NOTES
- 1. ALL DIMENSIONS ARE IN MILLIMETRES AND LEVELS,
PEDESTAL
INSERT a CO-ORDINATES ARE IN METRES UNO.
PLATE
PEDESTAL
3-T12
LINKS e f e 2. FOR OTHER NOTES, REFERENCES AND LEGENDS REFER
EL (T.O.C)
DRAWING NO. NG-100-A2Q-5-01609-001.
t
F.G.L (VARIES) F.G.L (VARIES) 2d 3. INSERT PLATE SHALL BE WELDABLE STEEL IN
(REFER SPECIAL NOTE) ACCORDANCE WITH BS EN 10025-S275JR.
REFER SPECIAL
4. ALL STRUCTURAL HOLDFAST/ REINFORCEMENT LUGS
300 (MIN.)
CONCRETE PROTECTION
g
LUGS SHALL BE HOT DIP GALVANIZED IN ACCORDANCE WITH
NOTE
REFER PLAN
TYPE-B (CASE B1)
ASTM A123M OR BS EN ISO1461 AS PER
REFER STD. DWG NO. 6
LINKS
AGES-SP-01-001.
AD-90-C-331011
T10-200-C/C
LINKS (TYP) B SECTION
-
(TYP)
CJ (TYP) (NTS)
150
(TYP)
(TYP)
(TYP)
100
LAP
50
T16 @ 150 C/C
(BOTH WAYS)
FDN. THK
==
EL (B.O.F)
(TYP) a
=I=
100 Ld
e f e
(TYP) REFER NOTE 7 & 8 (TYP)
WELL COMPACTED 1-T10 LINK
e
50 THK BLINDING IN DWG NO.
SOIL (TYP) (TYP) SPECIAL NOTE
CONCRETE AD-90-C-331112
(TYP) T16 @ 150 C/C F.G.L SHALL BE MINIMUM 300 BELOW T.O.C. SITE
c
(BOTH WAYS) GRADING TO BE DONE LOCALLY TO MATCH
TYPICAL CROSS SECTION FOR B-
c c c
EXISTING GROUND PROFILE AROUND STRUCTURE.
TYPICAL CROSS SECTION FOR
=I=
IP
b
(FORMWORK DETAILS) SPS-4-AG-2011, 2012 & 2017
(REINFORCEMENT DETAILS) HOLD
c
(NTS)
FOR B.O.F, TOC & FDN. THK REFER DRG. NO. (NTS)
IP
e
NG-100-A2Q-5-01609-001
REFER PLAN
=I=
INSERT PLATE
REFERENCE DRAWINGS
T12-200
L
REFER PLAN
REFER PLAN
C PEDESTAL
CLEAR TO MESH
IN SINGLE LAYER
=I=
=I=
PEDESTAL
(BOTH WAYS)
150
CLEAR
3-T12
50
PD (BOTH WAYS)
LINKS
75
75
A-
PEDESTAL
LEGEND
TYPICAL PLAN FOR SLEEPER 1 DETAIL A SECTION
SPS-4-AG-2011, 2012 & 2017 - SCALE (NTS) - SCALE (NTS) PD : PEDESTAL
IP : INSERT PLATE
(FOR LOCATION, DIMENSIONS & ORIENTATION REFER DWG NO. (REINFORCEMENT DETAILS AT TOP OF SLEEPER FOR PD2 / PD3)
NG-100-A2Q-5-01609-001 & NG-100-A2Q-5-01610-001)
(NTS)
1500 1000
16-T20
24-T20
T10-200-C/C
T10-200-C/C
LINKS 2 12.10.23 ISSUED FOR CONSTRUCTION SKI RL SS/SPM DLC
SCHEDULE OF INSERT PLATE
500
LINKS
500
(5-LINKS+2 TIES PER SET) (3-LINKS+2 TIES PER SET) DETAILS OF INSERT DETAILS OF LUG NO. OF DIA. OF
INSERT ABU DHABI GAS LIQUEFACTION COMPANY LTD.
