You are on page 1of 13

e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Contents lists available at ScienceDirect

e-Prime - Advances in Electrical


Engineering, Electronics and Energy
journal homepage: www.elsevier.com/locate/prime

Transformation of conventional transformers for enhanced DC mitigation in


AC power networks with advanced grid support
Moazzam Nazir a, *, Klaehn Burkes b, Johan H. Enslin a
a
Clemson University, North Charleston, SC 29405, USA
b
Savannah River National Laboratory, Savannah River Site, Aiken, SC 29808, USA

A R T I C L E I N F O A B S T R A C T

Keywords: The flow of quasi-DC or DC in AC networks may trigger half-cycle saturation of electrical grid transformers that
DC-AC power conversion could lead to their internal heating or grid collapse. Apart from the requirement of DC mitigation measures, the
Impedance balancing conversion of conventional power grid into an intricate network demands the need for power equipment with
Power converter
dynamic control capability. The transformers provide the most strategic point in the grid for the introduction of
Power quality
Voltage control
DC protection and grid-support features. This paper proposes a fractionally rated power-electronics module
coupled to neutral and ground terminals of conventional transformers that delivers efficient power network
protection against quasi-DC or DC flow with different advanced grid-support features injected on the transformer
primary. The proposed concept is validated on an experimental hardware prototype employing power hardware-
in-the-loop (P-HIL) configuration of Typhoon HIL-402 and compared with the simulation results in this paper.
Also, a transformer and associated module protection approach employing a hybrid bypass switch has been
suggested and experimentally validated in this work. The experimental results validate the capability of the
module to counter DC injection, perform harmonics mitigation, voltage control or unbalance compensation,
impedance matching and power flow control at the same injection point.

1. Introduction a large integration of unpredictable distributed energy resources (DERs).


Due to the unpredictable nature of DERs and modern loads, there are
1.1. Motivation non-ideal power flows across the transmission corridors with some
experiencing congestion and the other staying underutilized. The
With the recent warfare and space advancements, the energy secu­ traditional power flow control strategy employing different generator
rity is compromised owing to electric grid susceptibility to impairment dispatch algorithms is no longer viable and there is a dire need to
from quasi-direct current (DC) flow in transmission lines after a high- introduce distributed, granular, and dynamic control across strategic
amplitude electromagnetic pulse (HEMP) event [1]. A similar phe­ locations in the grid [6,7]. Also, owing to the volatility of DERs, tap
nomenon is created by the geomagnetic disturbance (GMD) resulting changers and phase shifters endure exceptionally higher switching rate
from the solar storms [2]. The quasi-DC or DC flow may also exist in AC leading to substantial deterioration. To address this issue, deliberate
grids because of inappropriate switching operation of power delays could be employed. However, that further worsens the required
electronics-centered devices or due to high-voltage DC (HVDC) rapid control action. The modern generation sources and loads also lead
monopolar or ground-return mode operation in parallel AC/DC net­ to degraded power quality thus leading to ineffective grid operation [8].
works [3,4]. The resultant quasi-DC or DC flow in power networks may
result in transformers heating or ultimate damage, enhanced noise level, 1.2. Literature review
inappropriate operation of power system protection devices and could
result in grid collapse [5]. To counter most of the previously discussed issues in modern grids,
Apart from the vulnerabilities related to the DC flow in AC networks, different FACTS strategies have been suggested; unified power flow
the electric utilities are also encountering unprecedented challenges controller (UPFC) [9], static VAR compensators (SVCs), thyristor
because of rapid grid transformation into an intricate network and with switched series capacitor (TSSC) [10], thyristor-controlled series

* Corresponding author.
E-mail address: mnazir@clemson.edu (M. Nazir).

https://doi.org/10.1016/j.prime.2022.100101
Received 12 October 2022; Received in revised form 21 November 2022; Accepted 17 December 2022
Available online 21 December 2022
2772-6711/© 2022 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-
nc-nd/4.0/).
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Table 1
Prime Features of exisitng solutions and proposed approach [14].
HVDC Light UPFC FR-BTB G-CDPAR G-CNT Proposed scheme

Transformer 2 fully rated, 2 fractionally rated, 1 fractional rating, 1 fully rated, standard 1 fully rated, standard 1 fully rated, standard
count & rating standard design custom design standard design design design design
Converter type & VSC B2B, fully VSC B2B, fractional VSC B2B, fractional AC chopper, fractional VSC B2B, fractional AC chopper, fractionally
rating rated rating rating rating rating rated
BIL management Handled by Challenging, relies on Challenging, converter Handled by standard Handled by standard Handled by standard
standard series transformer floating at the line transformer, converter at transformer, converter at transformer, converter at
transformer design voltage ground level ground level ground level
Cooling Active, deionized Active, forced air Forced air or Forced air or combined Forced air or combined Forced air or combined
water combined with with transformer cooling with transformer cooling with transformer cooling
transformer cooling
System ~95% ~99% ~99% ~99% ~99% ~99%
efficiency
DC mitigation/ No No No No No Yes
isolation
Voltage scaling Yes No No Yes Yes Yes
Power flow Complete and Independent PQ Independent PQ Optimized for P or Q Independent PQ control Independent PQ control
control independent PQ control around base control around base control around base around base power flow around base power flow
capability control power flow power flow power flow
Fail normal No Yes - large stress on Yes Yes Yes Yes
series transformer
Line unbalance Yes No No No Yes Yes
management
Scaling Yes BIL management BIL management BIL management limits Yes Yes
limits scalability impairs scalability scalability
Cost Highest Higher Lower Lowest Lower Lower

