You are on page 1of 24

Installation and operation manual

VRV system air conditioner

FXDA10A2VEB
FXDA15A2VEB
FXDA20A2VEB
FXDA25A2VEB
FXDA32A2VEB
FXDA40A2VEB
FXDA50A2VEB Installation and operation manual
English
FXDA63A2VEB VRV system air conditioner
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI

Daikin Industries Czech Republic s.r.o.


01 declares under its sole responsibility that the air conditioning models to which this declaration relates: 09 заявляет, исключительно под свою ответственность, что модели кондиционеров воздуха, к которым относится настоящее заявление: 17 deklaruje na własną i wyłączną odpowiedzialność, że modele klimatyzatorów, których dotyczy niniejsza deklaracja:
02 erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Erklärung bestimmt ist: 10 erklærer under eneansvar, at klimaanlægmodellerne, som denne deklaration vedrører: 18 declară pe proprie răspundere că aparatele de aer condiţionat la care se referă această declaraţie:
03 déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclaration: 11 deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berörs av denna deklaration innebär att: 19 z vso odgovornostjo izjavlja, da so modeli klimatskih naprav, na katere se izjava nanaša:
04 verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft: 12 erklærer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berøres av denne deklarasjon, innebærer at: 20 kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
05 declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace referencia la declaración: 13 ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat ilmastointilaitteiden mallit: 21 декларира на своя отговорност, че моделите климатична инсталация, за които се отнася тази декларация:
06 dichiara sotto sua responsabilità che i condizionatori modello a cui è riferita questa dichiarazione: 14 prohlašuje ve své plné odpovědnosti, že modely klimatizace, k nimž se toto prohlášení vztahuje: 22 visiška savo atsakomybe skelbia, kad oro kondicionavimo prietaisų modeliai, kuriems yra taikoma ši deklaracija:
07 δηλώνει με αποκλειστική της ευθύνη ότι τα μοντέλα των κλιματιστικών συσκευών στα οποία αναφέρεται η παρούσα δήλωση: 15 izjavljuje pod isključivo vlastitom odgovornošću da su modeli klima uređaja na koje se ova izjava odnosi: 23 ar pilnu atbildību apliecina, ka tālāk uzskaitīto modeļu gaisa kondicionētāji, uz kuriem attiecas šī deklarācija:
08 declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declaração se refere: 16 teljes felelőssége tudatában kijelenti, hogy a klímaberendezés modellek, melyekre e nyilatkozat vonatkozik: 24 vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely, na ktoré sa vzťahuje toto vyhlásenie:
25 tamamen kendi sorumluluǧunda olmak üzere bu bildirinin ilgili olduǧu klima modellerinin aşaǧıdaki gibi olduǧunu beyan eder:

FXDA10A2VEB, FXDA15A2VEB, FXDA20A2VEB, FXDA25A2VEB, FXDA32A2VEB, FXDA40A2VEB, FXDA50A2VEB, FXDA63A2VEB,

01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions: 08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de 16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß acordo com as nossas instruções: 17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi instrukcjami:
unseren Anweisungen eingesetzt werden: 09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим инструкциям: 18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în conformitate cu
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions: 10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser: instrucţiunile noastre:
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze 11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att 19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
instructies: användning sker i överensstämmelse med våra instruktioner: 20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras 12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i 21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите инструкции:
instrucciones: henhold til våre instrukser: 22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni: 13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti: 23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
07 είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται 14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům: 24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade s našim
σύμφωνα με τις οδηγίες μας: 15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama: návodom:
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
EN60335-2-40,
01 following the provisions of: 10 under iagttagelse af bestemmelserne i: 19 ob upoštevanju določb: 01 Directives, as amended. 10 Direktiver, med senere ændringer. 18 Directivelor, cu amendamentele respective.
02 gemäß den Vorschriften der: 11 enligt villkoren i: 20 vastavalt nõuetele: 02 Direktiven, gemäß Änderung. 11 Direktiv, med företagna ändringar. 19 Direktive z vsemi spremembami.
03 conformément aux stipulations des: 12 gitt i henhold til bestemmelsene i: 21 следвайки клаузите на: 03 Directives, telles que modifiées. 12 Direktiver, med foretatte endringer. 20 Direktiivid koos muudatustega.
04 overeenkomstig de bepalingen van: 13 noudattaen määräyksiä: 22 laikantis nuostatų, pateikiamų: Electromagnetic Compatibility 2014/30/EU * 04 Richtlijnen, zoals geamendeerd. 13 Direktiivejä, sellaisina kuin ne ovat muutettuina. 21 Директиви, с техните изменения.
05 siguiendo las disposiciones de: 14 za dodržení ustanovení předpisu: 23 ievērojot prasības, kas noteiktas: 05 Directivas, según lo enmendado. 14 v platném znění. 22 Direktyvose su papildymais.
06 secondo le prescrizioni per: 15 prema odredbama: 24 održiavajúc ustanovenia: Machinery 2006/42/EC ** 06 Direttive, come da modifica. 15 Smjernice, kako je izmijenjeno. 23 Direktīvās un to papildinājumos.
07 με τήρηση των διατάξεων των: 16 követi a(z): 25 bunun koşullarına uygun olarak: 07 Οδηγιών, όπως έχουν τροποποιηθεί. 16 irányelv(ek) és módosításaik rendelkezéseit. 24 Smernice, v platnom znení.
08 de acordo com o previsto em: 17 zgodnie z postanowieniami Dyrektyw: 08 Directivas, conforme alteração em. 17 z późniejszymi poprawkami. 25 Değiştirilmiş halleriyle Yönetmelikler.
09 в соответствии с положениями: 18 în urma prevederilor: 09 Директив со всеми поправками.
01 Note* as set out in <A> and judged positively by <B> 06 Nota* delineato nel <A> e giudicato positivamente da <B> 11 Information* enligt <A> och godkänts av <B> enligt 16 Megjegyzés* a(z) <A> alapján, a(z) <B> igazolta a megfelelést, a(z) 21 Забележка* както е изложено в <A> и оценено положително от <B>
according to the Certificate <C>. secondo il Certificato <C>. Certifikatet <C>. <C> tanúsítvány szerint. съгласно Сертификата <C>.
02 Hinweis* wie in <A> aufgeführt und von <B> positiv 07 Σημείωση* όπως καθορίζεται στο <A> και κρίνεται θετικά 12 Merk* som det fremkommer i <A> og gjennom positiv 17 Uwaga* zgodnie z dokumentacją <A>, pozytywną 22 Pastaba* kaip nustatyta <A> ir kaip teigiamai nuspręsta <B> pagal
beurteilt gemäß Zertifikat <C>. από το <B> σύμφωνα με το Πιστοποιητικό <C>. bedømmelse av <B> ifølge Sertifikat <C>. opinią <B> i Świadectwem <C>. Sertifikatą <C>.
03 Remarque* tel que défini dans <A> et évalué positivement par <B> 08 Nota* tal como estabelecido em <A> e com o parecer positivo 13 Huom* jotka on esitetty asiakirjassa <A> ja jotka <B> 18 Notă* aşa cum este stabilit în <A> şi apreciat pozitiv de <B> 23 Piezīmes* kā norādīts <A> un atbilstoši <B> pozitīvajam vērtējumam <A> DAIKIN.TCF.024-J3/06-2020
conformément au Certificat <C>. de <B> de acordo com o Certificado <C>. on hyväksynyt Sertifikaatin <C> mukaisesti. în conformitate cu Certificatul <C>. saskaņā ar sertifikātu <C>.
04 Bemerk* zoals vermeld in <A> en positief beoordeeld door <B> 09 Примечание* как указано в <A> и в соответствии с положительным 14 Poznámka* jak bylo uvedeno v <A> a pozitivně zjištěno 19 Opomba* kot je določeno v <A> in odobreno s strani <B> 24 Poznámka* ako bolo uvedené v <A> a pozitívne zistené <B> v súlade <B> TÜV (NB1856)
overeenkomstig Certificaat <C>. решением <B> согласно Свидетельству <C>. <B> v souladu s osvědčením <C>. v skladu s certifikatom <C>. s osvedčením <C>.
05 Nota* como se establece en <A> y es valorado 10 Bemærk* som anført i <A> og positivt vurderet af <B> i henhold til 15 Napomena* kako je izloženo u <A> i pozitivno ocijenjeno od strane 20 Märkus* nagu on näidatud dokumendis <A> ja heaks kiidetud 25 Not* <A>’da belirtildiği gibi ve <C> Sertifikasına göre <B> <C> 60127477
positivamente por <B> de acuerdo con el Certifikat <C>. <B> prema Certifikatu <C>. <B> järgi vastavalt sertifikaadile <C>. tarafından olumlu olarak değerlendirildiği gibi.
Certificado <C>.
01** DICz*** is authorised to compile the Technical Construction File. 07** Η DICz*** είναι εξουσιοδοτημένη να συντάξει τον Τεχνικό φάκελο κατασκευής. 13** DICz*** on valtuutettu laatimaan Teknisen asiakirjan. 19** DICz*** je pooblaščen za sestavo datoteke s tehnično mapo.
02** DICz*** hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen. 08** A DICz*** está autorizada a compilar a documentação técnica de fabrico. 14** Společnost DICz*** má oprávnění ke kompilaci souboru technické konstrukce. 20** DICz*** on volitatud koostama tehnilist dokumentatsiooni.
03** DICz*** est autorisé à compiler le Dossier de Construction Technique. 09** Компания DICz*** уполномочена составить Комплект технической документации. 15** DICz*** je ovlašten za izradu Datoteke o tehničkoj konstrukciji. 21** DICz*** е оторизирана да състави Акта за техническа конструкция.
04** DICz*** is bevoegd om het Technisch Constructiedossier samen te stellen. 10** DICz*** er autoriseret til at udarbejde de tekniske konstruktionsdata. 16** A DICz*** jogosult a műszaki konstrukciós dokumentáció összeállítására. 22** DICz*** yra įgaliota sudaryti šį techninės konstrukcijos failą.
05** DICz*** está autorizado a compilar el Archivo de Construcción Técnica. 11** DICz*** är bemyndigade att sammanställa den tekniska konstruktionsfilen. 17** DICz*** ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej. 23** DICz*** ir autorizēts sastādīt tehnisko dokumentāciju.
06** DICz*** è autorizzata a redigere il File Tecnico di Costruzione. 12** DICz*** har tillatelse til å kompilere den Tekniske konstruksjonsfilen. 18** DICz*** este autorizat să compileze Dosarul tehnic de construcţie. 24** Spoločnosť DICz*** je oprávnená vytvoriť súbor technickej konštrukcie.
25** DICz*** Teknik Yapı Dosyasını derlemeye yetkilidir.
***DICz = Daikin Industries Czech Republic s.r.o.

