Revision: B
Job No: 18705 Page: C/01
Calcs By: RKR Date: 06/02/2024
Data Input
Provide the dead load factor for the type of roof and state the code
= 0 kN
b) Live Load
All the same data input as above applies in this section so
Provide the live load factor for the type of roof and state the code
= 0 kN
= 168.75 kN
b) Live Load
All the same data input as above applies in this section so
Provide the live load factor for the type of floor area usage and state the code
= 140.625 kN
= 10.625 metres
Provide the unit weight of concrete in this component
= 5.87 kN
= 8.28 kN
Next up we have to take into account the stub of the column just before the base
5) Stub Column Type Rectangle
a) Dead Load
Provide Dimensions of tributary area Section Depth = 0.5
or provide section diameter
= 4.14 kN
Degrees Reduction factor = 1.155
(provide the length to the next support in metres)
(provide the length to the next support in metres)
ASCE 2002
0 X 1.155
ASCE 2002
0 X 1.155
BS
28.125
X 23
or Indiviudal Heights
X 23
Circle Rectangle
Circle Rectangle
Section Width = 0.230 metres
de section diameter = 0.46 which gives 0.16619
Component
Dead No: Result Live No: Result
Roof = 0.00 1 0.00 0.00 1 0.00
Slabs = 168.75 1 168.75 140.63 1 140.63
Walls on Slabs = 0 0 0.00 0 0 0.00
Beams = 5.87 3 17.60 0 3 0.00
Walls on Beams = 89.27 1 89.27 0 1 0.00
Columns = 8.28 2 16.56 0 2 0.00
Stub = 4.14 1 4.14 0 1 0.00
Maximum Allowable Bearing Pressure = 750 kPa or kN/m2 it’s the same