capacitor (TCSC) [11], controllable network transformer (CNT) [12], transformer that hinders its applicability to the existing two-winding
fractionally rated back-to-back (FR-BTB) converter and compact dy­ transmission transformers. Moreover, the above discussed FACTS de­
namic phase angle regulator (CDPAR) [13,14]. vices do not block quasi-DC or DC flow in AC power networks.
Accordingly, proper grid operation stays at risk even after the installa­
tion of these power-electronics based devices. Apart from the
1.3. Research gaps above-mentioned devices, the solid-state transformers (SSTs) also pro­
vide an alternate to address some of the above discussed issues. How­
Most of the above discussed device’s float near the line voltage that ever, they are still far from the complete replacement of traditional
raises isolation challenges [13]. This question was addressed in the transformers due to the comparative shorter life span and robustness.
grounded controllable network transformer (G-CNT) scheme discussed Moreover, there has been a significant investment on the already
in [14], that employs a three-winding transformer with its tertiary installed conventional transformers with their substitution accompanied
winding coupled to a marginally rated converter that operates near the with massive expenditure and time. In this perspective, strategies that
ground potential. But this approach necessitates a special triple-winding

Fig. 1. (a) DC elimination and grid-support approach, (b) DC link voltage control.

2
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 2. Injection strategy for different grid-support functions.

can introduce protection and grid-support features in the existing Section 7.


traditional transformers are a compelling solution leading to the concept
of hybrid transformers. 2. Proposed hybrid transformer

1.4. Contributions The single-phase counterpart of the hybrid transformer strategy is


demonstrated in Fig. 1(a). It employs a power-electronics centered
A marginally rated converter device installed with the two-winding module connected between the transformer neutral and ground termi­
electrical power transformers has been suggested that delivers effi­ nals. The scaled converter utilizes an H-bridge converter rated to
cient defense against DC flow in AC grids in addition to multiple grid- 25–30% of the line voltage. The DC-link of the proposed module utilizes
support functions [15,16]. These functions include impedance a capacitor C2 and an active storage, for instance, a battery or an ultra-
balancing, voltage unbalance compensation, harmonics mitigation, capacitor (UC), for storing the reverse power flow towards the converter
voltage control, and power flow control. The scheme essentially trans­ and supplying it when needed. The DC-link power flow control is not the
forms typical transformers into hybrid ones and the converter fractional focus of this paper, but a simplified DC-link voltage control is shown in
rating diminishes size, cost, and intricacy of the proposed module. The Fig. 1(b). The required energy storage to be integrated to the DC-link is
proposed strategy has also shown its superior performance to enhance largely dependent upon the application. For instance, if DC mitigation is
HVDC-classic reliability and reduced complexity [17]. A comparison of the only objective, a large DC-link capacitor or UC might be sufficient,
existing solutions for dynamic grid control and the strategy proposed in but if the objective is power flow control that usually spans over hours,
this paper is shown in Table 1 [14]. the DC-link might require a continuous power source, such as, a separate
This paper discusses the experimental evaluation of the hybrid converter fed by an independent source. The AC side switching har­
transformer scheme and compares it with the simulation results. The monics are mitigated employing a low-frequency filter comprised of C1
evaluation involves a laboratory prototype validated using the power and L1.
hardware-in-the-loop (P-HIL) configuration of Typhoon HIL-402. It has A hybrid switch accompanies the proposed device, where the solid-
been proposed in our previous works that the hybrid module could state component makes quick path to ground during faults and the
utilize a bypass switch to curtail high voltage development across the mechanical switch delivers a low-loss route to the associated high-value
module during inrush or ground faults scenarios. However, a compre­ currents. The bypass switch has a dual advantage, ensuring converter
hensive design and real operation of such a switch has not been pre­ and transformer protection from high voltage events across capacitor C1
sented earlier. In this work, the design of a bypass switch configuration and allowing continuity of traditional functions of the associated
is also presented, and its proper working is experimentally verified. transformer in case of module failure.
The proposed device bears the capability to inject voltage with var­
1.5. Organization of the paper iable amplitude and phase angle between transformer neutral terminal
and ground. This allows a traditional transformer to perform voltage,
The remainder of the paper is structured as follows: Section 2 gives a power flow and impedance control along with DC mitigation as shown in
concise overview of the proposed hybrid transformer topology. The Fig. 2, where the control limit is contingent upon the converter size. The
hardware prototype description is given in Section 3. The simulation utility transformers at transmission level sub-stations are normally in a
results of the scaled hardware prototype are presented in Section 4. The three-phase configuration preferably constructed by integrating three
experimental outcomes for a variety of operation modes of the proposed individual single-phase transformer units in required configuration
scheme are examined in Section 5. The protection strategy for the pro­ [18]. For transmission levels, three such proposed modules could be
posed module is discussed and associated experimental results are given employed, one between each of the three-transformer primary winding
in Section 6. The conclusion of the paper and future work is presented in neutrals and common substation ground.

3
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 3. Proposed controller for the DC mitigation and grid-support scheme.