Yasuto Hiraoka
Managing Director
Pilsen, 1st of July 2020

3P480520-17E
Table of contents
15.2 To perform a test run.................................................................. 19
Table of contents
16 Configuration 19
16.1 Field setting ................................................................................ 19

1 About the documentation 3 17 Technical data 20


1.1 About this document.................................................................. 3 17.1 Wiring diagram ........................................................................... 20
17.1.1 Unified wiring diagram legend...................................... 20
2 Specific installer safety instructions 4

For the user 5 1 About the documentation


3 User safety instructions 5
3.1 General...................................................................................... 5
1.1 About this document
3.2 Instructions for safe operation ................................................... 5 INFORMATION
4 About the system 7 Make sure that the user has the printed documentation and
4.1 System layout............................................................................ 8 ask him/her to keep it for future reference.

5 User interface 8 Target audience


Authorised installers + end users
6 Operation 8
6.1 Operation range ........................................................................ 8 INFORMATION
6.2 About operation modes ............................................................. 8
This appliance is intended to be used by expert or trained
6.2.1 Basic operation modes ............................................... 8
users in shops, in light industry and on farms, or for
6.2.2 Special heating operation modes................................ 9
commercial use by lay persons.
6.3 To operate the system............................................................... 9
WARNING
7 Maintenance and service 9
7.1 Precautions for maintenance and service ................................. 9 Make sure installation, servicing, maintenance, repair and
7.2 Cleaning the air filter and air outlet............................................ 9 applied materials follow the instructions from Daikin and, in
7.2.1 To clean the air filter ................................................... 9 addition, comply with applicable legislation and are
7.2.2 To clean the air outlet ................................................. 10 performed by qualified persons only. In Europe and areas
7.3 Maintenance before a long stop period ..................................... 10 where IEC standards apply, EN/IEC 60335-2-40 is the
7.4 Maintenance after a long stop period ........................................ 10 applicable standard.
7.5 About the refrigerant.................................................................. 10
Documentation set
7.5.1 About the refrigerant leakage sensor.......................... 10
This document is part of a documentation set. The complete set
8 Troubleshooting 11 consists of:

9 Relocation 11 ▪ General safety precautions:


▪ Safety instructions that you must read before installing
10 Disposal 11
▪ Format: Paper (in the box of the indoor unit)
▪ Indoor unit installation and operation manual:
For the installer 12 ▪ Installation and operation instructions

11 About the box 12 ▪ Format: Paper (in the box of the indoor unit)
11.1 Indoor unit ................................................................................. 12 ▪ Installer and user reference guide:
11.1.1 To remove the accessories from the indoor unit......... 12
▪ Preparation of the installation, good practices, reference data,…
12 Unit installation 12 ▪ Detailed step-by-step instructions and background information
12.1 Preparing the installation site .................................................... 12 for basic and advanced usage
12.1.1 Installation site requirements of the indoor unit .......... 12
▪ Format: Digital files on http://www.daikineurope.com/support-
12.2 Mounting the indoor unit............................................................ 13
and-manuals/product-information/
12.2.1 Guidelines when installing the indoor unit................... 13
12.2.2 Guidelines when installing the ducting........................ 14 Latest revisions of the supplied documentation may be available on
12.2.3 Guidelines when installing the drain piping................. 14 the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
13 Piping installation 16 are translations.
13.1 Preparing refrigerant piping....................................................... 16
13.1.1 Refrigerant piping requirements.................................. 16 Technical engineering data
13.1.2 Refrigerant piping insulation ....................................... 16 ▪ A subset of the latest technical data is available on the regional
13.2 Connecting the refrigerant piping .............................................. 17 Daikin website (publicly accessible).
13.2.1 To connect the refrigerant piping to the indoor unit .... 17
▪ The full set of latest technical data is available on the Daikin
14 Electrical installation 17 Business Portal (authentication required).
14.1 Specifications of standard wiring components .......................... 17
14.2 To connect the electrical wiring to the indoor unit ..................... 17

15 Commissioning 18
15.1 Checklist before commissioning................................................ 18

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 3
2 Specific installer safety instructions
Refrigerant piping installation (see "13 Piping
2 Specific installer safety installation" 4
[ 16])
instructions CAUTION
Always observe the following safety instructions and regulations. ▪ Do NOT use mineral oil on flared part.
General ▪ Do NOT reuse piping from previous installations.

