You are on page 1of 2

Electrical Laboratory

ELECTRICAL SITE INSPECTION AND TEST RECORD SHEET Form: EL-07

Title: LV POWER AND CONTROL CABLES (up to 1000V) Area/Unit: LSC S/S Protocol №: EL-07-4
Date 03.01.2022
Equip Tag No.: 40ANF30 NF1.HA001 DC UPS MCC PS1 Work Order: 222021523107
Sheet. № 1 of 2

1. Insulation resistance standart:


Length, м. Test
Cable tag № As per cable HV Test
Brand and type of cables Cable cross-section Rated voltage, V voltage
schedule Duration
kV
Electric cable 0.6/1kV
40ANF30GS001-
N2XRH (XLPE) CABLES 4x10 400 20 1 1
W101.4
4x10

Insulation test Measurement of insulation resistance, GΩ R min.0.5 MΩ


Ref. IR Test (1kV) 1 min DAR
(GΩ)

L1 - E >1 -

L2 - E >1 -

L3 - E >1 -

L1 – L2 >1 -

L2 – L3 >1 -

L3 – L1 >1 -

L1 - N >1 -
Caterpillar: Confidential Green
Electrical Laboratory

ELECTRICAL SITE INSPECTION AND TEST RECORD SHEET Form: EL-07

Title: LV POWER AND CONTROL CABLES (up to 1000V) Area/Unit: LSC S/S Protocol №: EL-07-4
Date 03.01.2022
Equip Tag No.: 40ANF30 NF1.HA001 DC UPS MCC PS1 Work Order: 222021523107
Sheet. № 2 of 2

L2 – N >1 -

L3 – N >1 -

N–E >1 -

G–E - -

2. Test instrument
Test instrument Manufacturer Model Serial № Expire Date
Mega ohmmeter Megger MIT230 101291956 02/05/2022

3. Remarks: Works were carried out according to WORK ORDER


4. Conclusion: Measurements and testing of the LV power cable’s parameters were performed in compliance with the scopes and regulations IEC 60332,
IEC 60331, VDE 0276-20 According to the complex tests LV power cable is applicable for use.
*This test has done by SPM Oil and Gas Company
Job Title Date Signature Name
Inspected and tested by: HVPT supervisor 03.01.2022
Laboratory Representative: HVPT Technician 03.01.2022