The controller proposed for the DC mitigation and grid-support injected between the transformer neutral and substation ground, as can
scheme that generates the pulse width modulation (PWM) set point is be seen in Fig. 3. This effectively retains the transformer primary
shown in Fig. 3. The proposed controller is explained in detail in the winding voltage (Vxmfr), shown in Fig. 2, at its desired value.
subsequent sections.
2.3. Power flow control
2.1. DC mitigation
The active (P) and reactive (Q) power flow between PCC and
The prime aspect of the device is its capability to perform DC miti­ transformer primary shown in Fig. 2 is given as:
⃒ ⃒ (
gation or prevention of power network harmonics from travelling to­ 3|VPCC |⃒Vxmfr,eq ⃒sin δPCC − δxmfr,eq
)
wards the downstream of the module-integrated transformer. This P= (1)
Zxmfr
objective is achieved by measuring the voltage at VPCC and isolating its
harmonic content (Vh) from the fundamental component (V1) employ­ ( ⃒ ⃒ ( )
3 |VPCC |2 − |VPCC |⃒Vxmfr,eq ⃒cos δPCC − δxmfr,eq
ing a SOGI-based PLL, that are frequently utilized for synchronization of Q= (2)
single-phase grid-connected converters [19]. This unwanted signal (Vh) Zxmfr
is further introduced between the transformer neutral terminal and
Where, Vxmfr,eq is the sum of transformer and converter voltage, δPCC
ground that ensures the voltage at the transformer primary terminals
and δxmfr,eq are the angles of VPCC and Vxmfr,eq respectively. The pro­
(Vxmfr) is always harmonic free. This DC mitigation control branch can
posed strategy offers separate control over the converter voltage and
be seen in Fig. 3.
angle, therefore, Vxmfr,eq and δxmfr,eq could be adjusted individually. This
provides separate control over the active and reactive power. The
2.2. Voltage regulation implementation of this control fuction is shown in Fig. 3.

For the purpose of voltage regulation or balancing, the difference


between the desired (VPCC,ref) and actual voltage (VPCC) at PCC is

Fig. 4. Experimental laboratory hardware protoype to evaluate proposed scheme.

4
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 5. One-line illustration of hardware prototype.

2.4. Impedance control


Table 2
Hardware prototype parameters.
The replacement or upgradation of a transformer is usually associ­
ated with concerns like impedance mismatch that adversely effects Item Description
power flow and grid balance. The proposed device can address this issue TUT transformer 240V/240V, 1 kVA
through cancellation of the additional transformer impedance (Zxmfr) IGBT/chopper module Semikron B6U+E1C1F+B6C1
voltage resulting from the mismatch. This impedance control approach Converter controller Typhoon HIL-402
Voltage controller Kp=0.05, Ki=165, Limit=-4 to 4
is described in Fig. 2, where the converter injects an opposing voltage Current controller Kp=0.1, Ki=50, Limit=-1 to 1
(Vconv), by adjusting the gain G1, to nullify the extra voltage (Vz-Vz, Switching frequency (fsw) 5 kHz
effective) appearing across the transformer inductance, thus restoring its Level converter IC TI CD-4504BE
original value (Vz,effective). The implementation of impedance control Filter capacitor (C1) 50 uF
Filter inductor (L1) 1 mH, 10A
feature is shown in Fig. 3.
Solid state relay Crydom D2490-10
An internal current-control loop is also added to the proposed Mechanical relay Hiltego 5V, 10A
controller as can be seen in Fig. 3. This enables the current-limiting
mode of the module during ground faults when the bypass switch
operates and generates a short circuit across the module terminals. The sags or swells on the power networks and the isolation transformer is
variety of control actions discussed previously could be performed under utilized for safety objectives. An RL load is tied to the secondary winding
varying grid conditions. of TUT that loads it to 80%. The DC flow in power networks is mimicked
In the proposed strategy, the fractionally rated power converter is utilizing a DC power supply that is integrated to the neutral terminal of
positioned closed to the ground that helps to avert surpassing the basic the isolation transformer. The proposed module is realized employing an
insulation level (BIL) of the transformer and facilitates in reducing the IGBT converter/chopper unit from Semikron operated in a single-phase
converter isolation requirements. Also, the positioning of the module mode. The DC link is fed using a variac coupled to an isolation trans­
adjacent to the transformer helps in reducing the cooling cost, where the former for controlled input and safety purposes, respectively. For
module could be mounted on plates cooled with the associated trans­ experimental DC-link regulation, the DC chopper is activated above a
former oil. It is also recommended that the future transformers that are pre-defined threshold followed by the reverse power dissipation across a
desired to be equipped with these modules should be upgraded with braking resistor. In the practical scenario, it is desirable to store the
increased oil tank capacity and more radiator plates to ensure efficient reverse active power flow utilizing battery storage with the DC-link and
simultaneous cooling of transformer and the proposed converter supplying this stored power to the main grid when required. The
modules. Typhoon HIL-402 is used as a controller for the proposed module by
operating it in a P-HIL configuration. However, the maximum digital
3. Laboratory prototype description output of Typhoon HIL is 5V (TTL) that is unable to switch the IGBTs in
the module that operate at a 15V (CMOS) pulse signal. To resolve this
The hybrid transformer scheme is tested on a laboratory prototype as issue, a Texas Instrument (TI) voltage level shifter IC CD-4504BE is in­
presented in Fig. 4. The single-line diagram of the prototype is shown in tegrated to the digital output of Typhoon.
Fig. 5. It comprises of a one-to-one single-phase transformer (TUT) fed The equipment and control parameters of the hardware prototype
through a variac coupled to an isolation transformer. The variac mimics are presented in Table 2.

5
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 6. Proposed strategy simulation under harmonics injection for scaled prototype; Top subplot shows voltage (VPCC) and current (Iprim) on HST primary, second
subplot shows HST load voltage (Vload), third subplot shows harmonic content in HST primary voltage (Vh) and compensation signal generated by proposed module
(Vconv), bottom subplot shows DC link voltage (VDC,link).