WARNING ▪ NEVER install a drier to this R32 unit to guarantee its


lifetime. The drying material may dissolve and damage
Make sure installation, servicing, maintenance, repair and the system.
applied materials follow the instructions from Daikin and, in
addition, comply with applicable legislation and are CAUTION
performed by qualified persons only. In Europe and areas
▪ Incomplete flaring may cause refrigerant gas leakage.
where IEC standards apply, EN/IEC 60335-2-40 is the
applicable standard. ▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
Installation site (see "12.1 Preparing the installation
site" 4
[ 12]) ▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
WARNING
CAUTION
The appliance shall be stored in a room without
continuously operating ignition sources (example: open Install the refrigerant piping or components in a position
flames, an operating gas appliance or an operating electric where they are unlikely to be exposed to any substance
heater). which may corrode components containing refrigerant,
unless the components are constructed of materials that
CAUTION are inherently resistant to corrosion or are suitably
Appliance not accessible to the general public, install it in a protected against corrosion.
secured area, protected from easy access.
WARNING: MILDLY FLAMMABLE MATERIAL
This unit, both indoor and outdoor, is suitable for
The refrigerant inside this unit is mildly flammable.
installation in a commercial and light industrial
environment. Electrical installation (see "14 Electrical installation" 4
[ 17])

CAUTION WARNING
The total refrigerant charge in the system cannot exceed ▪ All wiring MUST be performed by an authorised
the requirements for minimum floor area of the smallest electrician and MUST comply with the applicable
room that is served. For minimum floor area requirements legislation.
for indoor units, see the installation and operation manual
▪ Make electrical connections to the fixed wiring.
of the outdoor unit.
▪ All components procured on-site and all electrical
Duct installation (see "12.2.2 Guidelines when installing the construction MUST comply with the applicable
ducting" 4
[ 14]) legislation.
WARNING
WARNING
Do NOT install operating ignition sources (example: open
▪ If the power supply has a missing or wrong N-phase,
flames, an operating gas appliance or an operating electric
equipment might break down.
heater) in the duct work.
▪ Establish proper earthing. Do NOT earth the unit to a
CAUTION utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Make sure the installation of the duct does NOT exceed
the setting range of the external static pressure for the ▪ Install the required fuses or circuit breakers.
unit. Refer to the technical datasheet of your model for
▪ Secure the electrical wiring with cable ties so that the
the setting range.
cables do NOT come in contact with sharp edges or
▪ Make sure to install the canvas duct so vibrations are piping, particularly on the high-pressure side.
NOT transmitted to the duct or ceiling. Use a sound-
▪ Do NOT use taped wires, stranded conductor wires,
absorbing material (insulation material) for the lining of
extension cords, or connections from a star system.
the duct and apply vibration insulation rubber to the
They can cause overheating, electrical shock or fire.
hanging bolts.
▪ Do NOT install a phase advancing capacitor, because
▪ When welding, make sure NOT to spatter onto the
this unit is equipped with an inverter. A phase
drain pan or the air filter.
advancing capacitor will reduce performance and may
▪ If the metal duct passes through a metal lath, wire lath cause accidents.
or metal plate of the wooden structure, separate the
duct and wall electrically. WARNING
▪ Install the outlet grille in a position where the airflow will ALWAYS use multicore cable for power supply cables.
not come into direct contact with people.
WARNING
▪ Do NOT use booster fans in the duct. Use the function
to adjust the fan rate setting automatically (see Use an all-pole disconnection type breaker with at least
"16.1 Field setting" 4
[ 19]). 3 mm between the contact point gaps that provide full
disconnection under overvoltage category III.

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
4 3P599562-1 – 2020.05
3 User safety instructions
WARNING CAUTION
If the supply cord is damaged, it MUST be replaced by the ▪ Each indoor unit has to be connected to a separate
manufacturer, its service agent or similarly qualified user interface. Only a safety system compatible remote
persons in order to avoid a hazard. controller can be used as the user interface. See
technical data sheet for remote controller compatibility
(e.g. BRC1H52/82*).
▪ The user interface has to be put in the same room as
the indoor unit. For details, please refer to the
installation and operation manual of the user interface.

For the user

3 User safety instructions ▪ Do NOT sit, climb or stand on the


Always observe the following safety instructions and regulations.
unit.
▪ Units are marked with the following symbol:
3.1 General
WARNING
If you are NOT sure how to operate the This means that electrical and electronic products may NOT be
mixed with unsorted household waste. Do NOT try to dismantle
unit, contact your installer. the system yourself: the dismantling of the system, treatment of
the refrigerant, of oil and of other parts must be done by an
WARNING authorized installer and must comply with applicable legislation.
Units must be treated at a specialized treatment facility for reuse,
This appliance is not intended for use recycling and recovery. By ensuring this product is disposed of
by persons, including children, with correctly, you will help to prevent potential negative consequences
for the environment and human health. For more information,
reduced physical, sensory or mental contact your installer or local authority.
capabilities, or lack of experience and ▪ Batteries are marked with the following symbol:
knowledge, unless they have been
given supervision or instruction
concerning use of the appliance by a This means that the batteries may NOT be mixed with unsorted
person responsible for their safety. household waste. If a chemical symbol is printed beneath the
symbol, this chemical symbol means that the battery contains a
Children should be supervised to heavy metal above a certain concentration.
ensure that they do not play with the Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility
appliance. for reuse. By ensuring waste batteries are disposed of correctly,
you will help to prevent potential negative consequences for the
Cleaning and user maintenance must environment and human health.
not be carried out by children without
supervision. 3.2 Instructions for safe operation
WARNING WARNING
To prevent electrical shocks or fire: ▪ Do not modify, disassemble, remove,
▪ Do NOT rinse the unit. reinstall or repair the unit yourself as
▪ Do NOT operate the unit with wet incorrect dismantling or installation
hands. may cause an electric shock or fire.
Contact your dealer.
▪ Do NOT place any objects containing
water on the unit.
CAUTION
▪ Do NOT place any objects or
equipment on top of the unit.

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 5
3 User safety instructions

▪ In case of accidental refrigerant CAUTION


leaks, make sure there are no naked Do NOT operate the system when
flames. The refrigerant itself is using a room fumigation-type
entirely safe, non-toxic and mildly insecticide. Chemicals could collect in
flammable, but it will generate toxic the unit, and endanger the health of
gas when it accidentally leaks into a people who are hypersensitive to
room where combustible air from fan chemicals.
heaters, gas cookers, etc. is present.
Always have qualified service CAUTION
personnel confirm that the point of NEVER expose little children, plants or
leakage has been repaired or animals directly to the airflow.
corrected before resuming operation.
WARNING
CAUTION
Do NOT place objects below the indoor
This unit is equipped with electrically and/or outdoor unit that may get wet.
powered safety measures, such as a Otherwise condensation on the unit or
refrigerant leak detector. In order to be refrigerant pipes, air filter dirt or drain
effective, the unit must be electrically blockage may cause dripping, and
powered at all times after installation, objects under the unit may get dirty or
except for short service periods. damaged.
CAUTION WARNING
▪ NEVER touch the internal parts of the Do NOT place a flammable spray
controller. bottle near the air conditioner and do
▪ Do NOT remove the front panel. NOT use sprays near the unit. Doing
Some parts inside are dangerous to so may result in a fire.
touch and appliance problems may Maintenance and service (see "7 Maintenance and
happen. For checking and adjusting service" 4
[ 9])

the internal parts, contact your CAUTION: Pay attention to the fan!
dealer.
It is dangerous to inspect the unit while
WARNING the fan is running.
This unit contains electrical and hot Be sure to turn off the main switch
parts. before executing any maintenance
task.
WARNING
Before operating the unit, be sure the CAUTION
installation has been carried out Do NOT insert fingers, rods or other
correctly by an installer. objects into the air inlet or outlet. When
the fan is rotating at high speed, it will
CAUTION cause injury.
It is not good for your health to expose
your body to the air flow for a long WARNING
time. Never replace a fuse with a fuse of a
wrong ampere ratings or other wires
CAUTION when a fuse blows out. Use of wire or
To avoid oxygen deficiency, ventilate copper wire may cause the unit to
the room sufficiently if equipment with break down or cause a fire.
burner is used together with the
system.

