지 반 조 사 보 고 서
2020. 11
제 출 문
2 0 2 0 년 1 1 월
토질 및 기초기술사
17112010087P 유 상 화
목 차
제 1 장 조사개요
1.1 조사목적 ······················································································································································· 6
제 2 장 조사내용
2.1 조사위치선정 ··············································································································································· 9
제 3 장 토질 및 암반의 분류
3.1 흙의 분류 ····················································································································································· 28
3.2 암반의 분류 ··············································································································································· 34
3.3 지형 및 지질 ··············································································································································· 36
제 4 장 조사결과
4.1 시추조사 위치 ··········································································································································· 38
제 6 장 기초에 대한 검토
6.1 기초형식의 일반사항 ······························································································································· 81
제 7 장 결 론
7. 결 론 ····················································································································································· 86
[ 부 록]
1. 시추조사 위치도
2. 지층 단면도
3. 시추 주상도
4. 현장시험
5. 실내실험
6. 하향식 탄성파 탐사
7. 사진첩
제1장 조 사 개 요
1.1 조사목적
1.2 조사위치
1.3 조사기간
1.4 조사항목
1.5 조사장비
춘천 후평동 729번지 주거복합 신축공사
제1장 조 사 개 요
1.1 조사목적
본 조사의 목적은“춘천 후평동 729번지 주거복합 신축공사” 지반조사 및 현장시험을 실시하
1.2 조사위치
• 강원 춘천시 후평동 729번지
현장위치
6
춘천 후평동 729번지 주거복합 신축공사
1.3 조사기간
▨ 현 장 조 사 및 시 험 : 2020. 10. 14. ˜
1.4 조사항목
조사의 목적을 수행하기 위하여 다음과 같은 내용의 지반조사를 실시하였다.
구 분 대 상 수 량 비 고
현장조사 시 추 조 사 신 축 부 지 4개소 NX 4공
기반암의
공내재하시험 BH-1 / BH-3 2회
변형특성 파악
1.5 조사장비
본 조사에 사용된 조사장비는 다음과 같다.
품 목 규 격 수 량 비 고
시 추 기 SUPER 4000MD 1대
지하수위측정기 50m 1식
기타부대장비 - 1식
7
제2장 조 사 내 용
2.1 조사위치선정
2.2 시추조사
2.3 표준관입시험
2.4 지하수위측정
2.5 현장시험
2.6 실내실험
2.7 하향식탄성파탐사
춘천 후평동 729번지 주거복합 신축공사
제2장 조 사 내 용
2.1 조사위치선정
조사위치선정은 “춘천 후평동 729번지 주거복합 신축공사” 대상부지에 대하여 배치도의 도상
2.2 시추조사
본 조사는 지층의 구성상태 및 기반암의 암종, 암질변화 등을 파악하기 위하여 지반조사 위치
료병에 넣어 보관하였다.
기반암층 구간에서는 Core 회수시 회수율을 높이고 정확한 암질상태를 파악하기 위해 Double
시추주상도에 기록한다.
9
춘천 후평동 729번지 주거복합 신축공사
성분을 파악하기 위하여 지층이 변화하는 경우 또는 동일지층의 경우라도 1.0m 간격으로 표준관
시료도 함께 채취하였다.
의 Split Spoon Sampler가 30cm 관입하는데 소요되는 타격횟수를 말하며 매 15cm씩, 총 45cm에
10
춘천 후평동 729번지 주거복합 신축공사
구 분 판정 및 추정사항
․상대밀도(Dr), 내부마찰각(Φ)
․기초지반의 탄성침하
사 질 토
․기초지반의 허용지지력
N치로 추정할 수 ․액상화 가능성 파악
있는 사항
․일축압축강도(qu), 비배수점착력(Cu)
점 성 토 ․기초지반의 허용지지력
․연․경 정도
지층이 매우 조밀하여 타격을 50회 이상 타격을 가하여도 30cm 관입이 불가능한 지층에서는 50
11
춘천 후평동 729번지 주거복합 신축공사
2.4 지하수위측정
지하수위 변화에 따른 수압 및 유효상재하중을 고려하기 위하여 각 시추공에서 지하수위를 측
정, 기록하였다.
2.5 현 장 시 험
2.5.1 투수시험
며 방법은 Casing을 삽입한 후 Casing 내부를 청소하고 Casing 끝부분에서 일정심도의 대수층을
다.
K : 투수계수(cm/sec)
∙ 본 조사지역에 분포하고 있는 지반의 투수성을 파악하기 위해
t1,t2 : (cm)
× Ln × Ln
H1,H2 경과시간(sec)
12
춘천 후평동 729번지 주거복합 신축공사
2.5.2 수압시험
가. 시험목적
•본 사업부지 구간에 분포하는 암반의 투수성에 관련된 수리지질학적 특성을 규명하기 위하여
시추공을 이용하여 실시.
나. 시험 및 분석방법
시험방법은 주입법의 일종인 Single Packer 방식으로 실시하였으며, 압력의 증감은 7단계
13
춘천 후평동 729번지 주거복합 신축공사
•Lugeon치 산정 •투수계수산정
Lu = 10
P×L
×Q K = 2.3 ×Q L
2πLH log r
위 식에서 위 식에서
Lu = Lugeon 치 K = 투수계수(cm/sec)
Q = 침투량(1/min) Q = 침투량(cm3/sec)
P = 주입압력(kg/cm2) L = 시험구간의 길이(cm)
L = 시험구간의 길이(m) H = 수두차(cm)
r = 케이싱반경(cm)
2.5.3 공내전단시험
(공내전단시험 상세 순서 및 흐름도)
14
춘천 후평동 729번지 주거복합 신축공사
2.5.4 공내재하시험
계수나 항복치를 구하여 공동주변의 느슨한 영역의 추정등의 목적으로 실시되는 경우도 있다.
(모 식 도)
(공내재하시험 PMT장비)
15
춘천 후평동 729번지 주거복합 신축공사
2.6 실 내 시 험
2.6.1 물성실험
물 성
시 험
밀도(비중) KS F 2308 함수비 KS F 2306
입도시험 및
물리시험용 KS F 2502
액성ㆍ소성한 시료 조제
입도시험 KS F 2302 KS F 2303
계
의 함수비라 한다.
나. 비중시험(KS F 2308)
16
춘천 후평동 729번지 주거복합 신축공사
고체상태로부터 반고체 상태로 변하는 순간의 함수비를 수축한계, 반고체 상태로부터 소성상태
■ 액성한계시험
서 액성상태로 변하는 순간의 함수비로 액상을 나타내는 최초의 함수비를 말한다. 이 방법은 KS
F2303에 규정되어 있다. 흙의 세립토는 함수비의 함량에 따라 4가지 상태로 존재하며 함수비의
함수비
수축한계 소성한계 액성한계 증 가
흙의부피
Vf
함수비(%)
한 주의를 요한다.
17
춘천 후평동 729번지 주거복합 신축공사
일 때의 함수비를 나타낸다.
■ 소성한계시험
와 반고체 상태의 한계를 나타낼때의 함수비를 말하며 시험방법은 KS F 2303에 규정되어 있다.
야 한다.
타낸다.
18
춘천 후평동 729번지 주거복합 신축공사
름을 한다.
남은 무게를 측정 한다.
비중계분석은 Stoke의 법칙을 이용하여 침강거리로서 토립자의 크기와 함유량을 구하는 방법으
의 온도가 같아지면 메스실린더를 꺼내어 실린더의 입구를 고무마개 등으로 막고 1분간 30회 정
각국마다 기준이 다르다. 모래에서 균등계수 6이상, 자갈에는 4이상이고, 곡률계수가 1∼3이면
입도가 좋다고 분류하는데 그것은 다양한 입경의 입자가 분포하므로 입자간의 Interlocking이 잘
되어 강도가 크고 작음을 의미한다. 또한, 10% 누가통과율을 말하는 유효입경( D 10 )으로 투수계
Cu D 60 Cg (D 30 ) 2
= D 10 = D 60×D 10
여기서, Cu : 균등계수
Cg : 곡률계수
19
춘천 후평동 729번지 주거복합 신축공사
그 목적이 있다.
(2) 탐사 위치
공 번 시추심도(m) 조사 구간(m) 비고
(3) 탐사 장비
〈하향식탄성파탐사 장비 및 제원〉
장비명 모델명/제원 장비사진
McSEIS SX(OYO) ‧MODEL-1125S(OYO)
Geophone ‧ 3-성분
2.7.2. 하향식탄성파탐사 원리
(1) 기초 이론
㉠ 정적 탄성상수
물체에 압축이나 인장 응력( σ )을 가하면 응력 방향으로의 변형률( ε σ )이 생기는데, 이 때의
20
춘천 후평동 729번지 주거복합 신축공사
E = σ
εσ
Rigidity modulus, G )라고 한다. 이들의 관계를 식으로 표현하면 다음과 같다.
