Professional Documents
Culture Documents
1 s2.0 S2772671122000729 Main
1 s2.0 S2772671122000729 Main
A R T I C L E I N F O A B S T R A C T
Keywords: The flow of quasi-DC or DC in AC networks may trigger half-cycle saturation of electrical grid transformers that
DC-AC power conversion could lead to their internal heating or grid collapse. Apart from the requirement of DC mitigation measures, the
Impedance balancing conversion of conventional power grid into an intricate network demands the need for power equipment with
Power converter
dynamic control capability. The transformers provide the most strategic point in the grid for the introduction of
Power quality
Voltage control
DC protection and grid-support features. This paper proposes a fractionally rated power-electronics module
coupled to neutral and ground terminals of conventional transformers that delivers efficient power network
protection against quasi-DC or DC flow with different advanced grid-support features injected on the transformer
primary. The proposed concept is validated on an experimental hardware prototype employing power hardware-
in-the-loop (P-HIL) configuration of Typhoon HIL-402 and compared with the simulation results in this paper.
Also, a transformer and associated module protection approach employing a hybrid bypass switch has been
suggested and experimentally validated in this work. The experimental results validate the capability of the
module to counter DC injection, perform harmonics mitigation, voltage control or unbalance compensation,
impedance matching and power flow control at the same injection point.
* Corresponding author.
E-mail address: mnazir@clemson.edu (M. Nazir).
https://doi.org/10.1016/j.prime.2022.100101
Received 12 October 2022; Received in revised form 21 November 2022; Accepted 17 December 2022
Available online 21 December 2022
2772-6711/© 2022 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-
nc-nd/4.0/).
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Table 1
Prime Features of exisitng solutions and proposed approach [14].
HVDC Light UPFC FR-BTB G-CDPAR G-CNT Proposed scheme
Transformer 2 fully rated, 2 fractionally rated, 1 fractional rating, 1 fully rated, standard 1 fully rated, standard 1 fully rated, standard
count & rating standard design custom design standard design design design design
Converter type & VSC B2B, fully VSC B2B, fractional VSC B2B, fractional AC chopper, fractional VSC B2B, fractional AC chopper, fractionally
rating rated rating rating rating rating rated
BIL management Handled by Challenging, relies on Challenging, converter Handled by standard Handled by standard Handled by standard
standard series transformer floating at the line transformer, converter at transformer, converter at transformer, converter at
transformer design voltage ground level ground level ground level
Cooling Active, deionized Active, forced air Forced air or Forced air or combined Forced air or combined Forced air or combined
water combined with with transformer cooling with transformer cooling with transformer cooling
transformer cooling
System ~95% ~99% ~99% ~99% ~99% ~99%
efficiency
DC mitigation/ No No No No No Yes
isolation
Voltage scaling Yes No No Yes Yes Yes
Power flow Complete and Independent PQ Independent PQ Optimized for P or Q Independent PQ control Independent PQ control
control independent PQ control around base control around base control around base around base power flow around base power flow
capability control power flow power flow power flow
Fail normal No Yes - large stress on Yes Yes Yes Yes
series transformer
Line unbalance Yes No No No Yes Yes
management
Scaling Yes BIL management BIL management BIL management limits Yes Yes
limits scalability impairs scalability scalability
Cost Highest Higher Lower Lowest Lower Lower
capacitor (TCSC) [11], controllable network transformer (CNT) [12], transformer that hinders its applicability to the existing two-winding
fractionally rated back-to-back (FR-BTB) converter and compact dy transmission transformers. Moreover, the above discussed FACTS de
namic phase angle regulator (CDPAR) [13,14]. vices do not block quasi-DC or DC flow in AC power networks.
Accordingly, proper grid operation stays at risk even after the installa
tion of these power-electronics based devices. Apart from the
1.3. Research gaps above-mentioned devices, the solid-state transformers (SSTs) also pro
vide an alternate to address some of the above discussed issues. How
Most of the above discussed device’s float near the line voltage that ever, they are still far from the complete replacement of traditional
raises isolation challenges [13]. This question was addressed in the transformers due to the comparative shorter life span and robustness.
grounded controllable network transformer (G-CNT) scheme discussed Moreover, there has been a significant investment on the already
in [14], that employs a three-winding transformer with its tertiary installed conventional transformers with their substitution accompanied
winding coupled to a marginally rated converter that operates near the with massive expenditure and time. In this perspective, strategies that
ground potential. But this approach necessitates a special triple-winding
Fig. 1. (a) DC elimination and grid-support approach, (b) DC link voltage control.