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
6 3P599562-1 – 2020.05
4 About the system

CAUTION burner, a heater, or a cooker, this may


After a long use, check the unit stand result in fire, or the formation of a
and fitting for damage. If damaged, the harmful gas.
unit may fall and result in injury. Turn off any combustible heating
devices, ventilate the room, and
CAUTION contact the dealer where you
Before accessing terminal devices, purchased the unit.
make sure to interrupt all power supply. Do NOT use the unit until a service
DANGER: RISK OF person confirms that the part from
ELECTROCUTION which the refrigerant leaked has been
repaired.
To clean the air conditioner or air filter,
be sure to stop operation and turn all WARNING
power supplies off. Otherwise, an The appliance shall be stored in a
electric shock and injury may result. room without continuously operating
WARNING ignition sources (example: open
flames, an operating gas appliance or
Be careful with ladders when working
an operating electric heater).
in high places.
WARNING
CAUTION
It is necessary to replace the sensor
Turn off the unit before cleaning the air
after every detection or at the end of
filter and air outlet.
the lifetime. Authorized person only
WARNING MUST replace the sensor.
Do NOT let the indoor unit get wet. Troubleshooting (see "8 Troubleshooting" 4
[ 11])

Possible consequence: Electric WARNING


shock or fire.
Stop operation and shut off the
About the refrigerant (see "7.5 About the refrigerant" 4
[ 10]) power if anything unusual occurs
WARNING: MILDLY FLAMMABLE (burning smells etc.).
MATERIAL Leaving the unit running under such
The refrigerant inside this unit is mildly circumstances may cause breakage,
flammable. electric shock or fire. Contact your
dealer.
WARNING
▪ Do NOT pierce or burn refrigerant
cycle parts. 4 About the system
▪ Do NOT use cleaning materials or WARNING

means to accelerate the defrosting ▪ Do not modify, disassemble, remove, reinstall or repair
the unit yourself as incorrect dismantling or installation
process other than those may cause an electric shock or fire. Contact your
recommended by the manufacturer. dealer.
▪ In case of accidental refrigerant leaks, make sure there
▪ Be aware that the refrigerant inside are no naked flames. The refrigerant itself is entirely
the system is odourless. safe, non-toxic and mildly flammable, but it will
generate toxic gas when it accidentally leaks into a
WARNING room where combustible air from fan heaters, gas
cookers, etc. is present. Always have qualified service
The refrigerant inside the unit is mildly personnel confirm that the point of leakage has been
flammable, but normally does NOT repaired or corrected before resuming operation.

leak. If the refrigerant leaks in the room


and comes in contact with fire from a

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 7
5 User interface
NOTICE
5 User interface
Do NOT use the system for other purposes. In order to
avoid any quality deterioration, do NOT use the unit for CAUTION
cooling precision instruments, food, plants, animals, or
▪ NEVER touch the internal parts of the controller.
works of art.
▪ Do NOT remove the front panel. Some parts inside are
NOTICE dangerous to touch and appliance problems may
happen. For checking and adjusting the internal parts,
For future modifications or expansions of your system:
contact your dealer.
A full overview of allowable combinations (for future
system extensions) is available in technical engineering NOTICE
data and should be consulted. Contact your installer to
Do NOT wipe the controller operation panel with benzine,
receive more information and professional advice.
thinner, chemical dust cloth, etc. The panel may get
discoloured or the coating peeled off. If it is heavily dirty,
CAUTION
soak a cloth in water-diluted neutral detergent, squeeze it
This unit is equipped with electrically powered safety well and wipe the panel clean. Wipe it with another dry
measures, such as a refrigerant leak detector. In order to cloth.
be effective, the unit must be electrically powered at all
times after installation, except for short service periods. NOTICE
NEVER press the button of the user interface with a hard,
4.1 System layout pointed object. The user interface may be damaged.

NOTICE
INFORMATION
NEVER pull or twist the electric wire of the user interface. It
The following illustration is an example and might NOT
may cause the unit to malfunction.
match your system layout.
This operation manual offers a non-exhaustive overview of the main
d functions of the system.
For more information about the user interface, see the operation
manual of the installed user interface.

f
6 Operation
a
g 6.1 Operation range
INFORMATION
For the operation limits see the technical data of the
c connected outdoor unit.

b
6.2 About operation modes
INFORMATION
Depending on the installed system, some operation modes
will not be available.
▪ The air flow rate may adjust itself depending on the room
temperature or the fan may stop immediately. This is not a
malfunction.
▪ If the main power supply is turned off during operation, operation
a Indoor unit will restart automatically after the power turns back on again.
b Outdoor unit
▪ Setpoint. Target temperature for the Cooling, Heating, and Auto
c User interface
d Suction air operation modes.
e Discharge air
f Refrigerant piping + transmission cable
▪ Setback. A function that keeps the room temperature in a specific
g Drain pipe range when the system is turned off (by the user, the schedule
function, or the OFF timer).

6.2.1 Basic operation modes


The indoor unit can operate in various operation modes.
Icon Operation mode
Cooling. In this mode, cooling will be activated as
required by the setpoint, or by Setback operation.

Heating. In this mode, heating will be activated as


required by the setpoint, or by Setback operation.

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
8 3P599562-1 – 2020.05
7 Maintenance and service
Icon Operation mode WARNING
Fan only. In this mode, air circulates without heating Never replace a fuse with a fuse of a wrong ampere ratings
or cooling. or other wires when a fuse blows out. Use of wire or
copper wire may cause the unit to break down or cause a
Auto. In Auto mode, the indoor unit automatically fire.
switches between heating and cooling mode, as
required by the setpoint. CAUTION
After a long use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.

6.2.2 Special heating operation modes NOTICE


Do NOT wipe the controller operation panel with benzine,
Operation Description thinner, chemical dust cloth, etc. The panel may get
Defrost To prevent a loss of heating discoloured or the coating peeled off. If it is heavily dirty,
capacity due to frost soak a cloth in water-diluted neutral detergent, squeeze it
accumulation in the outdoor unit, well and wipe the panel clean. Wipe it with another dry
the system will automatically cloth.
switch to defrost operation.
CAUTION
During defrost operation, the
indoor unit fan will stop Before accessing terminal devices, make sure to interrupt
operation, and the following icon all power supply.
will appear on the home screen:
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop
operation and turn all power supplies off. Otherwise, an
The system will resume normal electric shock and injury may result.
operation after approximately 6
to 8 minutes. WARNING

Hot start During hot start, the indoor unit Be careful with ladders when working in high places.
fan will stop operation, and the Following symbols may occur on the indoor unit:
following icon will appear on the
home screen: Symbol Explanation
Measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.

6.3 To operate the system


INFORMATION 7.2 Cleaning the air filter and air outlet
For setting of the operation mode or other settings, see the CAUTION
reference guide or operation manual of the user interface.
Turn off the unit before cleaning the air filter and air outlet.

7.2.1 To clean the air filter


7 Maintenance and service
When to clean the air filter:
▪ Rule of thumb: Clean every 6 months. If the air in the room is
7.1 Precautions for maintenance and extremely contaminated, increase the cleaning frequency.
service ▪ Depending on the settings, the user interface can display the
"Time to clean filter" notification. Clean the air filter when the
NOTICE
notification is displayed.
Maintenance MUST be done by an authorized installer or
▪ If the dirt becomes impossible to clean, change the air filter
service agent.
(= optional equipment).
We recommend performing maintenance at least once a
How to clean the air filter:
year. However, applicable legislation might require shorter
maintenance intervals. 1 Remove the air filter. Push the hooks and pull the filter as
shown in illustration below. (2 hooks for 10~32 class or 3 hooks
CAUTION for 40~63 class)
Do NOT insert fingers, rods or other objects into the air rear suction bottom suction
inlet or outlet. When the fan is rotating at high speed, it will
cause injury.

NOTICE
Never inspect or service the unit by yourself. Ask a
2
qualified service person to perform this work. However, as 1
2
end user, you may clean the air filter and air outlet. 1

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 9
7 Maintenance and service
2 Clean the air filter. Use a vacuum cleaner or wash with water. ▪ Clean the air filter and the casing of the indoor unit (see
If the air filter is very dirty, use a soft brush and neutral "7.2 Cleaning the air filter and air outlet" 4
[ 9]).
detergent.
▪ Turn on the power at least 6 hours before operating the unit in
order to ensure smoother operation. As soon as the power is
turned on, the user interface display appears.
▪ Insert batteries in the user interface (if applicable).

