01 Panel Enclosure


1.02 Manufacturer
1.03 Dimension shall be suit to the alloted
mxmxm
space
1.04 Material cold rolled electro
galvanized sheet steel
1.05 Thickness mm Not less than 2 mm
1.06 Finish Powder coated
1.07 Rated Insulated Voltage V
1.08 Ingress of Protection Not less than IP 54
1.09 Method of installation
1.10 Colour
1.11 Cable Connection
1.12 Incoming Cables Bottom of the panel
1.13 Outgoing Cables Top of the panel
1.14 Internal separation sheet thickness mm Not less than 1 mm
1.15 Internal separation
1.16 Mounting method sunk/Surface
1.17 Applicable standard BS EN 60670, BS EN
60529, IEC 60439-1

2.00 Common area consumer units


2.01 Panel Enclosure
2.02 Manufacturer
2.03 Dimension mxmxm
2.04 Material cold rolled electro
galvanized sheet steel
2.05 Thickness mm
2.06 Finish
2.07 Rated Insulated Voltage V
2.08 Ingress of Protection Not less than IP 54
2.09 Method of installation
2.10 Colour
2.11 Cable Connection
2.12 Incoming Cables Bottom of the panel
2.13 Outgoing Cables Top of the panel
2.14 Mounting method sunk
2.15 Applicable standard BS EN 60670, BS EN
60529

3.1 MCCB
3.1.01 Make
3.1.02 Model
3.1.03 Country of origine
3.1.04 No. of poles 4
3.1.05 Rated current A 63
3.1.06 Rated service voltage V 400
3.1.07 Rated insulation voltage V
1
REF. DESCRIPTION PARTICULARS
UNITS
As specified As offered
3.1.08 Rated impulse withstand voltage kV
3.1.09 Breaking capacity kA 50
3.1.10 Trip unit adjustment range
3.1.10.1 Thermal x In
3.1.10.2 Magnetic x In
3.1.11 Applicable standard BS EN 60947-2

3.2 MCCB Incoming Breaker


3.2.01 Make
3.2.02 Model
3.2.03 Country of origine
3.2.04 No. of poles 4
3.2.05 Rated current A 32
3.2.06 Rated service voltage V 400
3.2.07 Rated insulation voltage V
3.2.08 Rated impulse withstand voltage kV
3.2.09 Breaking capacity kA 36,25
3.2.10 Trip unit adjustment range
3.2.10.1 Thermal x In
3.2.10.2 Magnetic x In
3.2.11 Applicable standard BS EN 60947-2

3.3 MCB
3.3.01 Make
3.3.02 Model
3.3.03 Country of origine
3.3.04 No. of poles 4
3.3.05 Rated current A 20
3.3.06 Rated service voltage V 400
3.3.07 Rated insulation voltage V
3.3.08 Rated impulse withstand voltage kV
3.3.09 Breaking capacity kA 6,10
3.3.10 Trip unit adjustment range
3.3.10.1 Thermal x In
3.3.10.2 Magnetic x In
3.3.11 Applicable standard BS EN 60898

3.4 MCB
3.4.01 Make
3.4.02 Model
3.4.03 Country of origine
3.4.04 No. of poles 3
3.4.05 Rated current A 32
3.4.06 Rated service voltage V 400
3.4.07 Rated insulation voltage V
3.4.08 Rated impulse withstand voltage kV
3.4.09 Breaking capacity kA 6,10
3.4.10 Trip unit adjustment range
3.4.10.1 Thermal x In
3.4.10.2 Magnetic x In
3.4.11 Applicable standard BS EN 60898

3.5 MCB

2
REF. DESCRIPTION PARTICULARS
UNITS
As specified As offered
3.5.01 Make
3.5.02 Model
3.5.03 Country of origine
3.5.04 No. of poles 1
3.5.05 Rated current A 6,16
3.5.06 Rated service voltage V 230
3.5.07 Rated insulation voltage V
3.5.08 Rated impulse withstand voltage kV
3.5.09 Breaking capacity kA 6,10
3.5.10 Trip unit adjustment range
3.5.10.1 Thermal x In
3.5.10.2 Magnetic x In
3.5.11 Applicable standard BS EN 60898