2
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
3
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
The controller proposed for the DC mitigation and grid-support injected between the transformer neutral and substation ground, as can
scheme that generates the pulse width modulation (PWM) set point is be seen in Fig. 3. This effectively retains the transformer primary
shown in Fig. 3. The proposed controller is explained in detail in the winding voltage (Vxmfr), shown in Fig. 2, at its desired value.
subsequent sections.
2.3. Power flow control
2.1. DC mitigation
The active (P) and reactive (Q) power flow between PCC and
The prime aspect of the device is its capability to perform DC miti transformer primary shown in Fig. 2 is given as:
⃒ ⃒ (
gation or prevention of power network harmonics from travelling to 3|VPCC |⃒Vxmfr,eq ⃒sin δPCC − δxmfr,eq
)
wards the downstream of the module-integrated transformer. This P= (1)
Zxmfr
objective is achieved by measuring the voltage at VPCC and isolating its
harmonic content (Vh) from the fundamental component (V1) employ ( ⃒ ⃒ ( )
3 |VPCC |2 − |VPCC |⃒Vxmfr,eq ⃒cos δPCC − δxmfr,eq
ing a SOGI-based PLL, that are frequently utilized for synchronization of Q= (2)
single-phase grid-connected converters [19]. This unwanted signal (Vh) Zxmfr
is further introduced between the transformer neutral terminal and
Where, Vxmfr,eq is the sum of transformer and converter voltage, δPCC
ground that ensures the voltage at the transformer primary terminals
and δxmfr,eq are the angles of VPCC and Vxmfr,eq respectively. The pro
(Vxmfr) is always harmonic free. This DC mitigation control branch can
posed strategy offers separate control over the converter voltage and
be seen in Fig. 3.
angle, therefore, Vxmfr,eq and δxmfr,eq could be adjusted individually. This
provides separate control over the active and reactive power. The
2.2. Voltage regulation implementation of this control fuction is shown in Fig. 3.
4
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
5
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Fig. 6. Proposed strategy simulation under harmonics injection for scaled prototype; Top subplot shows voltage (VPCC) and current (Iprim) on HST primary, second
subplot shows HST load voltage (Vload), third subplot shows harmonic content in HST primary voltage (Vh) and compensation signal generated by proposed module
(Vconv), bottom subplot shows DC link voltage (VDC,link).
Fig. 7. Proposed strategy simulation under grid voltage sag for scaled prototype; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load
voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).
4. Scaled prototype simulation results scheme for a scaled prototype. In the next section, P-HIL results from an
actual hardware protype are presented and discussed. Finally, the
A simulation model was created for the laboratory scale hardware simulation and hardware results are compared and discussed in the
prototype whose results will be presented and compared with the actual subsequent section.
hardware prototype. First, the DC mitigation performance of the pro
posed device is evaluated by injecting DC and entering the TUT into half- 5. Experimental results
cycle saturation. Later, module is activated that effectively counters the
injected DC and returns the transformer to its normal operation as The different scenarios that a real utility transformer can experience
shown in Fig. 6. A simulation of the proposed scheme is also performed are created and proposed module is assessed against tackling these is
for the case of a voltage sag that is generated by reducing the source sues [2–6,8]. The experimental results are presented under respective
voltage to 0.85pu. Later, the module is activated to restore the load scenario.
voltage to its nominal value as shown in Fig. 7. These two simulation
results are discussed here to show the effectiveness of the proposed
6
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Fig. 8. Proposed strategy evaluation under harmonics injection; Top subplot shows voltage (VPCC) and current (Iprim) on HST primary, second subplot shows HST
load voltage (Vload), third subplot shows harmonic content in HST primary voltage (Vh) and compensation signal generated by proposed module (Vconv), bottom
subplot shows DC link voltage (VDC,link).
and its output effectively follows harmonics in the VPCC. This leads to
Table 3
isolation of harmonics from moving towards the load side. This facili
THD of load voltage for different operation scenarios.
tates to prevent transformer half-cycle saturation during flow of DC in
Normal operation DC injection DC injection compensation power networks. It is pertinent to mention that harmonics (Vh) during
3.5% 13% 1% normal operation of the transformer in Fig. 8 are preexistent in the grid
voltage that represent a non-ideal source. The THD of the load voltage
for the three regions of operation in Fig. 8 is shown in Table 3.
