U factor calculation for Ground Floor level (Type-1) (CW, RW SWGR ROOM, CLO2)
S.No Materials R Value Unit Reference
1 Inside air film co-efficient at floor 0.61 (ft².°F)/(BTU/hr)
2 6.35 mm thick Ceramic floor tile 0.02 (ft².°F)/(BTU/hr)
3 50 mm thick metalic hardener for floor leveling 0.15 (ft².°F)/(BTU/hr) ISHRAE Hand Book
4 75 mm thick PCC Flooring Concrete 0.24 (ft².°F)/(BTU/hr)
5 150 mm Stone Soling 1.13 (ft².°F)/(BTU/hr)
Total R Value 2.15 (ft².°F)/(BTU/hr)
U = (1/R) 0.465 (BTU/hr)/(ft².°F)
U factor calculation for Ground Floor level (Type-2) (Booster pump, CH.ETP, LAB, WTP)
S.No Materials R Value Unit Reference
1 Inside air film co-efficient at floor 0.61 (ft².°F)/(BTU/hr)
2 6.35 mm thick Ceramic floor tile- no need 0.02 (ft².°F)/(BTU/hr)
3 50 mm thick metalic hardener for floor leveling 0.15 (ft².°F)/(BTU/hr)
ISHRAE Hand Book
4 150 mm thick RCC Flooring Concrete 0.48 (ft².°F)/(BTU/hr)
5 75 mm thick PCC Flooring Concrete 0.24 (ft².°F)/(BTU/hr)
6 200 mm Stone Soling 1.5 (ft².°F)/(BTU/hr)
Total R Value 3 (ft².°F)/(BTU/hr)
U = (1/R) 0.333 (BTU/hr)/(ft².°F)