G = τ
ετ
ΔP
K= ΔV
㉡ 동적 탄성상수
반면에 원지반 상태에서 P파 및 S파의 속도 관계로부터 구한 여러 탄성상수를 동적 탄성상
K d + 43 G d Ed (1- ν d )
VP = ρ
= ρ (1-2 ν d )(1+ν d ) ,
21
춘천 후평동 729번지 주거복합 신축공사
VS = Gd = Ed 1
ρ ρ 2 (1+ ν d )
VP = 1- ν d 1-0.5 V( )
VP 2
1- ( V )
= S
,
VS 1 -ν νd
V P
2
2 d S
만족한다.
Ed ,
G d = 2 (1+ Ed
K d = 3 (1-2
ν d) ν d)
K d = 2 ρ3 V(1-2
S (1+ ν d )
2
Gd = ρ VS2 , Ed = 2 ρ V S 2 (1+ ν d ) ,
ν d)
(2) 하향식탄성파탐사 탐사 원리
wave, Compression wave, Primary wave)라 한다. 반면 S파는 파의 진행방향에 대하여 입자의
운동이 수직이므로 횡파(Transverse wave, Cross wave, Shear wave, Secondary wave)라고
한다. P파는 Primary wave로서 속도가 가장 빠르기 때문에 탄성파 수진기에 가장 먼저 도달하
22
춘천 후평동 729번지 주거복합 신축공사
성분을 지표에 설치한 진원의 방향과 일치하게 한다. 증폭, 기록기는 측정심도 내에 수진기의
수회의 탄성파를 Stacking하여 S/N비를 높이며 수신된 탄성파의 해독이 쉽도록 측정시간의
Scale을 넓혀 시간의 진행에 따른 입자의 운동을 파악하기 쉽도록 한다. 필요시 각종 Filter를
달을 확인한다.
한다.
(3) 탐사 방법
23
춘천 후평동 729번지 주거복합 신축공사
기 때문에 여러번 타격한 신호를 중첩하여 신호의 세기를 강화할 필요가 있다.
한편, S파 발생원은 P파도 발생시키게 되나 그 신호의 크기가 비교적 작고, 측정 심도가 깊어질
24
춘천 후평동 729번지 주거복합 신축공사
25
제3장 토질 및 암반의 분류
3.1 흙의 분류
3.2 암반의 분류
3.3 지형 및 지질
춘천 후평동 729번지 주거복합 신축공사
제3장 토질 및 암반의 분류
3.1 흙의 분류
토질에 대한 분류기준은 통일분류법(U.S.C.S)에 따랐으며, 그 기술내용은 토질의 상태 즉, 점
다.
사용하였다.
27
춘천 후평동 729번지 주거복합 신축공사
주 요 구 분 문 대표적인 흙 분 류 기 준
자
D60
세립분이 입도 분포가 좋은 Cu > 4 Cu =
자갈 또는 자갈과 D10
약간 GW 모래의 혼합토 세립분의 1 < Cc < 3
또는 세립분이 약간 또는 (D30)2
없음 함유율에 Cc =
거의 의한 분류 D10 x D60
없는 입도 분포가 나쁜
자갈(Gravel) 자갈 GP 자갈 또 는 자갈과 GW의 조건이 만족되지 않을때
#4 번체에 모래의 혼합토 #200 번체
세립분이 약간 또는 Atterberg 한계가
(4.76mm) 없음 통과율이
5 % 이하 A선 밑 소성지수 소성지수가
50%이상 실트질의 자갈 또는 4 이하
남음 GM 자갈, 모래, 점토의 인 경우 4-7 이면서
세립분을 혼합토 GW, GP, Atterberg 한계
조립토 : 함유한 SW, SP Atterberg 한계가 가 A선 위에
자갈 점토질의 자갈 또는 A선 위 소성지수
#200번체 7 이상 존재할 때는 2
GC 자갈․모래․점토의
에 (0.074 혼합토 중 문자로 표시
#200 번체
mm)
통과율이
50 %이상 세립분이 입도분포가 좋은 모래 12% 이상
또는 자갈질의 모래 Cu > 6
남음 약간 SW 인 경우
세립분은 약간 또는 1 < Cc < 3
또는 없음 GM, GC,
거의 SM, SC
모래(Sand) 없는 입도분포가 나쁜 모래
#4 번체에 모래 또는 자갈질의 모래
SP 세립분은 약간 또는 #200 번체 SW 의 조건이 만족되지 않을때
(4.76mm) 없음
통과율이
50%이상
5-12 %
통과 인 경우 Atterberg 한계가 소성지수가
실트질의 모래
세립분을 SM 2 중 문 A 선 밑 소성지수 4-7 이면서
모래․점토의 혼합토 4 이하 Atterberg 한계
함유한 자로 표시
Atterberg 한계가 가 A선 위에 존
모래 점토질의 모래
SC 모래․점토의 혼합토 A 선 위 소성지수 재할 때는 2 중
7 이상 문자로 표시
무기질의 실트
매우가는 모래, 암분, 소성도(Plasticity Chart)는 조립토에
ML 소성 이 작은 함유된 세립분과 세립토를 분류하기 위해
실트질의 세사나 사용된다.
점토질의세사 소성도의 빗금친 곳은 2 중 표기해야 하는
액성한계 50% 이하인 소성이 중간치 이하인 부분 이다.
무기질점토, 자갈질
실트나 점토 점토,
세립토 : CL
모래질 점토,
#200번체 실트질 점토,
에(0.074 소성이 작은 점토 60
mm) 소성이 작은 실트 및 50
OL 실트질 점토 CH
50 %이상 40
무기질의 실트,
Plasticity Index
통과
운모질 또는 규소의 30
L-2
0)
MH 세사 및 실트질 흙, CL
P I=
0 .7
3(L
e
20 Lin
0 10 20 30 40 50 60 70 80
28
춘천 후평동 729번지 주거복합 신축공사
3.2 암반의 분류
암석코아에 대한 기술내용은 색, 균열(Discontinuity)의 간격, 풍화상태, 강도, 암석명 등이
라 기재하였다.
3.2.1 색(Color)에 의한 분류
암석의 기본색(황색, 갈색, 회색, 청색 또는 녹색)에 담(연한)과 암(진한)의 명암 및 혼색에
대한 서술용어를 사용하였다.
분류기호 용 어 서 술
Fresh
D - 1 풍화된 흔적이 없으며 지질조사용 해머로 타격시 금속음을 내며 울린다.
(신선한 암반)
Slightly
D - 2 Weathered 갈라진 틈의 내부에 다소 풍화변색된 상태를 제외하곤 신선(F)과 비슷하다.
(약간 풍화)
Highly
대부분 광물이 풍화되어 있으며 암시료는 손으로 힘들여 부암반에 핵석(core
D - 4 Weathered
stone)이 있을수 있다. 조직은 뚜렷치 않지만 구조는 남아 있다.
(많이 풍화)
Completely
광물은 풍화되어 흙으로 변했지만 암의 조직과 구조는 남아있다. 시료는 쉽게
D - 5 Weathered
부서지거나 관입된다.
(완전 풍화)
29
춘천 후평동 729번지 주거복합 신축공사
분 류 기 호 용 어 Joint 간격 Joint 상태
약간 균열
F-2 20 ~ 100cm Wide
(Slightly Fractured)
보통 균열
F-3 10 ~ 20cm Moderately Close
(Moderately Fractured)
심한 균열
F-4 5 ~ 10cm Close
(Fractured)
매우 심한 균열
F-5 5 cm 이 하 Very Close
(Highly Fractured)
3.2.4 강도에 의한 분류
분류기호 용 어 암 반 상 태 일축압축강도(㎏/㎠)
보통강함
Hammer로 한번 타격하여 쉽게
S-3 Moderately Strong 250~500
모서리가 부서짐.
(Moderately Hard)
연함
S-4 Weak Hammer로 눌러서 부서짐. 50~250
(Soft)
매우 약함
S-5 Very Weak 손가락으로 눌러 부서짐. 10~50
(Very Soft)
30
춘천 후평동 729번지 주거복합 신축공사
3.2.5 암반(암석)의 분류
암반의 분류기준은 일반적으로 지질학적 분류, 품셈에 의한 분류, 공학적 분류가 있으며, 내용
을 요약하면 다음 표와 같다.
