VENDOR MUST FURNISH ALL PERTINENT DATA FOR THIS SPECIFICATION SHEET BEFORE RETURNING.
ITEM NO. SERVICE VLPC COMPRESSOR JOB NO.
MANUFACTURER
1 REFERENCE SPECIFICATIONS; APPLICABLE SPECIFICATIONS: IEC NEMA
2 ISO 10438 YES NO AREA CLASSIFICATION:
3 NOTE: For the purposes of this provision API 614 is equivalent to ISO 10438 AREA: CL 1 GROUP D DIV 2 NON-HAZARDOUS
4 MOTOR CONTROL & INSTRUMENT VOLTAGE:
5 VOLTS PHASE CYCLES
6 ALARM & SHUTDOWN VOLTAGE:
7 VOLTS PHASE CYCLES OR DC
8 LOCAL CONTROL PANEL: (6.4.3)
9 FURNISHED BY: VENDOR PURCHASER OTHERS
10 FREE STANDING WEATHERPROOF TOTALLY ENCLOSED EXTRA CUTOUTS
11 VIBRATION ISOLATORS STRIP HEATERS PURGE CONNECTIONS
12 ANNUNCIATOR: FURNISHED BY: VENDOR PURCHASER OTHERS
13 ANNUNCIATOR LOCATED ON LOCAL PANEL MAIN CONTROL BOARD
14 CUSTOMER CONNECTIONS BROUGHT OUT TO TERMINAL BOXES BY VENDOR
15 INSTRUMENT SUPPLIERS:
16 PRESSURE GAGES: MFR (NOTE 11) SIZE & TYPE
17 TEMPERATURE GAGES: MFR (NOTE 11) SIZE & TYPE
18 LEVEL GAGES: MFR (NOTE 11) SIZE & TYPE
19 DIFF. PRESSURE GAGES: MFR (NOTE 11) SIZE & TYPE
20 PRESSURE SWITCHES: MFR (NOTE 11) SIZE & TYPE
21 DIFF. PRESSURE SWITCHES: MFR (NOTE 11) SIZE & TYPE
22 TEMPERATURE SWITCHES: MFR (NOTE 11) SIZE & TYPE
23 LEVEL SWITCHES: MFR (NOTE 11) SIZE & TYPE
24 CONTROL VALVES: MFR (NOTE 11) SIZE & TYPE
25 PRESSURE RELIEF VALVES: (6.4.4.6) MFR (NOTE 11) SIZE & TYPE
26 THERMAL RELIEF VALVES: (6.4.4.6.4) MFR (NOTE 11) SIZE & TYPE
27 FLOW INDICATORS: (6.4.4.9) MFR (NOTE 11) SIZE & TYPE
28 GAS FLOW INDICATOR: MFR (NOTE 11) SIZE & TYPE
29 VIBRATION EQUIPMENT: MFR (NOTE 11) SIZE & TYPE
30 TACHOMETER: MFR (NOTE 11) SIZE & TYPE
31 SOLENOID VALVES MFR (NOTE 11) SIZE & TYPE
32 ANNUNCIATOR: MFR (NOTE 11) SIZE & TYPE
33 DEPRESSURIZATON VALVE (6.4.4.7) MFR (NOTE 11) SIZE & TYPE
34
35 NOTE: SUPPLIED BY VENDOR SUPPLIED BY PURCHASER
36 PRESSURE GAGE REQUIREMENTS LOCALLY LOCAL PRESSURE GAGE REQUIREMENTS LOCALLY LOCAL
37 FUNCTION MOUNTED (3.12) PANEL (3.31) FUNCTION MOUNTED (3.12) PANEL (3.31)
38 LUBE OIL PUMP DISCHARGE GOV. CONTROL OIL
39 LUBE OIL FILTER D P GOV. CONTROL OIL D P
40 LUBE OIL SUPPLY COUPLING OIL D P
41 SEAL OIL PUMP DISCHARGE MAIN STEAM IN
42 SEAL OIL FILTER D P 1ST STAGE STEAM
43 SEAL OIL SUPPLY (EACH LEVEL) STEAM CHEST
44 SEAL OIL DIFFERENTIAL EXHAUST STEAM
45 REFERENCE GAS EXTRACTION STEAM
46 BALANCE LINE STEAM EJECTOR
47 SEAL EDUCTOR COMPRESSOR SUCTION
48 BUFFER SEAL COMPRESSOR DISCHARGE
49 OIL/GAS COALESICING FILTER D P
50
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION PROJECT Doc. No. FRZ-M-DS-001
REVISION NO Rev. C DATE 26/07/2023
VENDOR MUST FURNISH ALL PERTINENT DATA FOR THIS SPECIFICATION SHEET BEFORE RETURNING.