Fig. 7. Proposed strategy simulation under grid voltage sag for scaled prototype; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load
voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).

4. Scaled prototype simulation results scheme for a scaled prototype. In the next section, P-HIL results from an
actual hardware protype are presented and discussed. Finally, the
A simulation model was created for the laboratory scale hardware simulation and hardware results are compared and discussed in the
prototype whose results will be presented and compared with the actual subsequent section.
hardware prototype. First, the DC mitigation performance of the pro­
posed device is evaluated by injecting DC and entering the TUT into half- 5. Experimental results
cycle saturation. Later, module is activated that effectively counters the
injected DC and returns the transformer to its normal operation as The different scenarios that a real utility transformer can experience
shown in Fig. 6. A simulation of the proposed scheme is also performed are created and proposed module is assessed against tackling these is­
for the case of a voltage sag that is generated by reducing the source sues [2–6,8]. The experimental results are presented under respective
voltage to 0.85pu. Later, the module is activated to restore the load scenario.
voltage to its nominal value as shown in Fig. 7. These two simulation
results are discussed here to show the effectiveness of the proposed

6
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 8. Proposed strategy evaluation under harmonics injection; Top subplot shows voltage (VPCC) and current (Iprim) on HST primary, second subplot shows HST
load voltage (Vload), third subplot shows harmonic content in HST primary voltage (Vh) and compensation signal generated by proposed module (Vconv), bottom
subplot shows DC link voltage (VDC,link).

and its output effectively follows harmonics in the VPCC. This leads to
Table 3
isolation of harmonics from moving towards the load side. This facili­
THD of load voltage for different operation scenarios.
tates to prevent transformer half-cycle saturation during flow of DC in
Normal operation DC injection DC injection compensation power networks. It is pertinent to mention that harmonics (Vh) during
3.5% 13% 1% normal operation of the transformer in Fig. 8 are preexistent in the grid
voltage that represent a non-ideal source. The THD of the load voltage
for the three regions of operation in Fig. 8 is shown in Table 3.
5.1. DC mitigation This DC mitigation ability of the proposed module is greatly desir­
able under the present scenario of exponential addition of power
To evaluate DC mitigation capability of the proposed module, the electronics-based generation resources and loads that lead to unabated
installed DC power supply is employed to force TUT into half-cycle injection of harmonics to the grid.
saturation by mimicking the previously discussed DC injection sce­
narios. This mode leads to increased harmonics on each side of the
transformer as depicted in Fig. 8. Afterwards, the module is triggered,

Fig. 9. Proposed strategy performance under grid voltage sag; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load voltage (Vload),
third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).

7
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 10. Proposed strategy performance under grid voltage swell; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load voltage
(Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).

Fig. 11. Utilization of proposed strategy to increase power flow across TUT; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load
voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).

5.2. Voltage regulation autotransformers endure rapid switching. This induces significant
deterioration and undesirable control action delays compromising grid
Now, the voltage regulation ability of the module is assessed. The reliability. In this situation, the module could provide rapid and grainy
objective, in this case, is to control the load voltage regardless of voltage grid voltage control. Also, the implementation of the proposed module
dips or surges on the grid. To simulate a voltage dip on the grid, the on a per-phase basis allows its utilization for grid unbalance mitigation
variac output connected to primary of TUT is reduced to 0.85pu. Next, [16]. Moreover, the voltage control feature of the suggested module
the module is actuated and result for this case is displayed in Fig. 9. The could be utilized to satisfy IEEE 1547-2018 by providing VRT services to
module successfully controls the load voltage to its normal value. Also, a DERs [20]. This objective could be achieved by operating the proposed
voltage swell is created by increasing the variac output that is followed device as a STATCOM. The more details regarding this feature of the
by voltage regulation by the proposed module. The result for this case is proposed device can be found in [21].
presented in Fig. 10, where the voltage control ability of the proposed
module is verified. This voltage control ability is extremely valuable for
the power networks due to rapid addition of volatile renewable energy 5.3. Power flow control
sources. The unpredictable renewable generation causes taps of
To depict the power flow management capability introduced by the

8
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 12. Utilization of proposed strategy to decrease power flow across TUT; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load
voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).

where the additional power is provided by the converter. In the second


Table 4
case, the quadrature voltage is injected at a leading angle w.r.t. the VPCC
Power flow control capability of proposed module.
and consequently a decreased power flow is observed across the trans­
State P flow across P flow from Q flow from former as depicted in Fig. 12. In this scenario, the power difference starts
TUT (p.u) module (p.u) module (p.u)
flowing towards the converter, where it could be stored for later utili­
Normal operation 0.76 -0.01 0 zation. The above presented power flow control results are summarized
20% lagging injection ( 0.88 0.07 0.05
in Table 4.
Fig. 9)
20% leading quadrature 0.6 -0.09 -0.02 The power flow control capability of the hybrid transformer is highly
injection (Fig. 10) relevant considering the exponential integration of DERs. The volatile
nature of DERs leads to congestion or underutilization of transmission
capacity under different generation scenarios. The proposed dynamic
module into the traditional TUT, an angular voltage injection from the power flow control ability introduced by the device in conventional
module w.r.t. the VPCC is utilized. In the first case, the injected voltage transformers can be employed for fast redistribution of power and
(Vconv) is lagging the VPCC by 50 degrees and the resultant response is eventually employing the DERs at their maximum generation capacity.
demonstrated in Fig. 11. The rise in the power angle leads to an This feature is also highly relevant to the parallel AC/DC transmission
enhanced power flow through the transformer, as per Eqs. (1) and (2),

Fig. 13. Impedance control aspect of the proposed module; Top subplot shows voltage across external impedance added to transformer primary (Vz), second subplot
shows HST load voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).

