You are on page 1of 3

S.

NO Load Description Rated Load


AMINE CIRCULATION PUMP A 500
AMINE CIRCULATION PUMP B 500
LEAN AMINE COOLER BAY-1 FAN-1 45
LEAN AMINE COOLER BAY-1 FAN-2 45
LEAN AMINE COOLER BAY-2 FAN-1 45
LEAN AMINE COOLER BAY-2 FAN-2 45
AMINE STRIPPER CONDENSER BAY-1 FAN-1 45
AMINE STRIPPER CONDENSER BAY-1 FAN-2 45
TREATED GAS COOLER BAY-1 FAN-1 15
TREATED GAS COOLER BAY-1 FAN-2 15
HIGH PRESSURE WATER PUMP-A FOR TREATED GAS COOLER 5.5
AMINE BOOSTER PUMP-A 30
AMINE BOOSTER PUMP-B 30
REFLUX PUMP-A 5.5
ANTI FOAM INJECTION PUMP-A 0.37
HOT OIL CIRCULATION PUMP - 1 260
HOT OIL CIRCULATION PUMP - 2 260
AIR BLOWER FOR HOT OIL UNIT 75
NORMAL LIGHTING LOAD 1.2
EMERGENCY LIGHTING 1.4
HOT OIL PACKAGE UCP UPS POWER 3.9
CONTROL PANEL FOR HOT OIL UNIT 1.8
SPACE HEATERS LOAD 0
Total Load of ASU 1974.67

6261
Efficiency Required Power
0.965 518.13
0.965 518.13
0.9 50.00
0.9 50.00
0.9 50.00
0.9 50.00
0.9 50.00
0.9 50.00
0.9 16.67
0.9 16.67
0.9 6.11
0.936 32.05
0.936 32.05
0.895 6.15
0.9 0.41
0.96 270.83
0.96 270.83
0.9 83.33
0.9 1.33
0.9 1.56
0.9 4.33
0.9 2.00
0.9 0.00
2080.5950233288
Input to load to counter losses.

4161.19004665761
5694.19004665761

3949.34
137
328
252
202
202
530
315
5915.34
7394.175