ITEM NO. SERVICE VLPC COMPRESSOR JOB NO.
MANUFACTURER
1 TEMPERATURE GAGE REQUIREMENTS: TEMPERATURE GAGE REQUIREMENTS:
2 LOCALLY LOCAL LOCALLY LOCAL
3 FUNCTION MOUNTED (3.12) PANEL (3.31) FUNCTION MOUNTED (3.12) PANEL (3.31)
4 LUBE OIL DISCHARGE FROM EA. COOLER OIL INLET & OUTLET
5 COMPR. JOURNAL BEARING SEAL OIL OUTLET
6 DRIVER JOURNAL BEARING COMPRESSOR SUCTION
7 GEAR JOURNAL BEARING COMPRESSOR DISCHARGE
8 COMPRESSOR THRUST BEARING LUBE OIL RESERVOIR
9 DRIVER THRUST BEARING LUBE OIL SUPPLY
10 GEAR THRUST BEARING
11 MISCELLANEOUS INSTRUMENTATION:
12 DRIVER START/STOP LOCAL PANEL SEPARATE PANEL MAIN BOARD
13 SIGHT FLOW INDICATORS, EACH JOURNAL & THRUST BEARING & EACH COUPLING OIL RETURN LINE
14 SIGHT FLOW INDICATORS, EACH SEAL OIL RETURN LINE
15 LEVEL GAGES, LUBE AND/OR SEAL OIL RESERVOIR, S.O. DRAIN TRAPS & S.O. OVERHEAD TANK
16 VIBRATION AND SHAFT POSITION PROBES & PROXIMITORS
17 VIBRATION AND SHAFT POSITION READOUT EQUIPMENT
18 VIBRATION READOUT LOCATED ON: LOCAL PANEL SEPARATE PANEL MAIN BOARD
19 TURBINE SPEED PICKUP DEVICES
20 TURBINE SPEED INDICATORS
21 TURBINE SPEED INDICATORS LOCATED ON: LOCAL PANEL MAIN BOARD
22 REMOTE HAND SPEED CHANGER - MOUNTED ON LOCAL PANEL
23 ALARM HORN & ACKNOWLEDGEMENT SWITCH
24 ALARM & SHUTDOWN SWITCHES: (6.4.5.2) PRE-
25 FUNCTION ALARM TRIP FUNCTION ALARM TRIP
26 LOW LUBE OIL PRESSURE Y Y TURBINE VIBRATION
27 HI LUBE OIL FILTER D P Y Y TURBINE AXIAL POSITION
28 HI SEAL OIL FILTER D P Y Y GEAR VIBRATION
29 LOW LUBE OIL RESERVOIR LEV. Y Y GEAR AXIAL POSITION
30 LOW SEAL OIL RESERVOIR LEV. Y Y COMPRESSOR MOTOR SHUTDOWN
31 HI SEAL OIL LEVEL Y TRIP & THROTTLE VALVE SHUT Y Y
32 LOW SEAL OIL LEVEL Y Y HI TURB. STEAM SEAL LEAKAGE
33 HI SEAL OIL PRESSURE Y HI COMPR. THRUST BRG. TEMP. Y Y
34 LOW SEAL OIL PRESSURE Y Y HI COMPR. JOURNALT BRG. TEMP. Y Y
35 AUX. SEAL OIL PUMP START Y Y HI DRIVER THRUST BRG. TEMP.
36 AUX. LUBE OIL PUMP START Y Y HI DRIVER JOURNAL BRG. TEMP.
37 HI SEAL OIL OUTLET TEMP. (COOLER) Y HI GEAR THRUST BRG. TEMP.
38 HI LIQUID LEV. SUCT. SEPARATOR Y HI GEAR JOURNAL BRG. TEMP.
39 COMPRESSOR HI DISCH. TEMP. Y Y COMPRESSOR D P Y Y
40 COMPRESSOR VIBRATION Y Y LOW SEAL-GAS PRESSURE
41 COMPRESSOR AXIAL POSITION Y Y HI COALESCING GAS/OIL FILTER D P Y Y
42 HI LUBE OIL OUTLET TEMP. (COOLER) Y
43 CONTACTS:
44 ALARM CONTACTS SHALL: OPEN CLOSE TO SOUND ALARM AND BE NORMALLY ENERGIZED DE-ENERGIZED
45 SHUTDOWN CONTACTS SHALL: OPEN CLOSE TO TRIP AND BE NORMALLY ENERGIZED DE-ENERGIZED
46 NOTE: NORMAL CONDITION IS WHEN COMPRESSOR IS IN OPERATION.
47 MISCELLANEOUS:
48 INSTRUMENT TAGGING REQUIRED.
49 ALARM AND SHUTDOWN SWITCHES SHALL BE SEPARATE.
