You are on page 1of 2

Clear

new circuit.IEEE9Nodeckt
~ basekv=16.5 pu=1.040 Bus1=Bus1 MVASC3=500000 500000

!GENERATORS
New Generator.B2 Bus1=Bus2 kV= 18 kW=163000 Model=3 Vpu=1.025 Maxkvar=5000
Minkvar=-300000 ! kvar=300000
New Generator.B3 Bus1=Bus3 kV= 13.8 kW=85000 Model=3 Vpu=1.025 Maxkvar=5000
Minkvar=-300000 ! kvar=-11000 !

!TRANSFORMERS
New Transformer.Sub1 Phases=3 Windings=2 XHL=6.25 %loadloss=0
~ wdg=1 bus=Bus2 conn=wye kv=18 kva=100000
~ wdg=2 bus=Bus7 conn=wye kv=230 kva=100000

New Transformer.Sub2 Phases=3 Windings=2 XHL=5.86 %loadloss=0


~ wdg=1 bus=Bus3 conn=wye kv=13.8 kva=100000
~ wdg=2 bus=Bus9 conn=wye kv=230 kva=100000

New Transformer.Sub3 Phases=3 Windings=2 XHL=5.76 %loadloss=0


~ wdg=1 bus=Bus1 conn=wye kv=16.5 kva=100000
~ wdg=2 bus=Bus4 conn=wye kv=230 kva=100000

!LINE CODES
New linecode.bus7_bus8 nphases=3 BaseFreq=60
~ rmatrix = (0.4512 | 0 0.4512 | 0 0 0.4512 )
~ xmatrix = (3.8155 | 0 3.8155 | 0 0 3.8155 )
~ Cmatrix = [149.29 | 0 149.29 | 0 0 149.29 ]
~ units=mi

New linecode.bus8_bus9 nphases=3 BaseFreq=60


~ rmatrix = (0.6339 | 0 0.6339 | 0 0 0.6339 )
~ xmatrix = (5.350858 | 0 5.350858 | 0 0 5.350858 )
~ Cmatrix = [209.23 | 0 209.23 | 0 0 209.23 ]
~ units=mi

New linecode.bus7_bus5 nphases=3 BaseFreq=60


~ rmatrix = (1.721010 | 0 1.721010 | 0 0 1.721010 )
~ xmatrix = (8.584683 | 0 8.584683 | 0 0 8.584683 )
~ Cmatrix = [305.61 | 0 305.61 | 0 0 305.61 ]
~ units=mi

New linecode.bus5_bus4 nphases=3 BaseFreq=60


~ rmatrix = (0.5316 | 0 0.5316 | 0 0 0.5316 )
~ xmatrix = (4.507588 | 0 4.507588 | 0 0 4.507588 )
~ Cmatrix = [176.28 | 0 176.28 | 0 0 176.28 ]
~ units=mi

New linecode.bus4_bus6 nphases=3 BaseFreq=60


~ rmatrix = (0.9036 | 0 0.9036 | 0 0 0.9036 )
~ xmatrix = (4.878219 | 0 4.878219 | 0 0 4.878219 )
~ Cmatrix = [158.26 | 0 158.26 | 0 0 158.26 ]
~ units=mi

New linecode.bus6_bus9 nphases=3 BaseFreq=60


~ rmatrix = (2.1066 | 0 2.1066 | 0 0 2.1066 )
~ xmatrix = (9.285581 | 0 9.285581 | 0 0 9.285581 )
~ Cmatrix = [357.15 | 0 357.15 | 0 0 357.15 ]
~ units=mi

!LOAD DEFINITIONS
New Load.Load8 Bus1=Bus8.1.2.3 Conn=Wye kV=230 kW=100000 kvar=35000
New Load.Load5 Bus1=Bus5.1.2.3 Conn=Wye kV=230 kW=125000 kvar=50000
New Load.Load6 Bus1=Bus6.1.2.3 Conn=Wye kV=230 kW=90000 kvar=30000

!LINE DEFINITIONS
New Line.Line7_8 Phases=3 Bus1=Bus7.1.2.3 Bus2=Bus8.1.2.3 LineCode=bus7_bus8
Length=10 units=mi
New Line.Line8_9 Phases=3 Bus1=Bus8.1.2.3 Bus2=Bus9.1.2.3 LineCode=bus8_bus9
Length=10 units=mi
New Line.Line7_5 Phases=3 Bus1=Bus7.1.2.3 Bus2=Bus5.1.2.3 LineCode=bus7_bus5
Length=10 units=mi
New Line.Line5_4 Phases=3 Bus1=Bus5.1.2.3 Bus2=Bus4.1.2.3 LineCode=bus5_bus4
Length=10 units=mi
New Line.Line4_6 Phases=3 Bus1=Bus4.1.2.3 Bus2=Bus6.1.2.3 LineCode=bus4_bus6
Length=10 units=mi
New Line.Line6_9 Phases=3 Bus1=Bus6.1.2.3 Bus2=Bus9.1.2.3 LineCode=bus6_bus9
Length=10 units=mi

Set Voltagebases=[230, 18, 16.5, 13.8]


Calcvoltagebases
calcv
Solve
Show Voltages LN Nodes
Show Y