9
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Table 5 performance of the proposed hybrid transformer strategy thus providing


Converter rating as a function of transformed power. an all-in-one solution to the electric utilities for resolving multiple
Function (Refer to Figs.6–13) Maximum converter Maximum converter contemporary grid problems.
output voltage (AC output power (AC From the field deployment perspective, the proposed solution is
side), pu of base side), pu of completely relevant for 24–500 kV networks where single-phase trans­
voltage transformed power
formers are deployed to form three-phase substations. The development
Simulation P-HIL Simulation P-
HIL of single-phase converter for the proposed application requires devices
that could provide high blocking voltage and switching speed or by
DC mitigation 0.19 0.2 0.12 0.14
Voltage regulation (sag of 0.85pu) 0.18 0.2 0.13 0.14
employing converter topologies with high number of series multi-level
Voltage regulation (swell of 1.15pu) 0.17 0.18 0.11 0.10 connections. High Voltage (>6 kV) wide bandgap (WBG) silicon car­
Power flow control (decreased 0.2 0.22 0.26 0.29 bide (SiC) based MOSFETs, in a three-cell cascaded H-bridge configu­
power flow) ration to handle the required high voltage (>20 kV) DC-bus voltage,
Power flow control (increased 0.2 0.18 0.14 0.15
could be utilized for this approach as described in [23]. The WBG de­
power flow)
Impedance control 0.006 0.008 0.017 0.02 vices have higher peak electric field strength and power devices with
blocking voltages in the range of 10–24 kV have already been demon­
strated [24–26]. The 15 kV SiC MOSFET may be a good option for future
that are experiencing a growing trend in China and Europe. The HVDC designs and is suitable for applications requiring higher voltages and
transmission possesses the inherent feature of performing power flow lower currents as its Ron increases exponentially with temperature that
control whereas the AC-tie lines do not bear this ability that could be leads to higher conduction loss [23]. Better cooling, such as forced air or
introduced utilizing the proposed modules [19]. water cooling could be utilized to drop thermal resistance significantly.
The other approach could be the utilization of low-voltage IGBTs or
5.4. Impedance control MOSFETs in series to split the high voltage. This approach has been
broadly utilized in designing Voltage Source Converters (VSCs), now
To assess the impedance control ability of the proposed device, an available upto 500 kV, for the HVDC substations and a wide variety of
impedance mismatch scenario is mimicked by adding an external topologies have already been demonstrated; MMC with half bridges,
inductance of 1mH to the primary winding of TUT. This leads to MMC with full bridges, hybrid MMC with half and full bridges, clamped
diminished flow across the transformer which is sensed by the proposed single cell MMC, clamped double-cell MMC, alternate arm converter and
module, and it injects a voltage by adjusting impedance gain G1 to so on [27,28]. Which converter topology to utilize for a specific appli­
nullify the resultant effects of impedance (Zxmfr) addition. The experi­ cation is largely dependent upon the respective requirements, such as,
mental result for this case is presented in Fig. 13, where it is seen that DC fault current limitation, DC fault current control, valve cost,
voltage appearing across the inserted impedance (Vz) is sensed by the switching and conduction losses etc. For the proposed device, the
controller and it adjusts the gain G1 to -0.67 for effective cancellation of thermal management could be efficiently performed utilizing passive
this additional voltage and restoring the normal operation of the TUT by cooling where the converter is mounted on plates cooled with the
recovering the load voltage. transformer oil. The transformers to be integrated with this module
The impedance control requires prior knowledge of the voltage drop could be upgraded with increased oil tank capacity and increasing
across the impedance (Zxmfr) of the replaced transformer and the new number of radiator plates for effective cooling. This also reduces
transformer to automatically adjust the gain G1. The impedance Zxmfr is pumping costs associated with water-cooled devices at this power level
not an external one in real transformers and, therefore, the voltage that are installed at significant distance from the substation
required for impedance control is hard to measure. However, there are transformers.
alternate ways to obtain this voltage. For instance, the impedance of
actual and replaced transformer can be obtained from the name plate, 6. Module protection strategy
which can be multiplied with the current flow through transformer
primary to obtain the required voltage injection. The other approach The converter protection against high voltage development across
could be the utilization of historical flows through the damaged trans­ the filter capacitor C1 during ground faults or inrush scenarios is highly
former to match them with the replaced transformer flows by tuning G1. critical. In addition to converter damage, this might lead to exceeding
However, once adjusted no continuous tuning of G1 is required as long as the protected transformer BIL, that is typically 10 times higher than the
the transformer operates within the linear operating range. The nominal rating of a transformer. As already discussed, the power
impedance control element of the proposed device could be utilized to electronics-based SSTs reliability is still significantly lower than the
balance the power flow across the phases of the three single-phase traditional transformers and therefore, integration of a power
transformers or two parallel three-phase transformers, where the electronics-based device without effective protection consideration
mismatch could be the result of utilizing non-custom built replacement might compromise the high reliability of conventional transformers.
transformer. This approach could be utilized for rapid transformer re­ Considering the speedy response and high-current requirement of the
placements or fast power recovery in event of irreversible damage by bypass, an antiparallel solid-state SCR arrangement coupled to a parallel
utilizing a spare unit or borrowing from a neighboring utility under mechanical switch could provide an optimum protection. The solid-state
auspices of programs like spare transformer equipment database (STED) portion of the proposed device could be utilized for rapid initiation of
or spare equipment database (SED) initiated by Edison Electric Insitute bypass that is followed by closure of the mechanical switch that carries
(EEI) and NERC [22]. the fault or inrush current with little loss. A Metal Oxide Varistor (MOV),
The maximum converter output voltage as per unit of base voltage set at 0.4pu, is also integrated parallel to the proposed switch to prevent
and converter output power as a fraction of the power flow across the damage of the converter from momentary voltage transients. The
transformer for the above discussed scenarios are shown in Table 5. It is module output voltage (Vconv) is constantly observed and when it ex­
pertinent to mention that these values are for the extreme scenarios ceeds a pre-defined threshold, a signal is generated to operate the bypass
generated in a laboratory environment to depict different functions of switch for 25 cycles. The 25 cycles are adequate for the clearance of
the proposed module. In a real-world scenario, the required power rat­ ground fault by protection devices and for the successful decay of inrush
ing of the module will be much lower due to less severe electrical grid currents [29]. The operation of bypass switch establishes a short circuit
disturbances. condition across the converter. However, a pre-defined current limiting
The above presented experimental results validate the promising threshold in the converter control (shown in Fig. 3) inhibits the flow of

