DESIGN OF SLAB

1 f'c = 21 Mpa
fy = 275 Mpa
L = 5,750 mm
2 minimum sl= L/28(0.4+( = 162.82 mm (both end continous)
use = 165.00 mm
3 effective d = 140.00 mm
clear cover= 20.00 mm
size of reb = 10.00 mm
4 weight of s= 3,877.50 Pa
5 Factored fl = 1.4DL + 1. = 7,020.00 Pa
DL = 2,100.00 Pa
LL = 2,400.00 Pa
6 Analyzing 1m (b=1000mm) width of slab
Wu = 7,020.00 N/m
7 maximum factored moment, Mu = 29,012.34 N-m
8 Mu = ɸRu b d^2
Ru = 1.64 Mpa

ρactual = 0.0063
ρmin = 1.4/fy = 0.0051
ρmax = 0.75((0.85f'cβ1*600)/(fy(600+fy)
ρmax = 0.0284
therefore = 0.0063
8 Area of ste = ρbd = 879.90 mm^2 per meter

9 using size = 10.00 mm


spacing = 89.22 mm
maximum spacing required by code
a = 2h = 330.00 mm
b = 450.00 mm
therefore = 130.00 mm

thus, use = 10 mm dia main rebars


130.00 mm on center spacing
10 temperature bar
As = 0.002bh = 330.00 mm2
use = 10 mm
spacing = 237.88 mm
maximum spacing req'd by code
= 5h = 825.00 mm
= 450 mm
therefore = 170.00 mm

thus, use = 10.00 mm dia temperature rebars


170.00 mm on center spacing
11 summary
a. main rebars = 10.00 mm dia.
spaced @ = 130.00 mm on center (along transversal direction
b. temperature bars = 10 mm dia.
spaced @ = 170.00 mm on center (along longitudinal directio
c thickness of slab = 165.00 mm
continous)
nter (along transversal direction)

nter (along longitudinal direction)