Verification of temperature-rise to IEC 61439

Customer/order: - - New calculation - Set 1


Enclosure type: Individual enclosure Custom enclosure
Decisive dimensions for temperature Height:
Width:
2,000
1,400 Siting type: Single enclosure,
rise Depth: 800 free-standing on all sides

Dimensions A0 Area factor b Ae


acc. to table 3 (Sp. 3) x (Sp. 4)
mxm m2 m2
2 3 4 5
Decisive Roof 1.40 x 0.80 1.12 0.90 1.01
dimensions for Floor 1.40 x 0.80 1.12 0.50 0.56
temperature rise
Front 1.40 x 2.00 2.80 0.90 2.52
Rear 1.40 x 2.00 2.80 0.90 2.52
Left side 0.80 x 2.00 1.60 0.90 1.44
Right side 0.80 x 2.00 1.60 0.90 1.44
Ae = ∑(AO - b) = 9.49

with effective cooling surface Ae


> 1.25 m 2 ≤ 1.25 m2
ƒ = h1.35 ÷ Ab = 2.28 (see 5.2.3) g = h ÷ w = (see 5.2.3)

Air inlet openings [cm2] 0


Enclosure constant k 0.102
Factor for horizontal divider panels d 1.00
Effective power loss [W] 523.00
Px = P*** 153.35
Δt0.5 = k × d × Px [K] 15.68
Temperature distribution factor c 1.32
Δt1.0 = c × Δt0.5 [K] 20.69

1.0 20.69
→ rotcaf sa thgieh erusolcnE

0.75

0.5 15.68

10 20 30
Excess air temperature Δt inside the enclosure →