10
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

avoiding its overvoltage or overcurrent damage. Throughout this time,


voltage across the converter output stays close to zero. Moreover, the
module output current is limited to around 4pu due to associated
current-limiting mode. After 25 cycles, the converter effectively returns
to its normal function of DC mitigation. The brief closure of the bypass
still prohibits the associated transformer from going into half-cycle
saturation owing to substantially longer time constant linked to the RL
circuit consisting of magnetizing inductance of the transformer and line
impedance [6].
Now, the protection strategy is also evaluated when the module is
performing the voltage regulation grid support under a grid voltage dip.
The experimental result for this scenario is presented in Fig. 17, where it
is again noticed that the initiation of a ground fault is successfully
detected followed by the bypass switch operation that limits the voltage
across the converter and avoids the high fault current to flow through
the converter. Also, the module returns to its normal operation of
voltage regulation as soon as the bypass switch opens after the delay of
25 cycles. It is pertinent to mention that due to the trip logic shown in
Fig. 15, the bypass switch repeats the same cycle if for some reason the
fault stays uncleared or there are consecutive high voltage events across
the converter. This ensures the module protection and its effective
operation under all scenarios.
The module bypass during transformer energization helps to avert
any adjustments to the 2nd harmonic blocking ability of differential re­
lays due to this new installation. The bypass switch also allows the
Fig. 14. Flow chart for bypass switch operation.
associated power transformer to continue performing its usual operation
in case of module failure. The proposed protection topology has many
considerably higher currents. Utilizing the current-limiting mode applications for dynamic grid controllers that utilize converters or
instead of blocking the converter aids in rapid servicing by the proposed analogous topologies.
module as soon as the bypass switch reopens to provide faster response
times. The bypass protection strategy discussed above is illustrated in 7. Conclusions and future work
Fig. 14. The signal generation logic to trip the bypass switch is shown in
Fig. 15. This paper proposes an effective DC mitigation and advanced grid-
The module fault protection scheme is evaluated on the experimental support module, that transforms the traditional transformers into
prototype. It is observed that the mechanical switch operates almost hybrid transformers. The experimental results from a laboratory-scale
instantaneously with the application of the trip signal. As this does not hardware prototype are also presented and compared with simulation
replicate the typical tripping behavior of a circuit breaker, a delay of 3 results. The experimental results validate the efficient functioning of the
cycles is created between the switch trip initiation and the mechanical proposed strategy in protecting the AC power grids against DC flow and
switch operation. From the perspective of field installation of the pro­ addressing critical challenges encountering electric utilities that involve
posed module, it represents a scenario where the solid-state switch is grid power quality, power flow control, impedance matching and
operated with the embedded controller to avoid the delays introduced voltage balancing. The paper also proposes and experimentally validates
by the field relays from damaging the converter, whereas the parallel a bypass protection module that is intended to protect the proposed
breaker is tripped by a typical substation relay. module and to circumvent surpassing the associated transformer basic
For the experimental evaluation, a fault is created for a few cycles by insulation level (BIL) rating in event of high-voltage events at module
shorting the primary of TUT at 0.95 s when the converter is performing output terminals. The design, control and operation of a multi-level
its DC mitigation operation. This scenario mimics a temporary ground converter for practical application of the proposed scheme remains a
fault, and the outcome is presented in Fig. 16. It is seen that occurrence challenge and will be addressed in the ongoing research. The future
of a ground fault raises the module output voltage (Vconv). As soon as it work includes implementation of the suggested scheme on a utility scale.
crosses the pre-defined threshold of 0.4pu, the controller generates a trip This involves its utilization in a selected substation with a transformer
signal for the bypass switch. The solid-state switch immediately operates experiencing different challenges discussed in this paper. The future
and creates a short across module terminals that is followed by me­ work also involves enhancing reliability of a transmission and distri­
chanical switch operation after 3 cycles. This bypass path avoids flow of bution network through optimal conversion of transformers into hybrid
the significantly higher fault current through the converter, thus, transformers.

Fig. 15. Generation of trip signal for hybird bypass switch.

11
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Fig. 16. Proposed protection scheme performance under a temporary ground fault during DC mitigation; Top subplot shows current on HST primary (Iprim), second
subplot shows HST load voltage (Vload), third subplot shows harmonics in HST primary voltage (Vharmonics) and compensation signal generated by proposed
module (Vconv), fourth subplot shows module output current (Iinv,op), fifth subplot shows DC link voltage (VDC,link), bottom subplot shows switching sequence of
solid state and mechanical switch.