5.1. DC mitigation This DC mitigation ability of the proposed module is greatly desir
able under the present scenario of exponential addition of power
To evaluate DC mitigation capability of the proposed module, the electronics-based generation resources and loads that lead to unabated
installed DC power supply is employed to force TUT into half-cycle injection of harmonics to the grid.
saturation by mimicking the previously discussed DC injection sce
narios. This mode leads to increased harmonics on each side of the
transformer as depicted in Fig. 8. Afterwards, the module is triggered,
Fig. 9. Proposed strategy performance under grid voltage sag; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load voltage (Vload),
third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).
7
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Fig. 10. Proposed strategy performance under grid voltage swell; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load voltage
(Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).
Fig. 11. Utilization of proposed strategy to increase power flow across TUT; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load
voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).
5.2. Voltage regulation autotransformers endure rapid switching. This induces significant
deterioration and undesirable control action delays compromising grid
Now, the voltage regulation ability of the module is assessed. The reliability. In this situation, the module could provide rapid and grainy
objective, in this case, is to control the load voltage regardless of voltage grid voltage control. Also, the implementation of the proposed module
dips or surges on the grid. To simulate a voltage dip on the grid, the on a per-phase basis allows its utilization for grid unbalance mitigation
variac output connected to primary of TUT is reduced to 0.85pu. Next, [16]. Moreover, the voltage control feature of the suggested module
the module is actuated and result for this case is displayed in Fig. 9. The could be utilized to satisfy IEEE 1547-2018 by providing VRT services to
module successfully controls the load voltage to its normal value. Also, a DERs [20]. This objective could be achieved by operating the proposed
voltage swell is created by increasing the variac output that is followed device as a STATCOM. The more details regarding this feature of the
by voltage regulation by the proposed module. The result for this case is proposed device can be found in [21].
presented in Fig. 10, where the voltage control ability of the proposed
module is verified. This voltage control ability is extremely valuable for
the power networks due to rapid addition of volatile renewable energy 5.3. Power flow control
sources. The unpredictable renewable generation causes taps of
To depict the power flow management capability introduced by the
8
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Fig. 12. Utilization of proposed strategy to decrease power flow across TUT; Top subplot shows voltage on HST primary (VPCC), second subplot shows HST load
voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).
Fig. 13. Impedance control aspect of the proposed module; Top subplot shows voltage across external impedance added to transformer primary (Vz), second subplot
shows HST load voltage (Vload), third subplot shows compensation signal generated by proposed module (Vconv), bottom subplot shows DC link voltage (VDC,link).
9
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
10
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
11
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Fig. 16. Proposed protection scheme performance under a temporary ground fault during DC mitigation; Top subplot shows current on HST primary (Iprim), second
subplot shows HST load voltage (Vload), third subplot shows harmonics in HST primary voltage (Vharmonics) and compensation signal generated by proposed
module (Vconv), fourth subplot shows module output current (Iinv,op), fifth subplot shows DC link voltage (VDC,link), bottom subplot shows switching sequence of
solid state and mechanical switch.
Fig. 17. Proposed protection scheme performance under a temporary ground fault during voltage regulation; Top subplot shows voltage on HST primary (VPCC),
second subplot shows HST load voltage (Vload) and compensation signal generated by proposed module (Vconv), third subplot shows module output current (Iinv,
op), fourth subplot shows DC link voltage (VDC,link), bottom subplot shows switching sequence of solid state and mechanical switch.
The authors declare that they have no known competing financial No data was used for the research described in the article.
interests or personal relationships that could have appeared to influence
the work reported in this paper.
Acknowledgments
12
M. Nazir et al. e-Prime - Advances in Electrical Engineering, Electronics and Energy 3 (2023) 100101
Development (LDRD) program within the Savannah River National [21] M. Nazir, J.H. Enslin, Converter-based intelligent transformer for enhanced grid
monitoring and control, in: Proceedings of the 5th IEEE Workshop on the
Laboratory (SRNL). This document was prepared in conjunction with
Electronic Grid (eGRID), Aachen, Germany, 2020, pp. 1–6, https://doi.org/
work accomplished under Contract No. DE-AC09-08SR22470 with the 10.1109/eGRID48559.2020.9330675.
U.S. Department of Energy (DOE) Office of Environmental Management [22] Benefits of Using Mobile Transformers and Mobile Substations for Rapidly
(EM). Restoring Electrical Service,” A Report to the United States Congress pursuant to
Section 1816 of the Energy Policy Act of 2005, U.S. Department of Energy, 2006.
August[Online].