50 PURCHASERS ELECTRICAL AND INSTRUMENT CONNECTIONS WITHIN THE CONFINES OF THE BASEPLATE AND CONSOLE SHALL
51 BROUGHT OUT TO TERMINAL BOXES. MADE DIRECTLY BY THE PURCHASER.
52 COMMENT REGARDING INSTRUMENTATION
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION PROJECT Doc. No. FRZ-M-DS-001
REVISION NO Rev. C DATE 26/07/2023
1 NOTES
2 1. Package scope of supply shall be as per Project Design Basis – Fariz VLPC Installation, Doc. No. FRZ-G-DB-001
3 2. Compressor shall suitable with fluid service condition, with 100% turndown via speed adjustment, capacity control, and recycle line.
4 3. Gas engine shall be suitable for compressed gas as fuel gas, Low BTU Carburization, Class I, Div. 2, Group D Capable, equipped with silencers and flame arrester,
5 12V/24V Electrical System, flexible dry coupling system complete with non-sparking guard.
6 4. Package scope supply shall include compressor, gas engine driver, gas and lube oil cooler, scrubber and blowcase, structural frame and enclosure, on skid piping
7 system, valves, instrumentation sytem, panel, starting system, battery and electrical system. the package are installed in containerized size to have easy mobilization.
8 5. Package suction scrubber with integral blowcase to automatically eject separated liquids and oil separator designed in accordance to ASME Sec VIII code
9 pressure vessels latest edition and completed with pressure relieving system.
10 6. Local control panel, instrumentation, and electrical equipment shall be provided and suitable for hazardous classified area
11 7. All equipment and accessories shall be installed on single/integral baseplate/skid, completed with drip pan and drain valve (flanged connection), and equipped with
12 four point lifting lugs and spreader bar that allowed package lifted with single point lifting.
13 8. Package shall be designed in compact design with skidframe size size complete with fire and gas system and fire suppression system, strobe and alarm for
14 abnormal package detection.
15 9. Design requirement for piping system shall be accordance with MEP-P-ES-002, Piping Material specification shall be accordance with MEP-P-ES-001 and also for
16 Valve Specification shall be accordance with MEP-P-ES-005.
17 10. Vendor to advise (VTA)
18 11. All equipment and accessories manufacturer shall be as per Preferred Manufacturer List (PML) Record Doc. No. COP-SFE-GE-FIR-423-F01 Rev. 04
19 12. Gas engine driver shall be as per Skid Mounted, Diesel And Natural Gas Fueled, Reciprocating Internal Combustion Engines, Doc. No. MEP-M-ES-001
20 13. Vendor shall provide vibration mounting on compressor and driver in order to take measurement.