PLATE LUGS LUGS NOS
PALTE (ADNOC GAS)
REINFORCEMENT DETAILS FOR PD2 REINFORCEMENT DETAILS FOR PD3 MKD LZ LTDP-1
(2 NO.S) (1 NO.) a b t e g c f N (mm) NEW MAIN GAS LINE (NMGL)
SCALE 1:25 SCALE 1:25 (mm) (mm) (mm) (mm) (mm) (mm) (mm) PROJECT
CONTRACTOR: NATIONAL PETROLEUM CONSTRUCTION COMPANY
P.O. BOX: 2058, MUSSAFAH ABU DHABI, UAE.
PEDESTAL/IP1
IP1 400 1400 167.5 340 Tel: +971 2 554 9000
PEDESTAL/IP2 16 30 250 9 16 2 Fax: +971 2 554 9111
1500 1000 IP2 400 900 16 30 250 168 340 6 16 1 CONTRACTOR
DRAWING NUMBER 2369-Q-08116-001
= = = =
DRAWING TITLE
FOUNDATION LAYOUT & DETAILS OF TRESTLE
= =
= =
500
500
PEDESTAL/IP1 PEDESTAL/IP2
NPCC Transmittal No: 2369-NPCC-ADNOC-T-52958 ADNOC Offshore Trl ref No: 11689-E-O-T-LNG-IFR-000270
*Approval Class:
1: Requires COMPANY review and approval to allow CONTRACTOR to proceed”
2: CONTRACTOR shall incorporate comments received from COMPANY within the Contract review period”
3: Documents issued for information, CONTRACTOR may proceed without COMPANY comments or approval:
**Approval Codes:
1: Approved without comment, 2: Approved with comments 3: Reviewed with Comments, 4: Information only,
5: Rejected
Page 1 of 4
LOWER ZAKUM LONG TERM DEVELOPMENT PHASE-1 (LZ LTDP-1)
2369 - EPC FOR NEW MAIN GAS LINE (NMGL) PROJECT
Document Review/Comment Sheet
*Approval Class:
1: Requires COMPANY review and approval to allow CONTRACTOR to proceed”
2: CONTRACTOR shall incorporate comments received from COMPANY within the Contract review period”
3: Documents issued for information, CONTRACTOR may proceed without COMPANY comments or approval:
**Approval Codes:
1: Approved without comment, 2: Approved with comments 3: Reviewed with Comments, 4: Information only,
5: Rejected
Page 2 of 4
LOWER ZAKUM LONG TERM DEVELOPMENT PHASE-1 (LZ LTDP-1)
2369 - EPC FOR NEW MAIN GAS LINE (NMGL) PROJECT
Document Review/Comment Sheet
COMMENTS ON Rev 1
Contractor
Srl. Reference Company Comment Contractor Response Company Comments
Response
1 NG-100-A2Q-5-01612-001 Comments in calculation report shall be addressed in drawings. Noted and Incorporated
SPS-4-AG-2007 and
NG-100-A2Q-5-01612-001 Contractor to note that position of Trestle shall be finalized based on
2 2001 is as per final
final company agreed routing of NMGL pipe.
position.
3 NG-100-A2Q-5-01612-001 Add base plate stiffener MTO Noted and Incorporated
8 NG-100-A2Q-5-01616-001 Add insert plate and lug specification follow valve pit drawings. Noted and Incorporated
9 NG-100-A2Q-5-01616-001 These are not sleepers, correct to 2011 2012 2017. Noted and Incorporated
*Approval Class:
1: Requires COMPANY review and approval to allow CONTRACTOR to proceed”
2: CONTRACTOR shall incorporate comments received from COMPANY within the Contract review period”
3: Documents issued for information, CONTRACTOR may proceed without COMPANY comments or approval:
**Approval Codes:
1: Approved without comment, 2: Approved with comments 3: Reviewed with Comments, 4: Information only,
5: Rejected
Page 4 of 4