4.1 Bus bar


4.1.1 Make
4.1.2 Nominal voltage V
4.1.3 Current rating A 100,160
4.1.4 Short circuit rating A
4.1.5 Fault Level kA
4.1.6 Applicable standard BS 5486

4.2 Bus bar


4.2.1 Make
4.2.2 Nominal voltage V
4.2.3 Current rating A 40
4.2.4 Short circuit rating A
4.2.5 Fault Level kA
4.2.6 Applicable standard BS 5486

5.0 Earth Leakage Relay


5.1.1 Make
5.1.2 Model
5.1.3 Country of origine
5.1.4 Current setting adjustment range
5.1.5 Time setting adjustment range
5.1.6 Applicable standard BS EN 50107-2

5.2 Core Balance Transformer


5.2.1 Make
5.2.2 Model
5.2.3 Country of origine
5.2.4 Current ratio
5.2.5 Secondary burden VA
5.2.6 Accuracy %
5.2.7 Applicable standard BS EN 60947

6.1 RCCB
6.1.1 Make
6.1.2 Model
6.1.3 Country of origine
6.1.4 No. of poles 4
6.1.5 Rated current A 63
6.1.6 Rated service voltage V 400

3
REF. DESCRIPTION PARTICULARS
UNITS
As specified As offered
6.1.7 Rated insulation voltage V
6.1.8 Sensitivity mA 100
6.1.9 Applicable standard BS EN 61008-1

6.2 RCCB
6.2.1 Make
6.2.2 Model
6.2.3 Country of origine
6.2.4 No. of poles 4
6.2.5 Rated current A 40
6.2.6 Rated service voltage V 400
6.2.7 Rated insulation voltage V
6.2.8 Sensitivity mA 100
6.2.9 Applicable standard BS EN 61008-1

6.3 RCCB
6.3.1 Make
6.3.2 Model
6.3.3 Country of origine
6.3.4 No. of poles 2
6.3.5 Rated current A 40
6.3.6 Rated service voltage V 230
6.3.7 Rated insulation voltage V
6.3.8 Sensitivity mA 100
6.3.9 Applicable standard BS EN 61008-1

6.4 RCCB
6.4.1 Make
6.4.2 Model
6.4.3 Country of origine
6.4.4 No. of poles 2
6.4.5 Rated current A 40
6.4.6 Rated service voltage V 230
6.4.7 Rated insulation voltage V
6.4.8 Sensitivity mA 30
6.4.9 Applicable standard BS EN 61008-1

6.5 Power analizer CTs


6.5.1 Make
6.5.2 Model
6.5.3 Country of origine
6.5.4 Accuracy %
6.5.5 Current ratio
6.5.6 Secondary buden
6.5.7 Applicable standard IEC 44

6.6 Power analizer


6.6.1 Make
6.6.2 Model
6.6.3 Country of origine
6.6.4 Input Current A
6.6.5 Accuracy %
6.6.6 Measuring data
6.6.6.1 Voltage YES/NO YES
6.6.6.2 Current YES/NO YES

4
REF. DESCRIPTION PARTICULARS
UNITS
As specified As offered
6.6.6.3 Active power YES/NO YES
6.6.6.4 Apparent power YES/NO YES
6.6.6.5 Reactive power YES/NO YES
6.6.6.6 Total energy consumption YES/NO YES
6.6.6.7 Frequency YES/NO YES
6.6.7 Applicable standard IEC 60253

7 Surge Arrestor
7.01 Make
7.02 Manufacture
7.03 Country of Origin
7.04 Type
Metal Oxide Varistor (MOV)
type
7.05 Maximum Discharge Current kA 50
7.06 Rated Surge Current kA 40(minimum)
7.07 Protection Level kV ( <1.3 & <0.8 )
7.08 Applicable Standards BS or equivalent
7.09 Agent
7.10 Warranty Yrs