7.5 About the refrigerant


This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
3 Dry the air filter in the shadow. Refrigerant type: R32
4 Reattach the air filter. Hook the filter behind the flap and Global warming potential (GWP) value: 675
attach the filter to the main unit while pushing down on the
hooks. NOTICE
rear suction bottom suction Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent
tonnes: GWP value of the refrigerant × total refrigerant
2
charge [in kg] / 1000
1
2
1
Please contact your installer for more information.

WARNING: MILDLY FLAMMABLE MATERIAL


5 Make sure that hooks are properly fixed. The refrigerant inside this unit is mildly flammable.
6 Turn ON the power. WARNING
7 To remove warning screens, see the reference guide of the The appliance shall be stored in a room without
user interface. continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
7.2.2 To clean the air outlet heater).

WARNING WARNING
Do NOT let the indoor unit get wet. Possible ▪ Do NOT pierce or burn refrigerant cycle parts.
consequence: Electric shock or fire.
▪ Do NOT use cleaning materials or means to accelerate
NOTICE the defrosting process other than those recommended
by the manufacturer.
▪ Do NOT use gasoline, benzene, thinner polishing
powder or liquid insecticide. Possible consequence: ▪ Be aware that the refrigerant inside the system is
Discoloration and deformation. odourless.

▪ Do NOT use water or air of 50°C or higher. Possible WARNING


consequence: Discoloration and deformation.
The refrigerant inside the unit is mildly flammable, but
Clean with a soft cloth. If it is difficult to remove stains, use water or normally does NOT leak. If the refrigerant leaks in the
a neutral detergent. room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.
7.3 Maintenance before a long stop
Turn off any combustible heating devices, ventilate the
period room, and contact the dealer where you purchased the
E.g., at the end of the season. unit.

▪ Let the indoor units run in fan only operation for about half a day in Do NOT use the unit until a service person confirms that
order to dry the interior of the units. the part from which the refrigerant leaked has been
repaired.
▪ Turn off the power. The user interface display disappears.
▪ Clean air filters and casings of indoor units (see "7.2 Cleaning the 7.5.1 About the refrigerant leakage sensor
air filter and air outlet" 4
[ 9]).
▪ Remove the batteries from the user interface (if applicable). WARNING
It is necessary to replace the sensor after every detection
or at the end of the lifetime. Authorized person only MUST
7.4 Maintenance after a long stop replace the sensor.
period
NOTICE
E.g., at the beginning of the season.
Functionality of the safety measures are periodically
▪ Check and remove everything that might be blocking inlet and automatically checked. In case of malfunction, error code
outlet vents of indoor units and outdoor units. will display on the user interface.

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
10 3P599562-1 – 2020.05
8 Troubleshooting
NOTICE WARNING
The R32 refrigerant leakage sensor is a semiconductor Stop operation and shut off the power if anything
detector which may incorrectly detect substances other unusual occurs (burning smells etc.).
than R32 refrigerant. Avoid using chemical substances
Leaving the unit running under such circumstances may
(e.g. organic solvents, hair spray, paint) in high
cause breakage, electric shock or fire. Contact your dealer.
concentrations, in the close proximity of the indoor unit
because this may cause misdetection of the R32 The system MUST be repaired by a qualified service person.
refrigerant leakage sensor.
Malfunction Measure
INFORMATION If a safety device such as a fuse, a Turn OFF all main power
circuit breaker or a residual current supply switches to the
Lifetime of the sensor is 10 years. The user interface
device frequently actuates or the ON/ unit.
displays error "CH-05" 6 months before the end of the
OFF switch does NOT function properly.
sensor lifetime and error "CH-02" after the end of the
sensor lifetime. For more information refer to the reference If water leaks from the unit. Stop operation.
guide of the user interface and contact you dealer. The operation switch does NOT function Turn OFF the power
properly. supply.
In case of detection when the unit is standby
If the user interface displays . Notify your installer and
When the detection occurs when the unit is standby, "false detection report the error code. To
check" will occur. display an error code see
False detection check the reference guide of the
user interface.
1 Unit starts fan operation on the lowest setting.
2 User interface displays error code "A0-13", emits alarm sound If the system does NOT operate properly except for the above
and status indicator is blinking. mentioned cases and none of the above mentioned malfunctions is
evident, investigate the system in accordance with the following
3 Sensor checks if refrigerant leakage or misdetection occurred. procedures.
▪ If refrigerant leakage is NOT detected, Result: system returns to
INFORMATION
normal operation after approximately 2 minutes.
Refer to the reference guide located on http://
▪ If refrigerant leakage is detected, Result:
www.daikineurope.com/support-and-manuals/product-
1 User interface displays error "A0-11", emits alarm sound and information/ for more troubleshooting tips.
status indicator is blinking.
If after checking all above items, it is impossible to fix the problem
2 Contact your dealer immediately. For more information, see the yourself, contact your installer and state the symptoms, the complete
installation manual of the outdoor unit. model name of the unit (with manufacturing number if possible) and
In case of detection when the unit is turned on the installation date (possibly listed on the warranty card).

1 User interface displays error "A0-11", emits alarm sound and


status indicator is blinking.
2 Contact your dealer immediately. For more information, see the 9 Relocation
installation manual of the outdoor unit. Contact your dealer for removing and reinstalling the total unit.
INFORMATION Moving units requires technical expertise.

To stop alarm of the user interface see the reference guide


of the user interface.
10 Disposal
INFORMATION
The minimum airflow during normal operation or during the NOTICE
refrigerant leakage detection is always >240 m3/h. Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
8 Troubleshooting reuse, recycling and recovery.
If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 11
11 About the box

For the installer

11 About the box 12.1.1 Installation site requirements of the


indoor unit

11.1 Indoor unit INFORMATION


The sound pressure level is less than 70 dBA.
11.1.1 To remove the accessories from the ▪ Spacing. Mind the following requirements:
indoor unit
A
a

≥300 ≥300

b b
C
B

e ≥240
200
≥20
c c

A
A a b B c ≥400
1× 1× 1×
d ≥620

f (mm)

A Minimum distance to the floor:


C d e f g h i 2.7 m to avoid accidental touching.
8× 26× 1× 1× 2× 2.5 m in case the fan is covered (e.g. false ceiling, grille,
…)

1× a Control box
b Maintenance space
c Ceiling
C j k l m d Ceiling opening
1× 1× 4× e Select the dimension to ensure downward slope of at
8× least 1/100
4× f Floor surface
▪ Discharge grille. Minimum requirement installation height of
A On the unit discharge grille ≥1.8 m.
a Installation and operation manual
b General safety precautions ▪ Ceiling opening size. Make sure the ceiling opening is within the
following limits:
B On the bottom of the packing box
c Air filter

C In the fan motor space


d Washers for hanger bracket
e Screws for duct flanges
f Metal clamp
g Sealing pads: middle and large
h Drain hose
A

i Sealing material
j Insulation piece: Small (liquid pipe)
k Insulation piece: Large (gas pipe)
l Tie wraps: small and large
m Washer fixing plate

12 Unit installation 620 (mm)

12.1 Preparing the installation site 12‒1 Ceiling opening dimension (A)
Class A (mm)
Avoid installation in an environment with a lot of organic solvents
such as ink and siloxane. 10~32 790
40~50 990
WARNING
63 1190
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
12 3P599562-1 – 2020.05
12 Unit installation
Service space
12.2 Mounting the indoor unit
A B

12.2.1 Guidelines when installing the indoor unit

300
INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
620
Depending on the field conditions, it might be easier to

C
install the optional equipment first.