<표 3.2-4> 암 반 분 류 기 준
구 분 분 류 방 법 개 요
지질학적 분
‧성인에 따른 분류 ‧암석의 생성조건에 따라 분류
류
(1) 지질학적 분류
지질학적 분류는 지질연대에 의한 분류와 성인에 의한 분류로 나누어진다. 지질연대에
따른 분류는 지층의 층사와 암석의 경년을 기준으로한 연대에 따라 대(代, Era), 기(紀,
31
춘천 후평동 729번지 주거복합 신축공사
(2) 품셈에 의한 분류
㉠ 지반조사시 암반분류
등 3등급으로 분류한다.
㉡ 탄성파속도에 의한 암석의 분류
구 분 A 그룹 B 그룹
32
춘천 후평동 729번지 주거복합 신축공사
내압강도
A 1.2~1.9 2.7~3.9 700~1,000 시 편 : 5cm입방체
연 암
B 1.8~2.8 3.0~4.3 200~500 노 건 조 : 24시간
수중침윤 : 2일
내압시험
A 1.9~2.9 3.7~4.7 1,000~1,300 시험방향(가압방향) : z축(결면에
보통암 수직, 탄성파속도가 느린방향)
B 2.8~4.1 4.3~5.7 500~800
암편 탄성파 속도
1. 시편 : 두께 15~20cm 상하면이
평행선
A 2.9~4.2 4.7~5.8 1,300~1,600 2. 측정방향 : x축(탄성파속도가 가장
경 암
B 4.1 이상 5.7 이상 800 이상 빠른 방향), (결면에 평행)
A
극경암 4.2 이상 5.8 이상 1,600 이상
B
㉢ 토공작업성에 의한 분류기준
A
700m/sec 미만 700~1,200m/sec 미만 1,200m/sec 이상
그룹
탄성파
속 도
B
1,000m/sec 미만 1,000~1,800m/sec 미만 1,800m/sec 이상
그룹
33
춘천 후평동 729번지 주거복합 신축공사
토공작업의 난이도 결정
사질셰일, 역암,경사암,규질셰일,
중생대 퇴적암 각 암석의 셰일, 석영맥,쳐트,
실트스톤, 화강암,반암,규장암,
화성암 풍화암 탄질셰일 혼펠스
장석질사암 화강편마암,쳐트,혼펠스
셰일, 사암,역암,규질셰일,
실트스톤, 슬레이트, 규질석회암,섬록암,
고생대 및 탄질셰일, 백운암, 섬장암,반려암,석영반암
선캠브리아기 각 암석의 석회암, 흑운모편암, 화강반암,페그마타이트반 경사암,규암,
퇴적암, 화성암 풍화암 대리석, 흑연편암, 암, 화강편마암, 석영맥
및 변성암 점판암, 녹리석편암, 운모편마암, 각섬편마암,
천매암, 견운모편암 호상편마암, 석영편암,
사문암 각섬편암, 운모편암
일축압축강도 1,200이상
125 이하 125~400 400~800 800~1,200
(kgf/cm²) 경우에는 1,800
34
춘천 후평동 729번지 주거복합 신축공사
3.3 지형 및 지질
3.3 지질 및 지반현황
3.3.1 지형분석
과업위치
[ 사업구간 지형 ]
35
춘천 후평동 729번지 주거복합 신축공사
3.3.2 지질분석
- Jkcgr 흑운모화강암
Qa
Jkcgr
과업위치
Jbgr
Qa
Jkcgr
[ 지질도 ]
36
제4장 조 사 결 과
4.1 시추조사 위치
4.2 시추조사 성과
4.3 지하수위측정 결과
4.4 시추조사 결과
4.5 현장시험 결과
4.6 실내시험 결과
4.7 하향식탄성파탐사 결과
춘천 후평동 729번지 주거복합 신축공사
제4장 조 사 결 과
4.1 시추조사 위치
본 조사지역은 “강원 춘천시 후평동 729번지”에 위치하고 있다.
4.2 시추조사 성과
본 조사부지에서 실시한 4개소의 시추조사 결과를 정리하면 다음과 같다.
4.2.1. 시추조사 결과
심 도 층 후
공 번 지 층 구성상태 N 치 비 고
(m) (m)
매 립 층 0.0 ~ 2.0 2.0 실트섞인 모래 6/30
퇴 적 층 2.0 ~ 14.4 12.4 실트질 모래(자갈) 8/30 ~ 40/30
BH-1 풍 화 토 14.4 ~ 15.0 0.6 실트섞인 모래 50/8
굴진시 세편상 암편으로
풍 화 암 15.0 ~ 30.0 15.0 50/8 ~ 50/1
분해
매 립 층 0.0 ~ 1.0 1.0 실트섞인 모래 7/30
퇴 적 층 1.0 ~ 14.5 13.5 실트질 모래(자갈) 7/30 ~50/23
BH-2 풍 화 토 14.5 ~ 15.0 0.5 실트섞인 모래 50/14
굴진시 세편상 암편으로
풍 화 암 15.0 ~ 30.0 15.0 50/7 ~ 50/1
분해
매 립 층 0.0 ~ 0.8 0.8 실트섞인 모래 -
퇴 적 층 0.8 ~ 13.5 12.7 실트질 모래(자갈) 7/30 ~48/30
BH-3 풍 화 토 13.5 ~ 14.0 0.5 실트섞인 모래 -
굴진시 세편상 암편으로
풍 화 암 14.0 ~ 30.0 16.0 50/4 ~ 50/1
분해
매 립 층 0.0 ~ 0.9 0.9 실트섞인 모래 -
퇴 적 층 0.9 ~ 14.0 13.1 실트질 모래(자갈) 7/30 ~ 49/30
BH-4
굴진시 세편상 암편으로
풍 화 암 14.0 ~ 30.0 16.0 50/3 ~ 50/1
분해
38
춘천 후평동 729번지 주거복합 신축공사
4.2.2. 지층개요
지 층 지 층 현 황
39
춘천 후평동 729번지 주거복합 신축공사
지하수위 (m)
공 번
24시간 48시간 72시간
4.4 시추조사 결과
4.4.1. 조사결과
조사부지의 지층상태 파악을 위해 실시된 4개소의 시추조사 결과를 요약하면 다음과 같다.