References [23] A.Q. Huang, Q. Zhu, L. Wang, L. Zhang, 15 kV SiC MOSFET: an enabling
technology for medium voltage solid state transformers, CPSS Trans. Power
[1] EMP Task force Work Plan July 2019, "Overview of objectives and key Electron. Appl. 2 (2) (2017) 118–130, https://doi.org/10.24295/
deliverables," Accessed on: December 03, 2020. [Online]. Available: https://www. CPSSTPEA.2017.00012.
nerc.com/pa/Stand/EMPTaskForceDL/Workshop_Presentations_July_25_2019.pdf. [24] L. Cheng, et al., 15 kV, large area (1 cm2), 4H-SiC p-type gate turnoffthyristors,
[2] Hearing of the U.S. Senate Homeland Security and Governmental Affairs Mater. Sci. Forum 740–742 (2013) 978–981. Jan.
Committee February 2019, "Perspectives on protecting the electric grid from an [25] L. Cheng, et al., 20 kV, 2 cm2, 4H-SiC gate turn-off thyristors for advanced pulsed
electromagnetic pulse or geomagnetic disturbance," Accessed on: December 03, power applications, in: Proceedings of the 19th IEEE Pulsed Power Conference
2020. [Online]. Available: https://www.hsgac.senate.gov/imo/media/doc/Tes (PPC), San Francisco, CA, USA, 2013, pp. 1–4. Jun.
timony-Horton-2019-02-27.pdf. [26] E. V. Brunt et al., "22 kV, 1 cm2, 4H-SiC n-IGBTs with improved conductivity
[3] M. Yang, D. Deswal, F. de Leόn, Mitigation of half-cycle saturation of adjacent modulation," 2014 IEEE 26th International Symposium on Power Semiconductor
transformers during HVDC monopolar operation—part i: mitigation principle and Devices & IC’s (ISPSD), 2014, pp. 358-361, doi: 10.1109/ISPSD.2014.6856050.
device design, IEEE Trans. Power Deliv. 34 (6) (2019) 2232–2239, https://doi.org/ [27] S. Norrga, Xiaoqian Li, L. Ängquist, Converter topologies for HVDC grids, in:
10.1109/TPWRD.2019.2907607. Dec. Proceedings of the IEEE International Energy Conference (ENERGYCON), Cavtat,
[4] V. Salas, M. Alonso-Abella, E. Olias, F. Chenlo, A. Barrado, DC current injection 2014, pp. 1554–1561, https://doi.org/10.1109/ENERGYCON.2014.6850630.
into the network from PV inverters of <5 kW for low-voltage small grid-connected [28] A. Nami, J. Liang, F. Dijkhuizen, G.D. Demetriades, Modular multilevel converters
PV systems, Sol. Energy Mater. Sol. Cells 91 (9) (2007) 801–806. for HVDC applications: review on converter cells and functionalities, IEEE Trans.
[5] J. Kappenman, Geomagnetic storms and their Impacts on the U.S. power grid. Power Electron. 30 (1) (2015) 18–36, https://doi.org/10.1109/
Metatech Corporation, Meta-R-319, prepared for Oak Ridge National Laboratory TPEL.2014.2327641. Jan.
for the Federal Energy Regulatory Commission (FERC), the U.S. Department of [29] L. Bolduc, M. Granger, G. Pare, J. Saintonge, L. Brophy, Development of a DC
Energy (DOE), and the U.S. Department of Homeland Security (DHS), 2010. current-blocking device for transformer neutrals, IEEE Trans. Power Deliv. 20 (1)
January. (2005) 163–168.
[6] K.P. Schneider, et al., A distributed power system control architecture for improved
distribution system resiliency, IEEE Access 7 (2019) 9957–9970, https://doi.org/
10.1109/ACCESS.2019.2891368. Moazzam Nazir is a PhD student in the Holcombe Department
[7] J. Burkard, J. Biela, Design of a protection concept for a 100-kVA hybrid of Electrical and Computer Engineering at Clemson University.
transformer, IEEE Trans. Power Electron. 35 (4) (2020) 3543–3557, https://doi. He has a bachelor’s and a master’s degree in Electrical Engi
org/10.1109/TPEL.2019.2936888. April. neering with more than 5 years of work experience in research
[8] K. Deng, J. Cao, P. Guo, X. Xu, Energy saving analysis of harmonic suppression in a organizations and industry pertaining to Electrical and Elec
distribution network, in: Proceedings of the 4th International Conference on tronics Engineering. He secured the Fulbright PhD scholarship
Networking and Distributed Computing, Los Angeles, CA, 2013, pp. 121–125, from the U.S. Department of State in 2017 and currently pur
https://doi.org/10.1109/ICNDC.2013.13. suing his research on a Savannah River National Laboratory
[9] L. Gyugyi, Unified power-flow control concept for flexible AC transmission project related to power systems reliability enhancement
systems, IEE Proc. C Gener. Transm. Distrib. 139 (4) (1992) 323–331, https://doi. through protection of transmission and distribution trans
org/10.1049/ip-c.1992.0048. July. formers against DC currents. His research interests include
[10] N. Johansson, L. Angquist, H. Nee, An adaptive controller for power system power systems protection, renewable technologies, power
stability improvement and power flow control by means of a thyristor switched converters and control systems.
series capacitor (TSSC), IEEE Trans. Power Syst. 25 (1) (2010) 381–391, https://
doi.org/10.1109/TPWRS.2009.2036484. Feb.