8.1 Isolators
8.1.1 Make
8.1.2 Model
8.1.3 Country of origine
8.1.4 No. of poles 4
8.1.5 Rated current A 40
8.1.6 Rated service voltage V 400
8.1.7 Rated insulation voltage V
8.1.8 Rated impulse withstand voltage kV
8.1.9 Breaking capacity kA
8.1.10 Applicable standard IEC 60129

8.2 Isolators
8.2.1 Make
8.2.2 Model
8.2.3 Country of origine
8.2.4 No. of poles 4
8.2.5 Rated current A 32
8.2.6 Rated service voltage V 400
8.2.7 Rated insulation voltage V
8.2.8 Rated impulse withstand voltage kV
8.2.9 Breaking capacity kA
8.2.10 Applicable standard IEC 60129

8.3 Isolators
8.3.1 Make
8.3.2 Model
8.3.3 Country of origine
8.3.4 No. of poles 2
8.3.5 Rated current A 40
8.3.6 Rated service voltage V 230
8.3.7 Rated insulation voltage V
8.3.8 Rated impulse withstand voltage kV
8.3.9 Breaking capacity kA
8.3.10 Applicable standard IEC 60129

5
REF. DESCRIPTION PARTICULARS
UNITS
As specified As offered

8.4 Isolators
8.4.1 Make
8.4.2 Model
8.4.3 Country of origine
8.4.4 No. of poles 2
8.4.5 Rated current A 32
8.4.6 Rated service voltage V 230
8.4.7 Rated insulation voltage V
8.4.8 Rated impulse withstand voltage kV
8.4.9 Breaking capacity kA
8.4.10 Applicable standard IEC 60129

9.1 Socket outlets


9.1.1 13A Socket outlets
9.1.2 Make
Orange(X7/X8), Clipsal,
ACL, Legrand or eq
9.1.3 Model
9.1.4 Country of origine Sri Lanka, France,
Europe, Japan or eq
9.1.5 Rated current A
9.1.6 Rated service voltage V
9.1.7 Available colours for cover plate 1. White
2. Black
9.1.8 Applicable standard BS 1361

10.1 Switches
10.1.1 Make
Orange(X7/X8), Clipsal,
ACL, Legrand or eq
10.1.2 Model
10.1.3 Country of origine Sri Lanka, France,
Europe, Japan or eq
10.1.4 Rated current A
10.1.5 Rated service voltage V
10.1.6 Available colours for cover plate 1. White
2. Black
10.1.7 Applicable standard BS 60669-1

11.1 Cables
11.1.1 PVC Cable
11.1.2 Type Cu/PVC/PVC
11.1.3 Designed current A
11.1.4 Cross-section area mm2 according to the BOQ
11.1.5 Number of cores Nos. 1 or 2 or 4
11.1.6 Number of cables
11.1.7 Insulation
11.1.8 Operating Voltage V
11.1.9 Voltage drop %
11.1.10 Method of Installation PVC casing
11.1.11 Applicable standard BS 6004

11.1.2 Earth Cable


6
REF. DESCRIPTION PARTICULARS
UNITS
As specified As offered
11.1.2.1 Type Cu/PVC/Earth
11.1.2.2 Designed current A
11.1.2.3 Cross-section area mm2 according to the BOQ
11.1.2.4 Number of cores Nos. 1
11.1.2.5 Number of cables
11.1.2.6 Insulation
11.1.2.7 Operating Voltage V
11.1.2.8 Voltage drop %
11.1.2.9 Method of Installation PVC casing
11.1.2.10 Applicable standard BS 6004

12.0 Ceiling & Wall Fans


12.1 Make
12.2 Country of Origin
12.3 Applicable Standards JIS or equivalent
12.4 Agent