You are on page 1of 1

Battery Discharge Test

Site name BR Power Gen Site ID 1 Tested by Madusha


Inspect Date 31-Dec-99 Indoor/Outdoor Indoor Bat. Capacity 100Ah
Start Time 15.00 End Time 16.10

Time Power on Power off 0:30 1:00 1:10 2:00 2:30 3:00 3:30 4:00

Clock Time 14.55 15.00 15.30 16.00 16.10

Current(A) 31.2 33.1 32.9 34.5 33.2

Battery group
53.2 52.8 47.5 45.3 44.8
voltage(V)
Cell 1 13.3 12.9 11.8 11.3 11.2

Cell 2 13.3 12.8 12.0 11.7 11.6

Cell 3 13.2 12.7 11.8 11.2 11.1

Cell 4 13.2 12.7 11.7 11.0 11.0

Cell 5 13.4 12.8 12.2 11.8 11.7

Cell 6 13.2 12.4 11.6 10.9 10.8

Cell 7 13.3 12.5 11.9 11.4 11.3

Cell 8 13.2 12.5 11.7 11.0 10.9

Remarks