Professional Documents
Culture Documents
E1 testing
procedure
Test Instrument: Four Terminal Earth Electrode Resistance
Tester
i) Isolate the supply.
ii) Disconnect the earthing conductor from the earth electrode, provided
it is safe to do so.
iii) With the four terminal (P1, C1, P2 and C2) instrument, short terminals
P1 and C1 and connect a lead to the earth electrode to be tested.
iv) Place the Current test probe, C2, a distance which is equal to ten times
the length of electrode under test, e.g. 10 × 3 m = 30 m, from the earth
electrode to be tested.
v) The Potential test probe, P2, is placed mid-point between C2 and the
electrode under test.
vi) A minimum of three test readings should be taken, the first with the
potential test probe P2 in its original position then a further two
readings with P2 moved either side of P2’s original position. The
distance should
be equal to 10% of the distance between the electrode under test and
C2. In the example given in (iv) the distance will be 3 metres.
vii) The average of the three readings is calculated and must not be greater
than 21Ω.
viii) On completion of the test the earth must be re-connected.
Caution: If there is just one earth electrode this may leave the installation
unprotected against earth faults, therefore complete isolation of the installation
must be made.
E2 Testing
Procedure
Test Instrument: One test
coil type
The testing method applied with the one test coil type of instrument is similar to
that used for Method El, inasmuch as two temporary test spikes (electrodes) are
used, but the earth electrode under test must not be disconnected.
E3 Testing
Procedure
Test instrument: Earth Fault Loop
Impedance Tester
i) Ensure it is safe to disconnect the earth conductor before testing takes
place.
ii) Isolate the supply before disconnecting the earth conductor.
iii) Connect the leads of the instrument between the installation’s
incoming live conductor and the earth electrode.
iv) The impedance reading taken is treated as the electrode resistance.
v) On completion of the test the earth electrode must be re-connected
Where an installation’s earthing protection is provided by TT, the
essential requirements to secure this type of protection are stipulated in
Regulations 411.5.1–411.5.4of BS 7671.
A significant component in the TT protection system is the RCD. Where
this device is used the following conditions must be fulfilled:
RA × IΔn ≤ 50 volts
Where:
RA is the sum of the resistances of the earth electrode and the
protective conductors connecting it to the exposed-conductive-
parts [in ohms (Ω)].
IΔn is the rated residual operating current of the RCD.
Where RA is not known, it may be replaced in the above equation
with Zs. Consequently the earth fault loop impedance (Zs) can be
determined as follows, after the transposition of the original equation:
50
Zs =
IΔn
where IΔn =
30mA