21 14. Coupling shall be flexible spacer type with anti spark coupling guard.
22 15 Battery shall be paced in Ex rated box suitable for Class I, Div. 2, Group D classified area.
23 17 Structural natural frequency shall be separated > +/- 25% from the operating speed.
24 18 Vendor shall provide skid deflection and strength calculation.
25 19 Vendor shall provide hydrotest report and certificate.
26 20 Vendor shall provide jack nut on skid.
27 21 Vendor shall provide shim for alignment.
28 22 Compressor bearing housing shall accommodate vibration switches/transmitters/proximity probes.
29 23 Electrical and instrumentation components shall be designed suitable for class 1 div. 2 temp. Class T3 area
30 24 Compressor baseplate shall be equipped with SS316 earthing boss.
31 25 Vendor shall supply material certificate type 3.1 for pressure retaining component and type 2.2 for non-pressure retaining component as per BS EN 10204 latest edition.
32 26 The Vendor's scope work and supply shall include commissioning and site acceptance test.
33 27 Compressor package shall have noise level less than or equal to 85 dBa in 3 ft.
34 28 Vendor shall provide first fill lubricant.
35 29 Vendor shall provide SS316 nameplate.
36 30 Vendor shall provide MDR, consist of but not limited to:
37 • 1 (one) set of part list/book, operating and maintenance manual for compressor
38 • 1 (one) set of part list/book, operating and maintenance manual for driver
39 • 1 (one) set of compressor test report
40 • 1 (one) set of driver test report
41 31 Vendor shall confirm/completed this data sheet and provide catalogue, performance curve in document submitted standard features for selected quotation.
42 32 Surface preparation and painting system shall be in accordance with MEP-G-ES-008, Skid design shall be as per MEP-S-ES-004-Structural Requirements for
43 Packaged Equipment Skid Rev-0
44 33 All piping system within package shall be tested as per ASME B31.3
45 34 Vendor shall provide suitable driver for both following fuel gas composition.
46 Initial starting will utilize Gas Soka composition until Fariz pipeline fulfiled with compressed gas, then fuel gas will changeover to Faris pipeline (Gas Fariz)
47 35 Vendor shall provide ITP for company review prior FAT.
48 36 Vendor shall provide flexible hoses for all conenction from VLPC package to user connection (i.e. inlet, outlet, fuelgas, nitrogen, drain, etc, as detailed in page 11.
49
50
51
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION PROJECT Doc. No. FRZ-M-DS-001