지 층 층 후(m)
계
공 번
(m)
매 립 층 퇴적층 풍 화 토 풍 화 암
40
춘천 후평동 729번지 주거복합 신축공사
4.5 현장시험 결과
4.5.1 투수시험 결과
41
춘천 후평동 729번지 주거복합 신축공사
42
춘천 후평동 729번지 주거복합 신축공사
43
춘천 후평동 729번지 주거복합 신축공사
44
춘천 후평동 729번지 주거복합 신축공사
4.5.2 공내전단시험 결과
45
춘천 후평동 729번지 주거복합 신축공사
46
춘천 후평동 729번지 주거복합 신축공사
47
춘천 후평동 729번지 주거복합 신축공사
48
춘천 후평동 729번지 주거복합 신축공사
4.5.3 공내재하시험 결과
49
춘천 후평동 729번지 주거복합 신축공사
50
춘천 후평동 729번지 주거복합 신축공사
51
춘천 후평동 729번지 주거복합 신축공사
4.6 실내실험 결과
4.6.1 물성시험 결과
52
춘천 후평동 729번지 주거복합 신축공사
(1) BH-1
53
춘천 후평동 729번지 주거복합 신축공사
(2) BH-2
54
춘천 후평동 729번지 주거복합 신축공사
(3) BH-3
55
춘천 후평동 729번지 주거복합 신축공사
(4) BH-4
56
춘천 후평동 729번지 주거복합 신축공사
지 층 적용 단위중량 (t/m3) 비고
매 립 층 1.8
퇴 적 층 1.8
풍 화 토 1.9
풍 화 암 2.1
가. BH-1
심도 Vp Vs 동적 Gd Ed Kd
지층 (MPa) (MPa) (MPa)
(m) (m/sec) (m/sec) 포아송비
0.0~1.0 450 181 0.403 60 169 292
매립층
1.0~2.0 483 195 0.403 70 196 335
2.0~3.0 490 198 0.402 72 202 345
3.0~4.0 442 178 0.403 58 163 281
4.0~5.0 423 170 0.404 53 149 258
5.0~6.0 379 152 0.404 42 119 207
6.0~7.0 389 156 0.404 45 126 218
7.0~8.0 459 185 0.403 63 176 303
퇴적층
8.0~9.0 512 207 0.402 79 221 377
9.0~10.0 707 287 0.401 151 424 716
10.0~11.0 816 334 0.399 205 573 950
11.0~12.0 891 368 0.397 249 695 1,126
12.0~13.0 813 337 0.396 209 583 936
13.0~14.0 783 326 0.395 195 545 866
풍화토 14.0~15.0 981 410 0.394 326 909 1,431
15.0~16.0 1,018 431 0.391 398 1,107 1,690
풍화암
16.0~17.0 1,025 438 0.388 411 1,141 1,703
57
춘천 후평동 729번지 주거복합 신축공사
심도 Vp Vs 동적 Gd Ed Kd
지층 (MPa) (MPa) (MPa)
(m) (m/sec) (m/sec) 포아송비
17.0~18.0 1,047 449 0.387 432 1,199 1,773
18.0~19.0 1,061 457 0.386 448 1,241 1,816
19.0~20.0 1,082 468 0.385 469 1,300 1,883
20.0~21.0 1,128 490 0.384 515 1,424 2,041
21.0~22.0 1,150 502 0.382 540 1,493 2,114
22.0~23.0 1,207 529 0.381 600 1,656 2,322
풍화암 23.0~24.0 1,247 549 0.380 646 1,782 2,471
24.0~25.0 1,330 588 0.379 741 2,043 2,803
25.0~26.0 1,366 607 0.377 790 2,174 2,946
26.0~27.0 1,421 634 0.376 861 2,370 3,178
27.0~28.0 1,471 659 0.374 931 2,558 3,396
28.0~29.0 1,529 688 0.373 1,014 2,785 3,657
29.0~30.0 1,581 718 0.370 1,105 3,027 3,883
가. BH-1
58
춘천 후평동 729번지 주거복합 신축공사
가. 지반의 분류
59
춘천 후평동 729번지 주거복합 신축공사
(전단파속도에 의한 지반분류)
가. 지반의 분류
반을 아래 표와 같이 S1, S2, S3, S4, S5, S6의 6종류로 분류한다. 다만, 기반암은 전단파속도가
60
춘천 후평동 729번지 주거복합 신축공사
평균 지반 특성
지반
지반종류의 호칭 기반암 깊이, H 토층 평균 전단파속도, Vs,soil
분류
(m) (m/sec)
S1 암반 지반 1 미만 -
S2 얕고 단단한 지반 260 이상
1~20 이하
S3 얕고 연약한 지반 260 미만
S4 깊고 단단한 지반 180 이상
20 초과
S5 깊고 연약한 지반 180 미만
(전단파속도에 의한 지반분류)
나. 평균지반속도 및 지반분류
지반등급산정
공번 지반분류 지반분류의 호칭
전단파속도(m/sec)
및 지하 지형이 지반운동에 미치는 영향을 고려하기 위하여 원칙적으로 지반을 다음과 같이 S1,
61
춘천 후평동 729번지 주거복합 신축공사
제5장 지반특성 분석
춘천 후평동 729번지 주거복합 신축공사
제5장 지반특성 분석
5.1 토질 특성
본 조사지역 최상부에서부터 매립층, 퇴적층, 풍화토, 풍화암 순으로 분포하고 있다.
는 것이 일반적이다.
63
춘천 후평동 729번지 주거복합 신축공사
제 안 자 관 계 식 비 고
Φ= √12N+25 - 토립자가 모나고 입도분포가 양호
Φ= √12N+20 - 토립자가 모나고 입도분포가 불량
DUNHAM
Φ= √12N+20 - 토립자가 둥글고 입도분포가 양호
Φ= √12N+15 - 토립자가 둥글고 입도분포가 불량
MEYERHOF Φ= 1/4N+32.5 10 ≤ N ≤ 50
PECK Φ= 0.3N+27
대호 Φ= √20N+15
건설성 Φ= √15N+15 일 본
64
춘천 후평동 729번지 주거복합 신축공사
Φ, 도
입자의 크기 다져진 상태 둥근입자 모난 입자
입도분포 균등 입도분포 양호
대단히 느슨 28~30 32~34
중간 모래 중간 정도 촘촘 32~34 36~40
대단히 촘촘 35~38 44~46
65%G-35%S 느슨 - 39
모래(S)
65%G-35%S 중간 정도 촘촘 37 41
및
80%G-20%S 촘촘 - 45
자갈(G)
80%G-20%S 느슨 34 -
암 편 40~55
65
춘천 후평동 729번지 주거복합 신축공사
r Void
+ Strength++
Meterial Compactness DR, % N* dry, ratio
Φ
g/㎤ e
* N is blows per foot of penetration in the SPT. Adjustments for gradation are after
Burmister(1982) See Table 6.4 for general relationships of DR VS. N.
+
Denity given is for G= 2.68(quartz grains).
++
Friction angle Φdepends on mineral type normal stree, and grain angularity as well as
DR and gradation <Hunt, Roy E. "Geotechnical engineering analysis and evaluation" 1986.>
**From Hunt(1984). Reprinted with permission of McGraw-Hill Book Company
66
춘천 후평동 729번지 주거복합 신축공사
단위체적 내부 점 착 력
종 류 재료의 상태 중 량 마찰각 C 분류기호
(t/㎥) Ø(도) (t/㎡)
자갈 및
다 진 것 2.0 40 0 GW, GP
가갈섞인 모래
입도가 좋은것 2.0 35 0
흙 모래 다 진 것 SW, SP
입도가 나쁜것 1.9 30 0
쌓
사질토 다 진 것 1.9 25 3 이하 SM, SC
기
ML, CL,
점성토 다 진 것 1.8 15 5 이하
MH, CH
밀실한 것, 입도가 좋은것 2.0 40 0
자갈 GW, GP
밀실하지 않은 것, 입도가 나쁜것 1.8 35 0
밀실한것 2.1 40 0
자갈섞인모래 GW, GP
말실하지않은것 1.9 35 0
밀실한 것, 입도가 좋은것 2.0 35 0
모래 SW, SP
밀실하지 않은 것, 입도가 나쁜것 1.8 30 0
밀실한것 1.9 30 3 이하
사질토 SM, SC
자 말실하지않은것 1.7 25 0
연 굳은것(손가락으로 강하게 눌러 조
1.8 25 5 이하
지 금 들어감)
반 점성토 약간 무른것(손가락 중간정도의 힘 ML, CL
1.7 20 3 이하
으로 들어감)
무른것(손가락이 쉽게 들어감) 1.7 20 1.5 이하
굳은것(손가락으로 강하게 눌러 조
1.7 20 5 이하
점토 금 들어감)
CH,
및 약간 무른것(손가락 중간정도의 힘
1.6 15 3 이하 MH, ML
실트 으로 들어감)
무른것(손가락이 쉽게 들어감) 1.4 10 1.5 이하
1) 지하수위 이하에 있는 흙으 단위체적중량은 각각의 값에서 1.0을 뺀 값으로 한다.
2) 단위체적중량의 값을 결정하는 경우 다음 사항에 주의한다.
비
(가)터널 버럭이나 암괴등은 입경이나 간극에 따라 다르기 때문에 과거의 실적이나
현장실험에 의해 결정한다.
고
(나)자갈혼입 사질토나 자갈혼입 점성토는 자갈 혼합비율 및 상태에 따라 적절히 정한다.
3) 내부마찰각 및 점착력의 값은 압밀 비배수 전당강도에 의한 개략적인 값이다.
67
춘천 후평동 729번지 주거복합 신축공사
제6장 기초에 대한 검토
춘천 후평동 729번지 주거복합 신축공사
제6장 기초에 대한 검토
말뚝기초로 취급된다.
foundation)라고도 한다.
로 구분된다.
69
춘천 후평동 729번지 주거복합 신축공사
1) 기초의 형식
얕은기초는 그 형식과 기능에 따라 Footing기초와 전면기초 (Mat foundation)로 구분
한다. Footing기초는 상부하중을 넓게 분포시키기 위하여 밑면을 확대시킨 확대기초
독립기초
복합기초
확대기초
캔틸레버기초
연속기초
얕은기초
부력기초
전면기초 전면기초
이중슬레브기초
2) 얕은기초의 허용 지지력
일반적으로 기초의 지지력을 계산하기 위해서는 지반의 특성을 정확히 파악하여야 한다.
70
춘천 후평동 729번지 주거복합 신축공사
① 기준지지력표 이용
② 표준관입시험 결과 이용
③ 지지력 이론에 의한 계산
다.
ㆍ토사에서의 지지력
1) Terzaghi의 극한지지력 공식
B : 기초의 폭(m)
Df : 기초의 근입깊이(m)
α, γ : 기초의 형상 계수
e2(3π/4 - Φ/2)tanΦ
71
춘천 후평동 729번지 주거복합 신축공사
Kp
Nr = 1/2 [ - 1 ]tanΦ .......................... <식 6.1b>
cos2Φ
e2(3π/4 - Φ/2)tanΦ
<표 6.1>αㆍβ 값
기초면의 형상 연 속 성 정 사 각 형 원 형 직 사 각 형
2) Meyerhof의 지지력 공식
로 쓸수 있다.