Fig. 17. Proposed protection scheme performance under a temporary ground fault during voltage regulation; Top subplot shows voltage on HST primary (VPCC),
second subplot shows HST load voltage (Vload) and compensation signal generated by proposed module (Vconv), third subplot shows module output current (Iinv,
op), fourth subplot shows DC link voltage (VDC,link), bottom subplot shows switching sequence of solid state and mechanical switch.

Declaration of Competing Interest Data Availability

The authors declare that they have no known competing financial No data was used for the research described in the article.
interests or personal relationships that could have appeared to influence
the work reported in this paper.
Acknowledgments

This work was supported by the Laboratory Directed Research and

12
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101

Development (LDRD) program within the Savannah River National [21] M. Nazir, J.H. Enslin, Converter-based intelligent transformer for enhanced grid
monitoring and control, in: Proceedings of the 5th IEEE Workshop on the
Laboratory (SRNL). This document was prepared in conjunction with
Electronic Grid (eGRID), Aachen, Germany, 2020, pp. 1–6, https://doi.org/
work accomplished under Contract No. DE-AC09-08SR22470 with the 10.1109/eGRID48559.2020.9330675.
U.S. Department of Energy (DOE) Office of Environmental Management [22] Benefits of Using Mobile Transformers and Mobile Substations for Rapidly
(EM). Restoring Electrical Service,” A Report to the United States Congress pursuant to
Section 1816 of the Energy Policy Act of 2005, U.S. Department of Energy, 2006.
August[Online].
References [23] A.Q. Huang, Q. Zhu, L. Wang, L. Zhang, 15 kV SiC MOSFET: an enabling
technology for medium voltage solid state transformers, CPSS Trans. Power
[1] EMP Task force Work Plan July 2019, "Overview of objectives and key Electron. Appl. 2 (2) (2017) 118–130, https://doi.org/10.24295/
deliverables," Accessed on: December 03, 2020. [Online]. Available: https://www. CPSSTPEA.2017.00012.
nerc.com/pa/Stand/EMPTaskForceDL/Workshop_Presentations_July_25_2019.pdf. [24] L. Cheng, et al., 15 kV, large area (1 cm2), 4H-SiC p-type gate turnoffthyristors,
[2] Hearing of the U.S. Senate Homeland Security and Governmental Affairs Mater. Sci. Forum 740–742 (2013) 978–981. Jan.
Committee February 2019, "Perspectives on protecting the electric grid from an [25] L. Cheng, et al., 20 kV, 2 cm2, 4H-SiC gate turn-off thyristors for advanced pulsed
electromagnetic pulse or geomagnetic disturbance," Accessed on: December 03, power applications, in: Proceedings of the 19th IEEE Pulsed Power Conference
2020. [Online]. Available: https://www.hsgac.senate.gov/imo/media/doc/Tes (PPC), San Francisco, CA, USA, 2013, pp. 1–4. Jun.
timony-Horton-2019-02-27.pdf. [26] E. V. Brunt et al., "22 kV, 1 cm2, 4H-SiC n-IGBTs with improved conductivity
[3] M. Yang, D. Deswal, F. de Leόn, Mitigation of half-cycle saturation of adjacent modulation," 2014 IEEE 26th International Symposium on Power Semiconductor
transformers during HVDC monopolar operation—part i: mitigation principle and Devices & IC’s (ISPSD), 2014, pp. 358-361, doi: 10.1109/ISPSD.2014.6856050.
device design, IEEE Trans. Power Deliv. 34 (6) (2019) 2232–2239, https://doi.org/ [27] S. Norrga, Xiaoqian Li, L. Ängquist, Converter topologies for HVDC grids, in:
10.1109/TPWRD.2019.2907607. Dec. Proceedings of the IEEE International Energy Conference (ENERGYCON), Cavtat,
[4] V. Salas, M. Alonso-Abella, E. Olias, F. Chenlo, A. Barrado, DC current injection 2014, pp. 1554–1561, https://doi.org/10.1109/ENERGYCON.2014.6850630.
into the network from PV inverters of <5 kW for low-voltage small grid-connected [28] A. Nami, J. Liang, F. Dijkhuizen, G.D. Demetriades, Modular multilevel converters
PV systems, Sol. Energy Mater. Sol. Cells 91 (9) (2007) 801–806. for HVDC applications: review on converter cells and functionalities, IEEE Trans.
[5] J. Kappenman, Geomagnetic storms and their Impacts on the U.S. power grid. Power Electron. 30 (1) (2015) 18–36, https://doi.org/10.1109/
Metatech Corporation, Meta-R-319, prepared for Oak Ridge National Laboratory TPEL.2014.2327641. Jan.
for the Federal Energy Regulatory Commission (FERC), the U.S. Department of [29] L. Bolduc, M. Granger, G. Pare, J. Saintonge, L. Brophy, Development of a DC
Energy (DOE), and the U.S. Department of Homeland Security (DHS), 2010. current-blocking device for transformer neutrals, IEEE Trans. Power Deliv. 20 (1)
January. (2005) 163–168.
[6] K.P. Schneider, et al., A distributed power system control architecture for improved
distribution system resiliency, IEEE Access 7 (2019) 9957–9970, https://doi.org/
10.1109/ACCESS.2019.2891368. Moazzam Nazir is a PhD student in the Holcombe Department
[7] J. Burkard, J. Biela, Design of a protection concept for a 100-kVA hybrid of Electrical and Computer Engineering at Clemson University.
transformer, IEEE Trans. Power Electron. 35 (4) (2020) 3543–3557, https://doi. He has a bachelor’s and a master’s degree in Electrical Engi­
