You are on page 1of 8

SWITCHING SHEET

DARWIN INTERNATIONAL AIRPORT

Switching Sheet Number 001

1. Location:
Equipment to be isolated
Voltage:

2. Reason for Isolation

3. Special Precautions

4. Work to be carried out

Isolations will be

Reference Drawing Number

Start Date Completion Date

Start Time Completion Time

Switching Operator Name: Signature Date

Switching Operators Assistant Name: Signature Date

Written by Name: Signature Date

Checked by Name: Signature Date

Approved (SHVO) Name: Signature Date

Switching Sheet Number 001

Step Location on Plant Isolation Point description Operation Isolated By Checked By


No Time & Initial Time & Initial

1.

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 1 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

2.

3.

4.

5.

6. DPS HV SWITCH VT’s 00AEA01CE301 and CONFIRM OPEN


YARD 00AEA02CE301 OPEN CIRCUITS IN PLACE
BAY 00AEA01 CIRCUITS
BAY 00AEA02

7. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV OPEN EARTHING


MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH SWITCH LOCALLY
LINE 1 INCOMER BAY 00AEA01GS603 AND SELECT TO
00AEA01 OFF POSITION

8. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV CONFIRM


MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH EARTHING SWITCH
LINE 1 INCOMER BAY 00AEA01GS603 IS OPEN
00AEA01

9. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV PULL MECHANICAL


MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH INTERLOCKING
LINE 1 INCOMER BAY 00AEA01GS603 LEVER AND INSERT
00AEA01 MECHANICAL
INTERLOCKING
DEVICE

10. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH MECHANICAL
LINE 1 INCOMER BAY 00AEA01GS603 INTERLOCKING
00AEA01 DEVICE IN PLACE

11. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV OPEN EARTHING
MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH SWITCH LOCALLY
LINE 2 INCOMER BAY 00AEA02GS603 AND SELECT TO
00AEA02 OFF POSITION

12. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV CONFIRM


MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH EARTHING SWITCH
LINE 2 INCOMER BAY 00AEA02GS603 IS OPEN

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 2 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

13. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH INTERLOCKING
LINE 2 INCOMER BAY 00AEA02GS603 LEVER AND INSERT
00AEA02 MECHANICAL
INTERLOCKING
DEVICE

14. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH MECHANICAL
LINE 2 INCOMER BAY 00AEA02GS603 INTERLOCKING
00AEA02 DEVICE IN PLACE

15. DPS HV SWITCH YARD BAY 00AEA03 132KV STEP UP CONFIRM CB OPEN
BAY 00AEA03 TRF CB 10BAT20GS101

16. DPS HV SWITCH YARD BAY 00AEA04 132KV STEP UP CONFIRM CB OPEN
BAY 00AEA04 TRF CB 10BAT10GS101

17. DPS HV SWITCH YARD BAY 00AEA05 132KV STEP UP CONFIRM CB OPEN
BAY 00AEA05 TRF CB 10BAT30GS101

18. DPS HV SWITCH YARD BAY 00AEA06 132KV STEP UP CONFIRM CB OPEN
BAY 00AEA06 TRF CB 20BAT20GS101

19. DPS HV SWITCH YARD BAY 00AEA07 132KV STEP UP CONFIRM CB OPEN
BAY 00AEA07 TRF CB 20BAT10GS101

20. DPS HV SWITCH YARD BAY 00AEA08 132KV STEP UP CONFIRM CB OPEN
BAY 00AEA08 TRF CB 20BAT30GS101

21. DPS HV SWITCH YARD 132KV OHL 1 BUS BAR A CLOSE EARTHING
00 BUS BAR A EARTHING SWITCH SWITCH LOCALLY
00AEA10 00AEA10GS601 AND SELECT TO
OFF POSITION

22. DPS HV SWITCH YARD 132KV OHL 1 BUS BAR A CONFIRM


BUS BAR A EARTHING SWITCH EARTHING SWITCH
00AEA10 00AEA10GS601 IS CLOSED

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 3 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