여기서,
72
춘천 후평동 729번지 주거복합 신축공사
Sc Sr Sq : 형상계수
dc dr dq : 깊이계수
ic ir iq : 경사계수
구할 수 있다.
① 형상계수
Sr = 1.0 (Φ = 0°)
② 깊이계수
dr = dq = 1.0 (Φ = 0°)
③ 경사계수
73
춘천 후평동 729번지 주거복합 신축공사
Terzaghi Meryerhof
Φ
Nc Nr Nq Nc Nr Nq
력은 다음 <표6.3>와 같다.
N치 2 4 6 8 10 12 14 16 18 20 22 24 26
점토 2.7 5.4 8.1 10.8 13.5 16.2 19.0 21.6 24.3 27.0 29.7 32.5 35.2
모래
2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5 25.0 27.5 30.0 32.5
및 풍화대
N치 28 30 32 34 36 38 40 42 44 46 48 50
점 토 38.0 41.0 - - - - - - - - - -
모래
35.0 37.5 40.0 42.5 45.0 46.2 50.0 52.5 55.0 57.5 60.0 62.5
및 풍화대
74
춘천 후평동 729번지 주거복합 신축공사
허용지지력(ton/㎡)
지지층 현장 연경도 상태
범위 추천값
괴상의 결정질 화강암,변성암:화강암,
경질의 신선한 암 640~1070 860
섬록암,현무암,완전히 고결된 역암
유의사항 :
하여 결정한다.
75
춘천 후평동 729번지 주거복합 신축공사
조건에 지배된다.
② Sowers(1962)의 최대 허용침하량<표6.6>
최대부등침하(inch) 최대침하(inch)
기 준 각 변 위
점 토 모 래 점 토 모 래
( )는 추천 최대값임.
76
춘천 후평동 729번지 주거복합 신축공사
탑, 굴뚝 0.004 S
전 도 물품적재 0.010 S
크레인 레일 0.003 S
각 변 위 (δ/ L) 1/300
점 토 45 ㎜
최대부등침하
사 질 토 30 ㎜
점 토 80 ㎜
총 침 하 량
사 질 토 40 ㎜
77
춘천 후평동 729번지 주거복합 신축공사
저 자 구 조 형 식 허 용 침 하 량(㎝) 각 변 형 (rad)
철근콘크리트 구조 5.0 -
테르자기
(Terzaghi,1935)
연 와 구 조 - 1/280
테르자기 와 펙
철근콘크리트 구조 5.0 1/320
(Terzaghi &Peck,1948)
체보타리오프
연 와 구 조 5.0 ~ 7.5 -
(Tschebotarioff,1951)
와드 와 그린
연 와 구 조 - 1/480
(Ward & Green,1952)
철근콘크리트 구조 - 1/300
메이어호프
철근콘크리트 구조 - 1/1000
(Weyerhof,1953)
연 와 구 조 - 1/600
철근콘크리트 구조
오자끼(大崎 ,1956) - 1/600 ~1/1000
부 럭 구 조
78
춘천 후평동 729번지 주거복합 신축공사
1) 말뚝기초의 분류
말뚝기초의 분류로서는 지지형식에 의한 것, 재질에 의한 것, 공법에 의한 것, 형상에
의한 것 및 이용 목적에 의한 것이 고려 될 수 있으며 이중 시공법에 의한 분류, 연
직력의 지지기구에 의한 분류는<그림6.1>과 같다.
<그림6.1> 말뚝기초의 분류
79
춘천 후평동 729번지 주거복합 신축공사
2) 말뚝 공법의 선정기준
라마다 틀리다.
80
춘천 후평동 729번지 주거복합 신축공사
6.1.3 기초에 대한 제언
일반적으로 구조물의 기초 형식은 지지기반의 토층 상태, 구조물의 하중조건, 기초의 형
식, 기초의 근입 깊이, 현장여건, 공사비, 공기 등을 종합 검토하여 가장 합리적이며 안
전하고, 경제적인 기초를 선택하는 것이 바람직하다. 또한, 기초형식은 지층의 분포상태,
지하층의 규모 및 구조물의 하중을 감안하여 신중히 결정하여야 한다.
또한, 기초 공사 시행전 깊은기초의 경우 정재하 동재하시험을 시방기준에 의거하여 시
야 한다.
81
춘천 후평동 729번지 주거복합 신축공사
제7장 결 론
춘천 후평동 729번지 주거복합 신축공사
제7장 결 론
하면 아래의 표와 같다.
심 도 층 후
공 번 지 층 구성상태 N 치 비 고
(m) (m)
매 립 층 0.0 ~ 2.0 2.0 실트섞인 모래 6/30
퇴 적 층 2.0 ~ 14.4 12.4 실트질 모래(자갈) 8/30 ~ 40/30
BH-1 풍 화 토 14.4 ~ 15.0 0.6 실트섞인 모래 50/8
굴진시 세편상 암편으로
풍 화 암 15.0 ~ 30.0 15.0 50/8 ~ 50/1
분해
매 립 층 0.0 ~ 1.0 1.0 실트섞인 모래 7/30
퇴 적 층 1.0 ~ 14.5 13.5 실트질 모래(자갈) 7/30 ~50/23
BH-2 풍 화 토 14.5 ~ 15.0 0.5 실트섞인 모래 50/14
굴진시 세편상 암편으로
풍 화 암 15.0 ~ 30.0 15.0 50/7 ~ 50/1
분해
매 립 층 0.0 ~ 0.8 0.8 실트섞인 모래 -
퇴 적 층 0.8 ~ 13.5 12.7 실트질 모래(자갈) 7/30 ~48/30
BH-3 풍 화 토 13.5 ~ 14.0 0.5 실트섞인 모래 -
굴진시 세편상 암편으로
풍 화 암 14.0 ~ 30.0 16.0 50/4 ~ 50/1
분해
매 립 층 0.0 ~ 0.9 0.9 실트섞인 모래 -
퇴 적 층 0.9 ~ 14.0 13.1 실트질 모래(자갈) 7/30 ~ 49/30
BH-4
굴진시 세편상 암편으로
풍 화 암 14.0 ~ 30.0 16.0 50/3 ~ 50/1
분해
83
춘천 후평동 729번지 주거복합 신축공사
지하수위 (m)
공 번
24시간 48시간 72시간
BH-1 4.0 5.8 7.0
BH-2 3.8 5.1 6.7
BH-3 4.0 5.9 6.8
BH-4 3.6 5.2 6.4
4) 현장시험(투수시험) 결과
시험심도 투수계수
공번 지층
(GL.-m) (cm/s)
5) 현장시험(공내전단시험 결과)
내부마찰각 접 착 력
공 번 심 도(M) 지 층(N치) R Square(%)
(Degree) (Kpa)
84
춘천 후평동 729번지 주거복합 신축공사
6) 현장시험(공내재하시험 결과)
변 형 계 수 탄 성 계 수
공 번 심 도(M) 지 층(N치)
(Mpa) (Mpa)
7) 실내시험(물성시험) 결과
85
춘천 후평동 729번지 주거복합 신축공사
8) 탄성파 탐사 결과
지반등급산정
공번 지반분류 지반분류의 호칭
전단파속도(m/sec)
86
부 록
1. 시 추 조 사 위 치 도
2. 지 층 단 면 도
3. 시 추 주 상 도
4. 현장시험
5. 실내시험
6. 탄성파탐사시험
7. 사진첩
55
1. 시 추 조 사 위 치 도
55
2. 지 층 단 면 도
55
FREE SCALE
BH- 1 BH- 4
EL.0.0 EL.0.0
0 0.9
6/ 30 7/ 30
2.0 8/ 30 8/ 30
9/ 30 7/ 30
6/ 30 9/ 30
-5 7/ 30 9/ 30
3/ 30 10/ 30
3/ 30 10/ 30
7/ 30 9/ 30
8/ 30 11/ 30
-10 48/ 30 13/ 30
50/ 22 10/ 30
50/ 25 41/ 30
42/ 30 49/ 30
14.4 40/ 30 14.0 50/ 3
-15 15.0 50/ 8 50/ 3
50/ 4 50/ 4
50/ 3 50/ 3
50/ 2 50/ 2
50/ 2 50/ 2
-20 50/ 2 50/ 2
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
-25 50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
-30 30.0 50/ 1 30.0 50/ 1
매립층 풍화암
범례
퇴적층 풍화토
FREE SCALE
BH- 2 BH- 3
EL.0.0 EL.0.0
0 0.8
1.0 7/ 30 7/ 30
7/ 30 8/ 30
10/ 30 7/ 30
7/ 30 9/ 30
-5 8/ 30 8/ 30
4/ 30 9/ 30
7/ 30 7/ 30
8/ 30 7/ 30
9/ 30 9/ 30
-10 10/ 30 10/ 30
45/ 30 12/ 30
50/ 25 11/ 30
50/ 30 13.5 48/ 30
14.5 50/ 23 14.0 50/ 4
-15 15.0 50/ 14 50/ 3
50/ 7 50/ 4
50/ 4 50/ 3
50/ 4 50/ 2
50/ 3 50/ 2
-20 50/ 2 50/ 2
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
-25 50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
50/ 1 50/ 1
-30 30.0 50/ 1 30.0 50/ 1
매립층 풍화암
범례
퇴적층 풍화토
3. 시 추 주 상 도
55
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 1
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 7.0 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
- 매립층-
S- 7 7.0 3/ 30
S- 8 8.0 7/ 30
퇴적층
S- 9 9.0 8/ 30
10 S- 10 10.0 48/ 30
S- 11 11.0 50/ 22
S- 12 12.0 50/ 25
S- 13 13.0 42/ 30
S- 14 14.0 40/ 30
- 14.4 14.4 12.4
- 15.0 15.0 0.6 풍화토 - 풍화토-
15 S- 15 15.0 50/ 8
심도: 14.4m ~ 15.0m
실트섞인 모래
매우 조밀(Very Dense) S- 16 16.0 50/ 4
상대밀도
습윤상태
황갈색 S- 17 17.0 50/ 3
- 풍화암-