Installation options

INFORMATION

300
The unit can be used with bottom suction by replacing the
interchangeable plate by the air filter holding plate.
620
a
A Side view
B Top view
C Class 10~32: 750 mm
Class 40+50: 950 mm
Class 63: 1150 mm

Installation options
A
b

a b ≥620
B

a
a b ≥620 cd a e a Air filter holding plate with air filter (accessory)
b Interchangeable plate
C 100
▪ Air filter. Attach the air filter (accessory) by pushing down the
hooks (2 hooks for 10~32 type, 3 hooks for 40~63 type).
200

rear suction bottom suction


c
(160~300)

d
160

a f ≥400 a
b ≥620 (mm)
A Standard rear suction 2
1
B Installation with rear canvas duct and duct 2
1
C Installation with bottom canvas duct and air inlet grill
a Ceiling surface
b Ceiling opening
c Flange (field supply) ▪ Ceiling strength. Check whether the ceiling is strong enough to
d Canvas connection for air inlet panel (field supply)
e Duct
support the weight of the unit. If there is a risk, reinforce the ceiling
f Air inlet panel (field supply) opening with air filter (field before installing the unit.
supply)
▪ For existing ceilings, use anchors.
INFORMATION ▪ For new ceilings, use sunken inserts, sunken anchors or other
Some options may require additional service space. Refer field supplied parts.
to the installation manual of the used option before b
installation. a
Minimum floor area requirements
c
d
CAUTION
e
The total refrigerant charge in the system cannot exceed
a Anchor
the requirements for minimum floor area of the smallest
b Ceiling slab
room that is served. For minimum floor area requirements c Long nut or turnbuckle
for indoor units, see the installation and operation manual d Suspension bolt
of the outdoor unit. e Indoor unit
▪ Suspension bolts. Use M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely
using a nut and washer from the upper and lower sides of the
hanger bracket.

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 13
12 Unit installation
CAUTION
▪ Make sure the installation of the duct does NOT exceed
the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.
4× ▪ Make sure to install the canvas duct so vibrations are
NOT transmitted to the duct or ceiling. Use a sound-
a absorbing material (insulation material) for the lining of
b
the duct and apply vibration insulation rubber to the
c hanging bolts.
e: A

b ▪ When welding, make sure NOT to spatter onto the


d drain pan or the air filter.
▪ If the metal duct passes through a metal lath, wire lath
or metal plate of the wooden structure, separate the
duct and wall electrically.
▪ Install the outlet grille in a position where the airflow will
e: 500 (mm) not come into direct contact with people.
a Nut (field supply) ▪ Do NOT use booster fans in the duct. Use the function
b Washer (accessories) to adjust the fan rate setting automatically (see
c Hanger bracket "16.1 Field setting" 4
[ 19]).
d Double nut (field supply)
e Suspension bolt pitch The ducting is to be field supplied.
12‒2 Suspension bolt pitch (A) 1 Air inlet side. Connect the inlet side flange (field supply) to the
indoor unit, use screws from accessory (table below). Connect
Class A (mm)
the canvas duct to the inside of the inlet side flange. Connect
10~32 740 the duct to the canvas duct.
40~50 940 Number of screws according to class
63 1140 10~32 40~50 63
▪ Level. Make sure the unit is level at all four corners using a level 16 22 26
or a water-filled vinyl tube.
2 Air outlet side. Connect the canvas duct to the inside of the
outlet side flange. Connect the duct to the canvas duct.
a b c b a

a
a Water level
b Vinyl tube

NOTICE d e f f e d
Do NOT install the unit tilted. Possible consequence: If a Screws for duct flanges
the unit is tilted against the direction of the condensate flow For air inlet side: accessory
(the drain piping side is raised), the float switch might For air outlet side: on the unit
malfunction and cause water to drip. b Flange
For air inlet side: field supply
For air outlet side: on the unit
c Indoor unit
d Insulation (field supply)
12.2.2 Guidelines when installing the ducting e Canvas duct (field supply)
f Aluminium tape (field supply)
WARNING 3 Wind aluminium tape around the flange and duct connection on
Do NOT install operating ignition sources (example: open both sides. Make sure there are no air leaks at any other
flames, an operating gas appliance or an operating electric connection.
heater) in the duct work. 4 Insulate the duct to prevent condensation from forming. Use
glass wool or polyethylene foam 25 mm thick.
▪ Filter. Be sure to attach an air filter inside the air passage on the
intake side. Use an air filter with dust collecting efficiency ≥50%
(gravimetric method). The included filter is not used when the
intake duct is attached.

12.2.3 Guidelines when installing the drain


piping
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
14 3P599562-1 – 2020.05
12 Unit installation
▪ Checking for water leaks

General guidelines
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 20 mm nominal diameter and
26 mm outer diameter).
▪ Slope. Make sure the drain piping slopes down (at least 1/100) to a Drain outlet for maintenance
prevent air from being trapped in the piping. Use hanging bars as b Refrigerant pipes
shown. c Drain pipe connection
1 Push the drain hose as far as possible over the drain pipe
connection.
2 Tighten the metal clamp until the screw head is less than 4 mm
1~1.5 m
from the metal clamp part.
a 3 Check for water leaks (see "To check for water leaks" 4
[ 16]).
4 Wind the large sealing pad (= insulation) around the metal
a Hanging bar clamp and drain hose, and fix it with tie wraps.
O Allowed
X Not allowed 5 Connect the drain piping to the drain hose.
▪ Condensation. Take measures against condensation. Insulate 1 2~6
the complete drain piping in the building. c d e
2 4 5
▪ Rising piping. If necessary to make the slope possible, you can
install rising piping.
▪ Drain hose inclination: 0~75 mm to avoid stress on the piping A
and to avoid air bubbles. 1

a b
≤300 1000~1500
A'
A' ≤4 mm
0~75

≤600

d
a b 3 A-A' c
b
(mm) a

a b c d d a Drain pipe connection (attached to the unit)


b Drain hose (accessory)
a Metal clamp (accessory) c Metal clamp (accessory)
b Drain hose (accessory) d Large sealing pad (accessory)
c Rising drain piping (vinyl pipe nominal Ø20 mm and outer e Drain piping (field supply)
Ø26 mm)
d Hanging bars (field supply) NOTICE
▪ Combining drain pipes. You can combine drain pipes. Make ▪ Do NOT remove the drain pipe plug. Water might leak
sure to use drain pipes and T-joints with the correct gauge for the out.
operating capacity of the units.
▪ Use the drain outlet only to discharge the water before
maintenance.
≥100

▪ Insert and remove the drain plug gently. Excessive


force may deform the drain socket of the drain pan.
a
Pull out the plug.
▪ Do NOT wiggle the plug up and down.
a
≤600

(mm)

a T-joint
Push in the plug.
To connect the drain piping to the indoor unit
▪ Set the plug and push it in using a Phillips screwdriver.
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 15
13 Piping installation
▪ Remove the service cover.
a ▪ Disconnect the power supply.
▪ Disconnect the user interface.
b ▪ Reattach the service cover.

When installation of the system is already completed


1 Start cooling operation (see the reference guide or the service
manual of the user interface).
2 Gradually pour approximately 1 l of water through the water
a Drain plug inlet, and check for leaks (see "When installation of the system
b Philips screwdriver is not yet completed" 4[ 16]).
To check for water leaks
The procedure differs depending on whether installation of the
system is already completed. When installation of the system is not
13 Piping installation
yet completed, temporarily connect the user interface and power
supply to the unit.
13.1 Preparing refrigerant piping
When installation of the system is not yet completed
1 Temporarily connect electrical wiring. 13.1.1 Refrigerant piping requirements
▪ Remove the service cover. CAUTION
▪ Connect the power supply (a).
▪ Connect the user interface (b). Piping MUST be installed according to instructions given in
▪ Reattach the service cover. "13 Piping installation" 4
[ 16]. Only mechanical joints (e.g.
braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.

NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant.
▪ Foreign materials inside pipes (including oils for fabrication) must
be ≤30 mg/10 m.

