DESIGN PARAMETERS
F'c = 20.69 MPa = 3.00 ksi
Fy = 275.80 MPa = 40.00 ksi
Length (L) = 2.74 m
Minimum thickness of slab if
Simply supported (L) = 136.88 mm ~ 150.00 mm
One end continous (L) = 114.06 mm ~ 125.00 mm
Both ends continous (L) = 97.77 mm ~ 100.00 mm
Cantilever (L) = 273.75 mm ~ 275.00 mm
Diameter of bar = 10.00 mm
Depth (d) = 75.00 mm
t = 100.00 mm 2.36 KPa
b = 1,000.00 mm
LOADINGS
Dead Load service(input)
Total load (Factored) = 7.67 KPa 3.12 KPa superimp
Live Load (Factored) = 3.26 KPa 1.92 KPa
SUPPORTS 1E
Total Moment including / Mom constant
@ midspan / 14 = 5.85 KN-m 5.76 128/9
@ continous end / 10 = 8.20 KN-m 10.24 8
@ discontinous end / 24 = 3.41 KN-m 1.92 h31/3
.
Required rho
rho required @ midspan = 0.00434031
rho required @ continous end = 0.00616797
rho required @ discontinous end = 0.00249446
adopt
@ discontinous end = 10.00 mm @ 300.00 mm o.c.
@ midspan = 10.00 mm @ 225.00 mm o.c.
@ continous end = 10.00 mm @ 150.00 mm o.c.