You are on page 1of 5

Construction of Gas Treatment Plant -Tataouine Gas Project

Contract No. Document No. Rev.


AOI NO 01/2018 TGP-JE-GTPT-250-EQ-DAT-00105 001
Date 30/09/2019 Page 1 of 8
DATA SHEET

Document Name:DATA SHEET FOR AIR COOLED HEAT EXCHANGER


Document No.:TGP-JE-GTPT-250-EQ-DAT-00105
PO No. :GTPT-GC-PUR-001
Equipment Name:Turbo-Expander
Equipment Tag No.:GTPT-PK-250-001
Vendor Name: HANGZHOU HANGYANG EXPANDER
Vendor Code/Logo :

001 21/12/2021 Issued for use


000 28/05/2021 Issued for use
Rev Date Description Prepared by Reviewed by Approved by
END USER : N/A

CUSTOMER : FLENCO NINGBO POWER AUXILIARY EQUIPMENT & SYSTEM CO., LTD.

PURCHASE ORDER N°: N/A

PROJECT TITLE : GAS TREATMENT PLANT – TATAOUINE GAS PROJECT

PROJECT N°: N/A

LOCATION : TATAOUINE, TUNISIA

1 ISSUED FOR REVIEW


M.Lu 2020-10-26 J.Liu 2020-10-26
0 ISSUED FOR REVIEW
M.Lu 2020-08-19 J.Liu 2020-08-19
Rev. Description of revision Prepared By Date Verified by Date
版本 描述 编制 日期 校对 日期
PAGE 页数 : 1 BPI : BPE :
EQUIPMENT : AIR COOLED HEAT EXCHANGER
设备名称 空冷式换热器

TITLE : DATA SHEET


标题 数据表

ITEM NO. 位号 : E1
Rev.

N°21C201015-000-0001 版本

1
Kelvion Thermal Solutions (JiangSu) Co., Ltd. – Confidential
Communication, copying of this document, and use of its contents, are not permitted without prior written authorization.
在获得预先的书面授权之前,禁止交流、复制本文件和使用其中的内容。
注释小结:TGP-JE-GTPT-250-EQ-
DAT-00105_000_HY_Data Sheet for Air Cooled
HeatExchanger-Reviewed
页面:1
作者:kais.hajji 主题:Note 日期:2021/12/21 18:28:58
000

作者:suncy 主题:附注 日期:2021/12/21 18:29:08


Agree.
页面:3
作者:amine.labiadh 主题:Rectangle 日期:2021/12/21 18:29:17
2.5 mm as minimum (refer to air cooler specification)

作者:suncy 主题:附注 日期:2021/12/21 18:37:02


1. Our material of tube is SS304L, according to the API661 Table 5, Minimum required wall thickness is 1.65mm.
2. Under the design pressure of 1 Mpa. The theoretical thickness is 0.16mm. So the thickness of 1.65mm is enough.

作者:amine.labiadh 主题:Rectangle 日期:2021/12/21 18:37:24


please confirm that each fan & driver are capable of delivering a minimum of 110% of the required air flow

作者:suncy 主题:附注 日期:2021/12/21 18:37:45


Confirmed that 110% air flow is considered for each fan.

作者:amine.labiadh 主题:Pense-bête 日期:2021/12/21 18:41:21


1) As per the air cooler specification, detailed calculations of heat transfer, fouling factors and pressure drops shall be submitted
The detailed calculations shall include:
● All physical properties with the data reference source, for all fluids.
● Assumptions used.
● Detailed calculations stating all equations used.
2) Plase also attach the fan perofrmance characteristic curves.

作者:suncy 主题:附注 日期:2021/12/21 18:44:13


1) Please find left side from lines 8 to 35 , above informations heat transfer, fouling factors and pressure drops , physical properties
are all specified .
2) Please find attachments 1.