org/10.1109/TPEL.2019.2936888. April. neering with more than 5 years of work experience in research
[8] K. Deng, J. Cao, P. Guo, X. Xu, Energy saving analysis of harmonic suppression in a organizations and industry pertaining to Electrical and Elec­
distribution network, in: Proceedings of the 4th International Conference on tronics Engineering. He secured the Fulbright PhD scholarship
Networking and Distributed Computing, Los Angeles, CA, 2013, pp. 121–125, from the U.S. Department of State in 2017 and currently pur­
https://doi.org/10.1109/ICNDC.2013.13. suing his research on a Savannah River National Laboratory
[9] L. Gyugyi, Unified power-flow control concept for flexible AC transmission project related to power systems reliability enhancement
systems, IEE Proc. C Gener. Transm. Distrib. 139 (4) (1992) 323–331, https://doi. through protection of transmission and distribution trans­
org/10.1049/ip-c.1992.0048. July. formers against DC currents. His research interests include
[10] N. Johansson, L. Angquist, H. Nee, An adaptive controller for power system power systems protection, renewable technologies, power
stability improvement and power flow control by means of a thyristor switched converters and control systems.
series capacitor (TSSC), IEEE Trans. Power Syst. 25 (1) (2010) 381–391, https://
doi.org/10.1109/TPWRS.2009.2036484. Feb.
[11] L.F.W. de Souza, E.H. Watanabe, J.E. da Rocha Alves, Thyristor and gate-controlled
series capacitors: a comparison of components rating, IEEE Trans. Power Deliv. 23 Klaehn Burkes is a Senior Engineer in the Cybersecurity Pro­
(2) (2008) 899–906, https://doi.org/10.1109/TPWRD.2008.917941. April. grams group in the Digital Transformation Directorate at
[12] D. Das, D.M. Divan, R.G. Harley, Power flow control in networks using controllable Savannah River National Laboratory. He received a B.S. degree
network transformers, IEEE Trans. Power Electron. 25 (7) (2010) 1753–1760, in electrical engineering and a M.S. degree in power systems
https://doi.org/10.1109/TPEL.2010.2042076. July. from Clemson University, Clemson, SC, USA, in 2012 and 2014
[13] R.P. Kandula, et al., Field test results for a 3-phase 12.47 kV 1 MVA power router, respectively. His current research interests include industrial
in: Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE), control systems, defense critical infrastructure, solid state
Milwaukee, WI, 2016, pp. 1–8, https://doi.org/10.1109/ECCE.2016.7855115. technologies, large power equipment testing, Electric Grid/
[14] M.J. Mauger, P. Kandula, F. Lambert, D. Divan, Grounded controllable network Petroleum SCADA Cybersecurity, and data acquisition.
transformer for cost-effective grid control, in: Proceedings of the IEEE Energy
Conversion Congress and Exposition (ECCE), Portland, OR, 2018, pp. 3732–3739,
https://doi.org/10.1109/ECCE.2018.8557956.
[15] M. Nazir, K. Burkes, J.H.R. Enslin, Converter-based power system protection
against DC in transmission and distribution networks, IEEE Trans. Power Electron.
35 (7) (2020) 6701–6704, https://doi.org/10.1109/TPEL.2019.2963313. July.
[16] M. Nazir, K. Burkes, J. Enslin, Converter-based solutions: opening new avenues of
power system protection against Solar and HEMP MHD-E3 GIC, IEEE Trans. Power Dr. Johan H Enslin (M’85; SM’92; F’12) is the Duke Energy
Deliv. (2022), https://doi.org/10.1109/TPWRD.2020.3016207. Endowed Chaired Professor in Smart Grid at Clemson Univer­
[17] M. Nazir, J.H. Enslin, Hybrid smart converter transformer for HVDC with advanced sity in North Charleston SC, USA and Executive Director for the
grid support, in: Proceedings of the 5th IEEE Workshop on the Electronic Grid Energy Systems Program at the Zucker Family Graduate Edu­
(eGRID), 2020, pp. 1–8, https://doi.org/10.1109/eGRID48559.2020.9330631. cation Center. Enslin has combined a 39-year career with
[18] Assessment of Large Power Transformer Risk Mitigation Strategies.-A Report leadership in industry and academia, in the US, Europe and
Prepared for the Office of Energy Policy and System Analysis, U.S. Department of South Africa. He served as a senior executive for private busi­
Energy, 2022 [Online]. ness operations and a professor in electrical engineering. He
[19] F. Xiao, L. Dong, L. Li, X. Liao, A frequency-fixed SOGI-based PLL for single-phase received the BS, MS and PhD degrees in Electrical and Elec­
grid-connected converters, IEEE Trans. Power Electron. 32 (3) (2017) 1713–1719, tronic Engineering from the Rand Afrikaans University (RAU),
https://doi.org/10.1109/TPEL.2016.2606623. March. South Africa, in 1981, 1983 and 1988 respectively. He is a
[20] IEEE standard for interconnection and interoperability of distributed energy registered Professional Engineer in South Africa, Fellow of the
resources with associated electric power systems interfaces," in IEEE Std 1547- SAIEE and Fellow of the IEEE.
2018 (Revision of IEEE Std 1547-2003), pp.1–138, 6 April 2018, doi: 10.1109/
IEEESTD.2018.8332112.

13

You might also like