심도 : 15.0m ~ 30.0m S- 18 18.0 50/ 2
굴진시 세편상 암편으로 분해
매우 조밀(Very Dense)
상대밀도 S- 19 19.0 50/ 2
습윤상태
황갈색
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 1
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 7.0 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
S- 20 20.0 50/ 2
S- 21 21.0 50/ 1
S- 22 22.0 50/ 1
S- 23 23.0 50/ 1
S- 24 24.0 50/ 1
S- 26 26.0 50/ 1
S- 27 27.0 50/ 1
S- 28 28.0 50/ 1
S- 29 29.0 50/ 1
35
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 2
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 6.7 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
- 매립층-
매립층
- 1.0 1.0 1.0 심도 : 0.0m ~ 1.0m S- 1 1.0 7/ 30
실트섞인 모래
느슨(Loose) 상대밀도
상부0.0m ~ 0.15m 아스팔트
습윤상태 S- 2 2.0 7/ 30
갈색
- 퇴적층- S- 3 3.0 10/ 30
심도 : 1.0m ~ 14.5m
실트섞인 모래 S- 4 4.0 7/ 30
느슨(Loose)~ 매우 조밀(Very Dense)
상대밀도
5 습윤상태 S- 5 5.0 8/ 30
심도10.5m 하부 자갈혼재
암회색~ 암갈색
S- 6 6.0 4/ 30
S- 7 7.0 7/ 30
퇴적층
S- 8 8.0 8/ 30
S- 9 9.0 9/ 30
10 S- 10 10.0 10/ 30
S- 11 11.0 45/ 30
S- 12 12.0 50/ 25
S- 13 13.0 50/ 30
S- 14 14.0 50/ 23
- 14.5 14.5 13.5
- 15.0 15.0 0.5 풍화토 - 풍화토-
15 S- 15 15.0 50/ 14
심도: 14.5m ~ 15.0m
실트섞인 모래
매우 조밀(Very Dense) S- 16 16.0 50/ 7
상대밀도
습윤상태
황갈색 S- 17 17.0 50/ 4
- 풍화암-
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 6.7 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
S- 20 20.0 50/ 2
S- 21 21.0 50/ 1
S- 22 22.0 50/ 1
S- 23 23.0 50/ 1
S- 24 24.0 50/ 1
S- 26 26.0 50/ 1
S- 27 27.0 50/ 1
S- 28 28.0 50/ 1
S- 29 29.0 50/ 1
35
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 3
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 6.8 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
매립층 - 매립층-
- 0.8 0.8 0.8
심도 : 0.0m ~ 0.8m S- 1 1.0 7/ 30
실트섞인 모래
상부0.0m ~ 0.15m 아스팔트
습윤상태
갈색 S- 2 2.0 8/ 30
- 퇴적층-
S- 3 3.0 7/ 30
심도 : 0.8m ~ 13.5m
실트섞인 모래
느슨(Loose) ~ 조밀(Dense) S- 4 4.0 9/ 30
상대밀도
습윤상태
5 심도13.0m 하부 자갈혼재 S- 5 5.0 8/ 30
암회색~ 암갈색
S- 6 6.0 9/ 30
퇴적층 S- 7 7.0 7/ 30
S- 8 8.0 7/ 30
S- 9 9.0 9/ 30
10 S- 10 10.0 10/ 30
S- 11 11.0 12/ 30
S- 12 12.0 11/ 30
S- 13 13.0 48/ 30
- 13.5 13.5 12.7
- 14.0 14.0 0.5 풍화토 - 풍화토-
S- 14 14.0 50/ 4
심도: 13.5m ~ 14.0m
실트섞인 모래
15 매우 조밀(Very Dense) S- 15 15.0 50/ 3
상대밀도
습윤상태
황갈색 S- 16 16.0 50/ 4
- 풍화암-
심도 : 14.0m ~ 30.0m S- 17 17.0 50/ 3
굴진시 세편상 암편으로 분해
매우 조밀(Very Dense)
상대밀도 S- 18 18.0 50/ 2
습윤상태
황갈색
S- 19 19.0 50/ 2
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 3
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 6.8 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
S- 20 20.0 50/ 2
S- 21 21.0 50/ 1
S- 22 22.0 50/ 1
S- 23 23.0 50/ 1
S- 24 24.0 50/ 1
S- 26 26.0 50/ 1
S- 27 27.0 50/ 1
S- 28 28.0 50/ 1
S- 29 29.0 50/ 1
35
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 4
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 6.4 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
- 매립층-
매립층
- 0.9 0.9 0.9 심도 : 0.0m ~ 0.9m S- 1 1.0 7/ 30
실트섞인 모래
상부0.0m ~ 0.15m 아스팔트
습윤상태
갈색 S- 2 2.0 8/ 30
- 퇴적층-
S- 3 3.0 7/ 30
심도 : 0.9m ~ 14.0m
실트섞인 모래
느슨(Loose) ~ 조밀(Dense) S- 4 4.0 9/ 30
상대밀도
습윤상태
5 심도11.5m 하부 자갈혼재 S- 5 5.0 9/ 30
암회색~ 암갈색
S- 6 6.0 10/ 30
S- 7 7.0 10/ 30
퇴적층
S- 8 8.0 9/ 30
S- 9 9.0 11/ 30
10 S- 10 10.0 13/ 30
S- 11 11.0 10/ 30
S- 12 12.0 41/ 30
S- 13 13.0 49/ 30
S- 18 18.0 50/ 2
S- 19 19.0 50/ 2
시 추 주 상 도
DRILL LOG
춘천시 후평동 729번지 주거 ( 주) 시
공 번 BH- 4
공 사 명
P
R
O
J
E
C
T
REMARKS
복합 신축공사 HOLE No. 자 시
지 반 고 현지반고
E
L
E
V
A
T
I
O
N
m U.D. SAMPLE
강원도 춘천시 후평동 729번 시 시
L
O
C
A
T
I
O
N
지 지 하
G
R
O
U
N
D
W
A
T
E
R
S.P.T. SAMPLE
(GL- ) 6.4 m 시
CORE SAMPLE
D
A
T
E
2020년10월14일 자
I
N
S
P
E
C
T
O
R
K.S.M 트 진시
DISTURBED SAMPLE
고 Scale 심도 층 후 주상도 시 시
지 층 명 U Sample Standard Penetration Test
일S
Depth Thick- Colum- 지층명
분C 시
Elev. N N blow
ness nar Description S
m m m m Section 번 심도 (회/cm) 10 20 30 40 50
S- 20 20.0 50/ 2
S- 21 21.0 50/ 1
S- 22 22.0 50/ 1
S- 23 23.0 50/ 1
S- 24 24.0 50/ 1
S- 26 26.0 50/ 1
S- 27 27.0 50/ 1
S- 28 28.0 50/ 1
S- 29 29.0 50/ 1
35
4. 현장시험
1. 공 내 재 하 시 험
2. 공 내 전 단 시 험
3. 투 수 시 험
55
4.1 공내재하시험
55
ELASTMETER TEST
Project Name 犞熢柢͑篊磏壟͑ͨͣͪ憎滆͑渂其懻穯͑柦犛击斲
Test Date 2020. 10. Model Elastometer - 2 G.W.L(m)
Hole No BH-1 Geology 禓筚橚 Hole Size NX
Test Depth(m) 18.0 Rock Grade Checked By 愛匶殷
TCR/RQD Strength Fracture
N-Value 50/2
3.21 43.07
2.61 43.07
2.03 43.07
1.62 43.04
1.02 42.91
0.47 42.32
0.91 42.78
ͣ
1.29 42.88
1.73 42.96
2.17 43.02
2.64 43.08
3.05 43.13
3.49 43.18
4.01 43.23
4.41 43.30 ͡
4.77 43.41 ͥ͟͡͡ ͥ͢͟͡ ͥͣ͟͡ ͥͤ͟͡ ͥͥ͟͡
5.27 43.78
4.84 43.82 ΒΕΚΦΤ͙ΞΞ͚͑
4.33 43.86
3.67 43.84
2.97 43.82
2.30 43.76 D(E) = (1+υ) x [( Py- Po )/( Ry- Ro )] x ( Ro+ Ry )/2
1.77 43.70 K = P/R
1.10 43.60 υ( Poisson`s ratio ) = 0.30
0.40 43.39
Modulus of Deformation (D) = 246 MPa
Po : 1.2 Py : 4.8
Ro : 42.60 Ry : 43.41
Po : 1.3 Py : 4.4
Ro : 42.88 Ry : 43.30
3.22 41.82
2.79 41.83