REVISION NO Rev. C DATE 26/07/2023
1 NOTES
2 Continuing note 34
3 Fuel gas composition:
4 Composition Gas Fariz Gas Soka
5 Nitrogen 1.2388% 1.4769%
6 CO2 5.3411% 5.6101%
7 H2S 0.0000% 0.0000%
8 Methane 83.0375% 79.1996%
9 Ethane 6.6673% 7.1491%
10 Propane 2.1321% 2.8307%
11 i-Butane 0.4680% 0.6375%
12 n-Butane 0.5125% 0.7192%
13 i-Pentane 0.2046% 0.3044%
14 n-Pentane 0.1219% 0.1951%
15 n-Hexane 0.1515% 0.2138%
16 n-Heptane 0.0000% 0.1419%
17 n-Octane 0.0000% 0.0453%
18 H2O 0.1246% 1.4734%
19
20 Continuing note 36
21 INDICATION DESCRIPTION SIZE RATING CONNECTION TYPE TO TIE IN POINTS QUANTITY MATERIAL
22 N1 Gas inlet 6" 150 lb ASME B16.5 RF flange 1 VTA
23 N2 Liquid inlet 2" 150 lb ASME B16.5 RF flange 1 VTA
24 N3 Gas outlet 4" 150 lb ASME B16.5 RF flange 1 VTA
25 N4 Gas vent/flare connection 3" 150 lb ASME B16.5 RF flange 1 VTA
26 N5 Closed drain connection 2" 150 lb ASME B16.5 RF flange 1 VTA
27 N6 Fuel gas 2" 150 lb ASME B16.5 RF flange 1 VTA
28 N7 Nitrogen 2" 150 lb ASME B16.5 RF flange 1 VTA
29
30 Hose minimum length is 6 meters.
31 Vendor to advise hose material, material shall be compatible with each fluid handled.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION
Doc. No. FRZ-M-DS-001
PROJECT
REVISION NO Rev. C DATE 26/07/2023
VLPC DATASHEET
PAGE 12 OF 17 BY BSP
(API 619 ROTARY COMPRESSOR)
9 Altitude (ft above mean sea level): Below 3300 Ft ASL Above……………………Ft ASL
10 Applicable Spesification
13 Other: PUIL/SNI-04-0025-2000
15 Prime Mover
19 Fuel System
25 Quantity: V: Phase: Hz :
27 Liquid Fuel* (ASTM): No. 1-GT No. 2-GT No. 3-GT No. 4-GT
28 Other: By Vendor
29 Ignition System
33 Other:
34 Governor System
VLPC DATASHEET
PAGE 13 OF 17 BY BSP
(API 619 ROTARY COMPRESSOR)
42 Starting System
44 Rest Periods Between Cranks: minimum of three 15 second starting cycles without recharging the batteries.
65 Lubricating Systems *
66 Lube Oil: By Packager By Mobil Other:
69 Manufacturer Recommended
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION
Doc. No. FRZ-M-DS-001
PROJECT
REVISION NO Rev. C DATE 26/07/2023
VLPC DATASHEET
PAGE 14 OF 17 BY BSP
(API 619 ROTARY COMPRESSOR)
72 Manufacturer Recommended
86 Silencer *
87 Silencer: Vertical Horizontal Spark Arrester Catalytic Converter
98 Cooling System
VLPC DATASHEET
PAGE 15 OF 17 BY BSP
(API 619 ROTARY COMPRESSOR)
112 Other:
125 Pyrometer
128
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION
Doc. No. FRZ-M-DS-001
PROJECT
REVISION NO Rev. C DATE 26/07/2023
VLPC DATASHEET
PAGE 16 OF 17 BY BSP
(API 619 ROTARY COMPRESSOR)
Shutdown engine
Alarm Buzzer
Trip breaker
130 Description Manufacturer* Model No.* Range*
136
137 Nameplates
138 Color: Black - White - Black (SS316 material) White - Black - White
143 Pneumatic: Air: ____ psig to ____ psig Dry Utility Starting
147 Miscellaneous:
158 Loss Prevention: Gas Detection (NOTE 8) Fire Detection Fire Suppression
159 Gas Detection: Detector Quantity: By Vendor Manufacturer: By Vendor Model No.: By Vendor
160 Fire Detection: Detector Quantity: By Vendor Manufacturer: By Vendor Model No.: By Vendor
JOB NO. ITEM NO. FRZ-DAE-801
FARIZ VLPC INSTALLATION
Doc. No. FRZ-M-DS-001
PROJECT
REVISION NO Rev. C DATE 26/07/2023
VLPC DATASHEET
PAGE 17 OF 17 BY BSP
(API 619 ROTARY COMPRESSOR)
173 Message Display PLC-Driven Annunciator Flat Panel Operator Terminal Indicating Light
174 Nameplates: Black - White - Black White - Black - White Other: SS316 Material
176 Overall Length Overall Width Overall Height Weight, Dry Weight, Wet
185 Other:
Notes:
*
Means to be determined & filled by Vendor
1 The element of fuel gas filter shall be capable of removing 99% of all solid and liquid particles, 3 microns absolute and
larger, while operating between 10% and 100% of its rated capacity.