[11] L.F.W. de Souza, E.H. Watanabe, J.E. da Rocha Alves, Thyristor and gate-controlled
series capacitors: a comparison of components rating, IEEE Trans. Power Deliv. 23 Klaehn Burkes is a Senior Engineer in the Cybersecurity Pro
(2) (2008) 899–906, https://doi.org/10.1109/TPWRD.2008.917941. April. grams group in the Digital Transformation Directorate at
[12] D. Das, D.M. Divan, R.G. Harley, Power flow control in networks using controllable Savannah River National Laboratory. He received a B.S. degree
network transformers, IEEE Trans. Power Electron. 25 (7) (2010) 1753–1760, in electrical engineering and a M.S. degree in power systems
https://doi.org/10.1109/TPEL.2010.2042076. July. from Clemson University, Clemson, SC, USA, in 2012 and 2014
[13] R.P. Kandula, et al., Field test results for a 3-phase 12.47 kV 1 MVA power router, respectively. His current research interests include industrial
in: Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE), control systems, defense critical infrastructure, solid state
Milwaukee, WI, 2016, pp. 1–8, https://doi.org/10.1109/ECCE.2016.7855115. technologies, large power equipment testing, Electric Grid/
[14] M.J. Mauger, P. Kandula, F. Lambert, D. Divan, Grounded controllable network Petroleum SCADA Cybersecurity, and data acquisition.
transformer for cost-effective grid control, in: Proceedings of the IEEE Energy
Conversion Congress and Exposition (ECCE), Portland, OR, 2018, pp. 3732–3739,
https://doi.org/10.1109/ECCE.2018.8557956.
[15] M. Nazir, K. Burkes, J.H.R. Enslin, Converter-based power system protection
against DC in transmission and distribution networks, IEEE Trans. Power Electron.
35 (7) (2020) 6701–6704, https://doi.org/10.1109/TPEL.2019.2963313. July.
[16] M. Nazir, K. Burkes, J. Enslin, Converter-based solutions: opening new avenues of
power system protection against Solar and HEMP MHD-E3 GIC, IEEE Trans. Power Dr. Johan H Enslin (M’85; SM’92; F’12) is the Duke Energy
Deliv. (2022), https://doi.org/10.1109/TPWRD.2020.3016207. Endowed Chaired Professor in Smart Grid at Clemson Univer
[17] M. Nazir, J.H. Enslin, Hybrid smart converter transformer for HVDC with advanced sity in North Charleston SC, USA and Executive Director for the
grid support, in: Proceedings of the 5th IEEE Workshop on the Electronic Grid Energy Systems Program at the Zucker Family Graduate Edu
(eGRID), 2020, pp. 1–8, https://doi.org/10.1109/eGRID48559.2020.9330631. cation Center. Enslin has combined a 39-year career with
[18] Assessment of Large Power Transformer Risk Mitigation Strategies.-A Report leadership in industry and academia, in the US, Europe and
Prepared for the Office of Energy Policy and System Analysis, U.S. Department of South Africa. He served as a senior executive for private busi
Energy, 2022 [Online]. ness operations and a professor in electrical engineering. He
[19] F. Xiao, L. Dong, L. Li, X. Liao, A frequency-fixed SOGI-based PLL for single-phase received the BS, MS and PhD degrees in Electrical and Elec
grid-connected converters, IEEE Trans. Power Electron. 32 (3) (2017) 1713–1719, tronic Engineering from the Rand Afrikaans University (RAU),
https://doi.org/10.1109/TPEL.2016.2606623. March. South Africa, in 1981, 1983 and 1988 respectively. He is a
[20] IEEE standard for interconnection and interoperability of distributed energy registered Professional Engineer in South Africa, Fellow of the
resources with associated electric power systems interfaces," in IEEE Std 1547- SAIEE and Fellow of the IEEE.
2018 (Revision of IEEE Std 1547-2003), pp.1–138, 6 April 2018, doi: 10.1109/
IEEESTD.2018.8332112.
13