2.18 41.82
1.60 41.69
1.18 41.58
0.93 41.34
0.68 40.98
ͣ
0.46 40.25
0.86 40.74
1.22 41.03
1.64 41.34
2.04 41.58
2.46 41.76
2.84 41.93
3.19 42.11 ͡
3.62 42.35 ͤͧ͟͡ ͤͩ͟͡ ͥ͟͡͡ ͥͣ͟͡ ͥͥ͟͡
4.00 42.70
4.20 43.22 ΒΕΚΦΤ͙ΞΞ͚͑
3.73 43.30
3.07 43.35
2.59 43.31
2.14 43.21 D(E) = (1+υ) x [( Py- Po )/( Ry- Ro )] x ( Ro+ Ry )/2
1.66 43.09 K = P/R
1.17 42.86 υ( Poisson`s ratio ) = 0.35
0.40 42.30
Modulus of Deformation (D) = 81 MPa
Po : 1.6 Py : 3.6
Ro : 40.94 Ry : 42.35
Po : 1.2 Py : 3.2
Ro : 41.03 Ry : 42.11
1.95 40.70
1.50 40.69
1.04 40.66
0.47 40.51 ͥ
0.86 40.55
1.43 40.61
2.07 40.67
2.54 40.71
2.99 40.75
ͣ
3.54 40.80
3.95 40.84
4.55 40.89
4.91 40.92
5.32 40.99
5.59 41.05 ͡
5.85 41.14 ͤͪͦ͟ ͥ͟͡͡ ͥͦ͟͡ ͥ͢͟͡ ͥͦ͢͟
4.93 41.14
3.95 41.13 ΒΕΚΦΤ͙ΞΞ͚͑
2.98 41.12
1.99 41.05
0.98 40.88
0.51 40.74 D(E) = (1+υ) x [( Py- Po )/( Ry- Ro )] x ( Ro+ Ry )/2
K = P/R
υ( Poisson`s ratio ) = 0.30
Po : 1.0 Py : 4.9
Ro : 40.35 Ry : 40.92
Po : 0.5 Py : 4.9
Ro : 40.51 Ry : 40.92
55
BOREHOLE SHEAR TEST
Project Name শঊݤ୯ૡѰءए࣯ʠـଢݦ˓ی
Location
4 250.0 152.0
180.0
160.0
140.0
Shear Stress(kPa)
120.0
100.0
80.0
60.0
40.0
20.0
0.0
0.0 50.0 100.0 150.0 200.0 250.0 300.0
Normal Stress(kPa)
BOREHOLE SHEAR TEST
Project Name শঊݤ୯ૡѰءए࣯ʠـଢݦ˓ی
Location
4 400.0 279.0
350.0
300.0
Shear Stress(kPa)
250.0
200.0
150.0
100.0
50.0
0.0
0.0 100.0 200.0 300.0 400.0 500.0
Normal Stress(kPa)
BOREHOLE SHEAR TEST
Project Name শঊݤ୯ૡѰءए࣯ʠـଢݦ˓ی
Location
4 320.0 202.0
250.0
200.0
Shear Stress(kPa)
150.0
100.0
50.0
0.0
0.0 50.0 100.0 150.0 200.0 250.0 300.0 350.0
Normal Stress(kPa)
BOREHOLE SHEAR TEST
Project Name শঊݤ୯ૡѰءए࣯ʠـଢݦ˓ی
Location
4 400.0 297.0
350.0
300.0
Shear Stress(kPa)
250.0
200.0
150.0
100.0
50.0
0.0
0.0 100.0 200.0 300.0 400.0 500.0
Normal Stress(kPa)
4.3 투수시험
55
RESULTS OF FIELD PERMEABILITY IN BORE HOLES
AVERAGE K = 1.24E-03
ABOVE GWL.
BELOW GWL.
AVERAGE K = 2.49E-03
ABOVE GWL.
BELOW GWL.
AVERAGE K = 4.21E-04
ABOVE GWL.
BELOW GWL.
AVERAGE K = 8.48E-04
ABOVE GWL.
BELOW GWL.
55
SOIL TEST SUMMARY TABLE
PROJECT : 춘천 후평동 729번지 주거복합 신축공사 DATE : 2020. 10.
BH-1 13.0 7.1 2.633 N.P. N.P. 58.8 48.8 30.8 14.3 - - SM
BH-2 6.0 26.2 2.645 N.P. N.P. 100.0 92.3 28.1 9.6 7.5 SM
BH-3 11.0 17.9 2.603 N.P. N.P. 98.2 73.7 21.6 1.6 - - SW
BH-4 2.0 27.6 2.677 39.4 18.7 100.0 92.0 70.1 48.3 17.7 13.5 SC
GRAIN SIZE ANALYSIS TEST
70
60
50
40
30
20
10
0
100 10 1 0.1 0.01 0.001
Grain Particle Size (mm)
Remarks
Technician Approved
GRAIN SIZE ANALYSIS TEST
70
60
50
40
30
20
10
0
100 10 1 0.1 0.01 0.001
Grain Particle Size (mm)
Remarks
Technician Approved
GRAIN SIZE ANALYSIS TEST
70
60
50
40
30
20
10
0
100 10 1 0.1 0.01 0.001
Grain Particle Size (mm)
Remarks
Technician Approved
GRAIN SIZE ANALYSIS TEST
70
60
50
40
30
20
10
0
100 10 1 0.1 0.01 0.001
Grain Particle Size (mm)
Remarks
Technician Approved
6. 탄성파탐사시험
55
목 차
제 1장 시험 개요
1.1 시험 목적 ················································································································································ 1
1.2 시험 위치 및 일정 ································································································································ 1
1.3 시험 현황 및 현장사진 ························································································································ 1
1.4 시험 장비 ················································································································································ 1
제 2장 시험 개요
2.1 시험 방법 ··············································································································································· 2
2.2 자료 처리 ··············································································································································· 3
2.3 지반 분류 ··············································································································································· 4
2.4 동적물성치 산정 ··································································································································· 4
제 3장 시험 결과
3.1 BH-1 결과 ············································································································································· 6
부 록
1. 파형도
2. 작업사진
제1장 시험 개요
1.1 시험 목적
1.2 시험 위치 및 일정
- "춘천시 후평동 729번지 주거복합 신축공사" 현장 내 BH-1 시추공
시험 기간 2020. 10
1.3 시험 현황 및 현장 사진
1.4 시험 장비
구 분 내 용
슬레지 햄머 시
지표 탄성파 험
탄성파 발생용 플레이트
발생장치
트 리 거 링 (Triggering) 장 치 장
시추공 지오폰 시추공 지오폰 비
시스템 (3-axis, geometrix사 ) 구
24채 널 성
탄성파 측정기 (M cSEIS NX Series,
OYO사 )
제2장 시험 내용
2.1 시험 방법
탄성파의 발생, 특히 횡파의 발생이 용이하고 비교적 측정이 간단하며 자료처리가 단순하여 지반의
∙ 지표에서 탄성파를 발생시키고 시추공 내에 삽입된 수신기(3성분 지오폰)를 통하여 심도별로 탄성파
위상변화를 보이는데, 정확한 도달시간 기록을 위하여 좌․우 두 방향으로 가격하여 180o의 위상차를
확인함.
