Metro Testing Laboratories (Burnaby) CONCRETE

6991 Curragh Avenue, Burnaby B.C., V5J 4V6 CERTIFIED TESTING LABORATORY TEST REPORT
Tel: (604) 436-9111 Fax: (604) 436-9050

PROJECT NO. 20887


TO CLIENT ERA ENTERPRISE LTD.
Site ERA ENTERPRISE LTD. C.C. RMC READY MIX LTD.
#7 - 9069 SHAUGHNESSY ST. ERA ENTERPRISE LTD.
VANCOUVER, BC
V6P 6R9

ATTN: JAMES HURLEY

PROJECT UBC - 1778 WESBROOK CRES.


MATERIALS TESTING WESBROOK CRES., 1778 (UBC)
VANCOUVER
SET NO. 9 SPECIMENS 5 CAST 2017.Mar.17 TRANSPORTED BY RECEIVED 2017.Mar.18 BY

AGE AVERAGE COMPRESSIVE


AVERAGE MAXIMUM
SPCM SPECIMEN CURE SPCM DATE AT TEST DIAMETER (mm) OR FLEXURAL FAILURE
LENGTH OR LOAD
NO. TYPE CONDN MASS TESTED TEST BY OR STRENGTH TYPE
SPAN (mm) (kN)
(g) (DAYS) SIDE (mm x mm) (MPa) Average

A Cylinder Lab Mar.24 7 VAL 101.6 203.2 179 22.1

B Cylinder Lab Apr.14 28 101.6 203.2

C Cylinder Lab Apr.14 28 101.6 203.2

D Cylinder Field Mar.23 6 JG 101.6 203.2 143 17.6

E Cylinder Field Mar.31 14 101.6 203.2

SPECIFIED STRENGTH 32 MPa @ 28 DAYS CONCRETE TEMP. 17.0 °C AIR TEMP. 7.0 °C TREND GRAPH

CEMENT CONTENT NA kg/m 3 SLUMP mm 90 SPEC. 75 ± 20


CEMENT TYPE GU SLUMP FLOW mm NA SPEC. ±
POZZOLAN CONTENT NA kg/m 3 FLOW TIME sec NA SPEC.
POZZOLAN TYPE FA AIR % 5.2 SPEC. 6.5 ± 1.5
MAXIMUM SIZE AGGREGATE 14 mm PLASTIC DENSITY NA kg/m 3
HARDENED DENSITY NA kg/m 3
BATCH TIME 09:17 SAMPLE TIME
ADMIXTURES (ml/m³) CAST TIME 11:00
CAST BY MTS MH MOULD TYPE PLASTIC
CURING CONDITIONS MIM
INITIAL CURING TEMP:MAXIMUM 20.0 °C MINIMUM 12.0 °C
LOCATION
ROOF SLAB, GL: A-B/ 1-2.
SUPPLIER RMC READY MIX LTD.

MIX NO. 932144


COMMENTS
TRUCK NO. 247113 TICKET NO. 77952535 " * " INDICATES RESULT IS LESS THAN 70% OF
SPECIFIED STRENGTH
LOAD VOL. 10 m 3 CUM. VOL. 10 m
3

WATER ADDED NA l AUTH. BY


Page 1 of 1 2017.Mar.27 Metro Testing Laboratories (Burnaby) PER. RS

For testing conducted by this company, the testing procedures are carried out in accordance with CSA. Reporting of these test results constitutes a
testing service only. Engineering interpretation or evaluation of test results is provided only on request.