Refrigerant piping diameter


N L

For piping connections of the indoor unit use the following piping
b a diameters:
a Power supply terminal block Class Pipe outer diameter (mm)
b User interface terminal block
Liquid piping Gas piping
2 Turn ON the power supply.
10~32 Ø6.4 mm Ø9.5 mm
3 Start fan only operation (see the reference guide or the service
40~63 Ø6.4 mm Ø12.7 mm
manual of the user interface).
4 Remove the water inlet cover (1 screw). Refrigerant piping material
5 Gradually pour approximately 1 l of water through the water ▪ Piping material: Phosphoric acid deoxidised seamless copper.
inlet, and check for leaks.
▪ Flare connections: Only use annealed material.
▪ Piping temper grade and thickness:
Outer diameter Temper grade Thickness (t)(a)
(Ø)
6.4 mm (1/4") Annealed (O) ≥0.8 mm Ø
t
9.5 mm (3/8")
12.7 mm (1/2")
(a)
Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
f a e c d b

a Water inlet 13.1.2 Refrigerant piping insulation


b Portable pump
c Water inlet cover
▪ Use polyethylene foam as insulation material:
d Bucket (adding water through water inlet)
e Drain outlet for maintenance ▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
f Refrigerant pipes
and 0.045 kcal/mh°C)
6 Turn OFF the power.
▪ with a heat resistance of at least 120°C
7 Disconnect the electrical wiring.
▪ Insulation thickness

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
16 3P599562-1 – 2020.05
14 Electrical installation
Pipe outer diameter Insulation inner Insulation thickness
(Øp) diameter (Øi) (t)
14 Electrical installation
6.4 mm (1/4") 8~10 mm ≥10 mm DANGER: RISK OF ELECTROCUTION
9.5 mm (3/8") 12~15 mm ≥13 mm
12.7 mm (1/2") 14~16 mm ≥13 mm WARNING

Øi ALWAYS use multicore cable for power supply cables.


Øp
t WARNING
Use an all-pole disconnection type breaker with at least
3 mm between the contact point gaps that provide full
If the temperature is higher than 30°C and the humidity is higher
disconnection under overvoltage category III.
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the WARNING
insulation.
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
13.2 Connecting the refrigerant piping persons in order to avoid a hazard.

DANGER: RISK OF BURNING/SCALDING


14.1 Specifications of standard wiring
13.2.1 To connect the refrigerant piping to the
components
indoor unit Component Class
10 15 20~32 40 50 63
CAUTION
Power MCA(a) 0.3 A 0.4 A 0.6 A 0.8 A 0.9 A 1A
Install the refrigerant piping or components in a position
supply Voltage 220~240 V
where they are unlikely to be exposed to any substance
cable
which may corrode components containing refrigerant, Phase 1~
unless the components are constructed of materials that Frequency 50/60 Hz
are inherently resistant to corrosion or are suitably
protected against corrosion. Wire sizes 1.5 mm2 (3‑core wire)
H07RN-F (60245 IEC 66)
WARNING: MILDLY FLAMMABLE MATERIAL
Transmission wiring 0.75 to 1.25 mm² (2‑core wire)
The refrigerant inside this unit is mildly flammable. User interface cable H05RN-F (60245 IEC 57)
▪ Pipe length. Keep refrigerant piping as short as possible. User interface - maximum 500 m
▪ Flare connections. Connect refrigerant piping to the unit using Recommended field 6A
flare connections. fuse
▪ Insulation. Insulate the refrigerant piping on the indoor unit as Residual current Must comply with applicable legislation
follows: device
A B (a)
MCA=Minimum circuit ampacity. Stated values are maximum
a b c d b e f a b c d b e f values (see electrical data of indoor unit for exact values).

14.2 To connect the electrical wiring to


1 3 2 1 3 2 the indoor unit
g4
NOTICE
A B ▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
A Gas piping ▪ For instructions on how to connect the optional
B Liquid piping
equipment, see the installation manual delivered with
a Insulation material (field supply) the optional equipment.
b Tie wraps: Large (accessory)
c Insulation pieces: Large (gas pipe), small (liquid pipe)
▪ Make sure the electrical wiring does NOT obstruct
(accessory) proper reattachment of the service cover.
d Flare nut (attached to the unit)
e Refrigerant pipe connection (attached to the unit) It is important to keep the power supply and the transmission wiring
f Unit separated from each other. In order to avoid any electrical
g Sealing pads: Middle (gas pipe) (accessory) interference the distance between both wirings should ALWAYS be
at least 50 mm.
1 Turn up the seams of the insulation pieces.
2 Attach to the base of the unit.
3 Tighten the tie wrap on the insulation pieces.
NOTICE
4 Wrap the sealing pad from the base of the unit to the top Be sure to keep the power line and transmission line apart
of the flare nut.
from each other. Transmission wiring and power supply
NOTICE wiring may cross, but may NOT run parallel.

Make sure to insulate all refrigerant piping. Any exposed 1 Remove the service cover.
piping might cause condensation.

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 17
15 Commissioning
a c d b Control box
a
IN/D OUT/D
F1 F2 F1 F2

eg g
e N L N L N L N L
f

d
AB
N L P1 P2 F1 F2 T1 T2 N L P1 P2 F1 F2 T1 T2 N L P1 P2 F1 F2 T1 T2 N L P1 P2 F1 F2 T1 T2

A Outside the unit b


B Inside the unit
a Service cover
b Connection of power supply P1 P2 P1 P2 P1 P2 P1 P2
c Wiring diagram c
d Connection of transmission and user interface wiring
e Sealing material (accessory)
a Outdoor unit
f Opening for cables
b Indoor unit
g Wire
c User interface
2 User interface cable: Route the cable through the frame, d Most downstream indoor unit
connect the cable to the terminal block (symbols P1, P2) and fix
NOTICE
the cable with a tie wrap.
Group control connection is NOT allowed.
3 Transmission cable: Route the cable through the frame,
connect the cable to the terminal block (make sure the symbols CAUTION
F1, F2 match with the symbols on the outdoor unit), and fix the
cable with a tie wrap. ▪ Each indoor unit has to be connected to a separate
user interface. Only a safety system compatible remote
4 Power supply cable: Route the cable through the frame and controller can be used as the user interface. See
connect the cable to the terminal block (L, N, earth). technical data sheet for remote controller compatibility
a (e.g. BRC1H52/82*).
b
▪ The user interface has to be put in the same room as
the indoor unit. For details, please refer to the
a Circuit breaker
b Residual current device installation and operation manual of the user interface.

15 Commissioning
a NOTICE
ALWAYS operate the unit with thermistors and/or pressure
b sensors/switches. If NOT, burning of the compressor might
a be the result.
P1P2 F1 F2
70~90
10~20
10~15 15.1 Checklist before commissioning
N L
7

After the installation of the unit, first check the items listed below.
70~90

Once all checks are fulfilled, the unit must be closed. Power-up the
10~15

d c d unit after it is closed.


You read the complete installation and operation
instructions, as described in the installer and user
a Opening for cables
b Transmission and user interface wiring reference guide.
c Power supply wiring The indoor unit is properly mounted.
d Tie wrap (accessory)
X Not allowed
O Allowed The outdoor unit is properly mounted.
5 Wrap the cables with the sealing material (accessory) to
prevent water from entering the unit. Seal all gaps to prevent Make sure drain piping is properly installed, insulated
small animals from entering the system. and drainage flows smoothly. Check for water leaks.

6 Reattach the service cover. Possible consequence: Condensate water might drip.
The ducting is properly installed and insulated.
Complete system example
1 user interface controls 1 indoor unit. The refrigerant pipes (gas and liquid) are installed
correctly and thermally insulated.
There are NO refrigerant leaks.

There are NO missing phases or reversed phases.

The system is properly earthed and the earth terminals


are tightened.