시험 모식도 주시 곡선
2.2 자료처리
하향식 탄성파탐사의 자료처리는 크게 자료변환 및 트레이스 정리, 주파수 분석 및 필터링, 초동발
췌, 구간속도 결정 및 탄성계수 산출 등으로 나눌 수 있으며 <그림 2.1>은 하향식 탄성파탐사의 자료처
리 흐름도이다.
∙ 자료처리 과정
동탄성계수 산출
2.3 지반 분류
지반의 전단파 속도를 적용하여 지반등급을 산정하는 기준은 다음과 같다. 국지적인 지질조건과 지
료 및 지하 지형이 지반운동에 미치는 영향을 고려하기 위하여 지반을 <표 2.1> 및 <표 2.2>와 같이 분
류한다. 기준면으로부터 보통암(지층의 전단파 속도, Vs=760m/s 이상)까지의 지반에 대한 평균지반특
성으로 분류하며, 보통암의 위치가 기준면으로부터 5m이하 혹은 30m 이상인 경우에는 상부 30m에
대한 평균지반특성으로 분류한다.
<표 2.1> 지반의 분류-건축구조기준(2016)
상부 30M에 대한 평균 지반 특성
지반
지반종류의 호칭 전단파 속도 표준관입시험 비배수전단강도
분류
(m/s) (타격횟수/30cm) (10-3N/mm2)
SA 경암 지반 초과
SB 보통암 지반 에서
매우 조밀한 토사 지반
SC 에서
또는 연암 지반
SD 단단한 토사 지반 에서 에서 에서
SE 연약한 토사 지반 미만
분류 기준
지반
지반종류의 호칭 토층 평균 전단파 속도, Vs
분류 기반암 깊이, H(m)
soil(m/s)
S1 암반 지반 미만
S2 얕고 단단한 지반 이하 이상
S3 얕고 연약한 지반 이하 초과 미만
S4 깊고 단단한 지반 초과 미만 이상
깊고 연약한 지반 초과 미만 초과 미만
S5
매우 연약한 지반 이상 이하
S6 부지 고유의 특성 평가 및 지반응답 해석이 요구되는 지반
(3) 대상지역의 지반을 분류할 수 있는 자료가 충분하지 않고, 지반의 종류가 일 가능성이 없는 경우에는
∙ BH-1번 시추공의 보통암(지층의 전단파 속도, Vs=760m/s 이상) 위치는 확인되지 않았으며, 30m 구간의 평균 전
단파 속도는 312m/s임
결과 분석
주시곡선 심도별 탄성파속도 구간속도
1. 파형도
2. 현장사진
1.파형도
P파 현장자료
S파 현장자료
2. 현장사진
자료 획득
자료 획득
Down Hole Test Data
용역명 춘천시 후평동 729번지 주거복합 신축공사
공 번 BH-1
시험일자 2020-10-00 측정심도 GL (-) 0.0m ~ 30.0m
Depth Soil&Rock 주시곡선(ms) Vp Vs 동탄성계수 동전단계수 동체적계수 단위중량 포아송비
GL.(-)m type P-wave S-wave (m/s) (m/s) (MPa) (MPa) (MPa) (kN/㎥) υd
0.0 ~ 1.0 2.2 5.5 450 181 169 60 292 18.0 0.403
매립층
1.0 ~ 2.0 4.3 10.7 483 195 196 70 335 18.0 0.403
2.0 ~ 3.0 6.3 15.7 490 198 202 72 345 18.0 0.402
3.0 ~ 4.0 8.6 21.3 442 178 163 58 281 18.0 0.403
4.0 ~ 5.0 11.0 27.2 423 170 149 53 258 18.0 0.404
5.0 ~ 6.0 13.6 33.8 379 152 119 42 207 18.0 0.404
6.0 ~ 7.0 16.2 40.2 389 156 126 45 218 18.0 0.404
7.0 ~ 8.0 18.3 45.6 459 185 176 63 303 18.0 0.403
퇴적층
8.0 ~ 9.0 20.3 50.4 512 207 221 79 377 18.0 0.402
9.0 ~ ### 21.7 53.9 707 287 424 151 716 18.0 0.401
10.0 ~ ### 22.9 56.9 816 334 573 205 950 18.0 0.399
11.0 ~ ### 24.1 59.6 891 368 695 249 1,126 18.0 0.397
12.0 ~ ### 25.3 62.6 813 337 583 209 936 18.0 0.396
13.0 ~ ### 26.6 65.7 783 326 545 195 866 18.0 0.395
14.0 ~ ### 풍화토 27.6 68.1 981 410 909 326 1,431 19.0 0.394
15.0 ~ ### 28.6 70.4 1,018 431 1,107 398 1,690 21.0 0.391
16.0 ~ ### 29.5 72.7 1,025 438 1,141 411 1,703 21.0 0.388
17.0 ~ ### 30.5 74.9 1,047 449 1,199 432 1,773 21.0 0.387
18.0 ~ ### 31.4 77.1 1,061 457 1,241 448 1,816 21.0 0.386
19.0 ~ ### 32.4 79.3 1,082 468 1,300 469 1,883 21.0 0.385
20.0 ~ ### 33.3 81.3 1,128 490 1,424 515 2,041 21.0 0.384
21.0 ~ ### 34.1 83.3 1,150 502 1,493 540 2,114 21.0 0.382
22.0 ~ ### 풍화암 35.0 85.2 1,207 529 1,656 600 2,322 21.0 0.381
23.0 ~ ### 35.8 87.0 1,247 549 1,782 646 2,471 21.0 0.380
24.0 ~ ### 36.5 88.7 1,330 588 2,043 741 2,803 21.0 0.379
25.0 ~ ### 37.2 90.3 1,366 607 2,174 790 2,946 21.0 0.377
26.0 ~ ### 37.9 91.9 1,421 634 2,370 861 3,178 21.0 0.376
27.0 ~ ### 38.6 93.4 1,471 659 2,558 931 3,396 21.0 0.374
28.0 ~ ### 39.3 94.9 1,529 688 2,785 1,014 3,657 21.0 0.373
29.0 ~ ### 39.9 96.3 1,581 718 3,027 1,105 3,883 21.0 0.370
Soil&Rock 평균값
심도(m)
type Vp(m/s) Vs(m/s) Ed(MPa) Gd(MPa) Kd(MPa) ρ(kN/㎥) υ
매립층 0.0 2.0 467 188 182 65 314 18.0 0.403
퇴적층 2.0 14.4 592 242 331 118 549 18.0 0.401
풍화토 14.4 15.0 981 410 909 326 1,431 19.0 0.394
풍화암 15.0 30.0 1,244 547 1,820 660 2,512 21.0 0.381
0 0 0
188 467 Vp
Vp Vp
2 2 2
Vs Vs Vs
4 4 4
6 6 6
8 8 8 242 592
10 10 10
12 12 12
14 981
14 14
G.L(-)m
G.L(-)m
G.L(-)m
16 16 16 410
18 18 18
20 20 20
22 22 22 547 1,244
24 24 24
26 26 26
28 28 28
30 30 30
0 20 40 60 80 100 120 0 500 1,000 1,500 2,000 0 500 1,000 1,500
0 0.365
0
Ed
ν Ed Gd Kd
2 Gd 2
Kd 0.37
4
4
6
6 0.375
8
8
10 0.38
10
12
12
14 0.385
G.L(-)m
14
동포아송비
심도(GL-m)
16
16
0.39
18
18
20 0.395
20
22
22
24 0.4
24
26
26
0.405
28
28
30 0.41
30
0 1,000 2,000 3,000 4,000 0 2,000 4,000 6,000
0.360 0.370 0.380 0.390 0.400 0.410
동적물성치(MPa) 동포아송비 동적 물성치(MPa)
7. 사진첩
55
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-1 시추 전경
BH-1 현장투수시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-1 표준관입시험
BH-1 시료
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-1 공내 전단시험
BH-1 공내 재하시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-2 시추 전경
BH-2 현장투수시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-2 표준관입시험
BH-2 시료
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-2 공내 재하시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-3 시추 전경
BH-3 현장투수시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-3 표준관입시험
BH-3 시료
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-3 공내 전단시험
BH-3 공내 재하시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-4 시추 전경
BH-4 현장투수시험
시 추 공 사 진
춘천 후평동729 주거복합 신축공사
BH-4 표준관입시험
BH-4 시료