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
18 3P599562-1 – 2020.05
16 Configuration
The fuses or locally installed protection devices are If the distance to the floor is (m) Then(1)
installed according to this document, and have NOT been M SW —
bypassed.
≤2.7 13 (23) 0 01
The power supply voltage matches the voltage on the
2.7<x≤3.0 02
identification label of the unit.
3.0<x≤3.5 03
There are NO loose connections or damaged electrical
components in the switch box. Setting: Static pressure
There are NO damaged components or squeezed Change the value number (—) in accordance with the external static
pipes on the inside of the indoor and outdoor units. pressure of the duct to be connected as in the table below. See
The stop valves (gas and liquid) on the outdoor unit are technical documentation for details.
fully open.
Setting(1) External static pressure
M SW —
15.2 To perform a test run 13(23) 5 01 Standard

INFORMATION 02 High static pressure setting

▪ Perform the test run according to the instructions in the Setting: Air volume when thermostat control is OFF
outdoor unit manual. This setting must correspond with the needs of the user. It
▪ The test run is only completed if there is no malfunction determines the fan speed of the indoor unit during thermostat OFF
code displayed on the user interface or the outdoor unit condition.
7‑segment display. 1 If you have set the fan to operate, set the air volume speed:
▪ See the service manual for the complete list of error If you want… Then(1)
codes and a detailed troubleshooting guideline for each
error. M SW —
(2)
During thermostat LL 12 (22) 6 01
NOTICE OFF at cooling Setup volume(2) 02
Do NOT interrupt the test run. operation
OFF(a) 03
Monitoring 1(2) 04
(2)
Monitoring 2 05
16 Configuration During thermostat LL(2) 12 (22) 3 01
OFF at heating Setup volume(2) 02
operation
16.1 Field setting OFF(a) 03
(2)
Monitoring 1 04
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user: Monitoring 2(2) 05
(a)
▪ Ceiling height Only use in combination with optional remote sensor or when
setting M 10 (20), SW 2, — 3 is used.
▪ Static pressure
▪ Air volume when thermostat control is OFF Setting: Time to clean air filter

▪ Time to clean air filter This setting must correspond with the air contamination in the room.
It determines the interval at which "Time to clean filter" notification
▪ Thermostat sensor selection is displayed on the user interface.
▪ Differential for automatic changeover If you want an interval of… Then(1)
▪ Auto-restart after power failure (air contamination) M SW —

INFORMATION ±2500 h (light) 10 (20) 0 01

▪ The fan speed of the indoor unit is preset to ensure the ±1250 h (heavy) 02
standard external static pressure. Notification ON 3 01
▪ To set a higher or lower external static pressure, reset Notification OFF 02
the initial setting with the user interface.
Setting: Thermostat sensor selection
Setting: Ceiling height This setting must correspond with how/if the remote controller
This setting must correspond with the actual distance to the floor, thermostat sensor is used.
capacity class and air flow directions.

(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
• : Default
(2)
Fan speed:
• LL: Low fan speed (set during thermostat OFF)
• L: Low fan speed (set by the user interface)
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by LL (Monitoring 1) or by L
(Monitoring 2).

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 19
17 Technical data
When the remote controller thermostat Then(1) 17.1 Wiring diagram
sensor is… M SW —
Used in combination with indoor unit 10 (20) 2 01 17.1.1 Unified wiring diagram legend
thermistor
For applied parts and numbering, refer to the wiring diagram on the
Not used (indoor unit thermistor only) 02
unit. Part numbering is by Arabic numbers in ascending order for
Used exclusively 03 each part and is represented in the overview below by "*" in the part
code.
Setting: Thermostat differential changeover (if remote sensor is
used) Symbol Meaning Symbol Meaning
If the system contains a remote sensor, set the increase/decrease Circuit breaker Protective earth
increments.
If you want to change increments to… Then(1)
M SW —
1°C 12 (22) 2 01 Connection Protective earth (screw)
0.5°C 02 ,
Connector A Rectifier
Setting: Differential for automatic changeover Earth Relay connector
Set temperature difference between cooling setpoint and heating Field wiring Short-circuit connector
setpoint in automatic mode (availability depends on the system
type). Differential is cooling setpoint minus heating setpoint. Fuse Terminal
If you want to Then(1) Example Indoor unit Terminal strip
set… M SW — INDOOR

0°C 12 (22) 4 01 cooling 24°C/heating Outdoor unit Wire clamp


OUTDOOR
24°C
1°C 02 cooling 24°C/heating Residual current
23°C device
2°C 03 cooling 24°C/heating Symbol Colour Symbol Colour
22°C
BLK Black ORG Orange
3°C 04 cooling 24°C/heating
21°C BLU Blue PNK Pink

4°C 05 cooling 24°C/heating BRN Brown PRP, PPL Purple


20°C GRN Green RED Red
5°C 06 cooling 24°C/heating GRY Grey WHT White
19°C YLW Yellow
6°C 07 cooling 24°C/heating
18°C Symbol Meaning
7°C 08 cooling 24°C/heating A*P Printed circuit board
17°C BS* Pushbutton ON/OFF, operation
switch
Setting: Auto-restart after power failure
BZ, H*O Buzzer
Depending on the needs of the user, you may disable/enable the
C* Capacitor
automatic restart after a power failure.
AC*, CN*, E*, HA*, HE*, HL*, Connection, connector
If you want auto-restart after power Then(1)
HN*, HR*, MR*_A, MR*_B, S*, U,
failure… M SW — V, W, X*A, K*R_*, NE
Disabled 12 (22) 5 01 D*, V*D Diode
Enabled 02 DB* Diode bridge
DS* DIP switch
E*H Heater
17 Technical data FU*, F*U, (for characteristics, Fuse
refer to PCB inside your unit)
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible). FG* Connector (frame ground)

▪ The full set of latest technical data is available on the Daikin H* Harness
Business Portal (authentication required). H*P, LED*, V*L Pilot lamp, light emitting diode
HAP Light emitting diode (service
monitor green)
HIGH VOLTAGE High voltage

(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
• : Default

Installation and operation manual FXDA10~63A2VEB


VRV system air conditioner
20 3P599562-1 – 2020.05
17 Technical data
Symbol Meaning Symbol Meaning
IES Intelligent eye sensor Z*C Ferrite core
IPM* Intelligent power module ZF, Z*F Noise filter
K*R, KCR, KFR, KHuR, K*M Magnetic relay
L Live
L* Coil
L*R Reactor
M* Stepper motor
M*C Compressor motor
M*F Fan motor
M*P Drain pump motor
M*S Swing motor
MR*, MRCW*, MRM*, MRN* Magnetic relay
N Neutral
n=*, N=* Number of passes through ferrite
core
PAM Pulse-amplitude modulation
PCB* Printed circuit board
PM* Power module
PS Switching power supply
PTC* PTC thermistor
Q* Insulated gate bipolar transistor
(IGBT )
Q*C Circuit breaker
Q*DI, KLM Earth leak circuit breaker
Q*L Overload protector
Q*M Thermo switch
Q*R Residual current device
R* Resistor
R*T Thermistor
RC Receiver
S*C Limit switch
S*L Float switch
S*NG Refrigerant leak detector
S*NPH Pressure sensor (high)
S*NPL Pressure sensor (low)
S*PH, HPS* Pressure switch (high)
S*PL Pressure switch (low)
S*T Thermostat
S*RH Humidity sensor
S*W, SW* Operation switch
SA*, F1S Surge arrester
SR*, WLU Signal receiver
SS* Selector switch
SHEET METAL Terminal strip fixed plate
T*R Transformer
TC, TRC Transmitter
V*, R*V Varistor
V*R Diode bridge, Insulated-gate
bipolar transistor (IGBT) power
module
WRC Wireless remote controller
X* Terminal
X*M Terminal strip (block)
Y*E Electronic expansion valve coil
Y*R, Y*S Reversing solenoid valve coil

FXDA10~63A2VEB Installation and operation manual


VRV system air conditioner
3P599562-1 – 2020.05 21
Copyright 2020 Daikin

3P599562-1 2020.05
Verantwortung für Energie und Umwelt

You might also like