23. DPS HV SWITCH YARD 132KV OHL 1 BUS BAR A PULL MECHANICAL
BUS BAR A EARTHING SWITCH INTERLOCKING
00AEA10 00AEA10GS601 LEVER AND INSERT
MECHANICAL
INTERLOCKING
DEVICE

24. DPS HV SWITCH YARD 132KV OHL 1 BUS BAR A LOCK AND TAG
BUS BAR A EARTHING SWITCH MECHANICAL
00AEA10 00AEA10GS601 INTERLOCKING
DEVICE IN PLACE

25. DPS HV SWITCH YARD 132KV OHL 2 BUS BAR B CLOSE EARTHING
BUS BAR B EARTHING SWITCH SWITCH LOCALLY
00AEA20 00AEA20GS601 AND SELECT TO
OFF POSITION

26. DPS HV SWITCH YARD 132KV OHL 2 BUS BAR B CONFIRM


BUS BAR B EARTHING SWITCH EARTHING SWITCH
00AEA20 00AEA20GS601 IS CLOSED

27. DPS HV SWITCH YARD 132KV OHL 2 BUS BAR B PULL MECHANICAL
BUS BAR B EARTHING SWITCH INTERLOCKING
00AEA20 00AEA20GS601 LEVER AND INSERT
MECHANICAL
INTERLOCKING
DEVICE

28. DPS HV SWITCH YARD 132KV OHL 2 BUS BAR B LOCK AND TAG
BUS BAR B EARTHING SWITCH MECHANICAL
00AEA20 00AEA20GS601 INTERLOCKING
DEVICE IN PLACE

29. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV OPEN


MOUNT ISA OVER HEAD OHL 1 BUS BAR A DISCONNECTOR
LINE 1 INCOMER BAY DISCONNECTOR LOCALLY AND
00AEA01 00AEA01GS201 SELECT TO OFF
POSITION
30. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV CONFIRM
MOUNT ISA OVER HEAD OHL 1 BUS BAR A DISCONNECTOR IS
LINE 1 INCOMER BAY DISCONNECTOR OPEN
00AEA01 00AEA01GS201

31. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 1 BUS BAR A INTERLOCKING
LINE 1 INCOMER BAY DISCONNECTOR LEVER AND INSERT
00AEA01 00AEA01GS201 MECHANICAL
INTERLOCKING
DEVICE

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 4 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

32. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 1 BUS BAR A MECHANICAL
LINE 1 INCOMER BAY DISCONNECTOR INTERLOCKING
00AEA01 00AEA01GS201 DEVICE IN PLACE

33. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV OPEN


MOUNT ISA OVER HEAD OHL 2 BUS BAR B DISCONNECTOR
LINE 2 INCOMER BAY DISCONNECTOR LOCALLY AND
00AEA02 00AEA02GS202 SELECT TO OFF
POSITION
34. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV CONFIRM
MOUNT ISA OVER HEAD OHL 2 BUS BAR B DISCONNECTOR IS
LINE 2 INCOMER BAY DISCONNECTOR OPEN
00AEA02 00AEA02GS202

35. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 2 BUS BAR B INTERLOCKING
LINE 2 INCOMER BAY DISCONNECTOR LEVER AND INSERT
00AEA02 00AEA02GS202 MECHANICAL
INTERLOCKING
DEVICE

36. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 2 BUS BAR B MECHANICAL
LINE 2 INCOMER BAY DISCONNECTOR INTERLOCKING
00AEA02 00AEA02GS202 DEVICE IN PLACE

37. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV CLOSE EARTHING
MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH SWITCH LOCALLY
LINE 1 INCOMER BAY 00AEA01GS601 AND SELECT TO
00AEA01 OFF POSITION

38. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV CONFIRM


MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH EARTHING SWITCH
LINE 1 INCOMER BAY 00AEA01GS601 IS CLOSED
00AEA01

39. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH INTERLOCKING
LINE 1 INCOMER BAY 00AEA01GS601 LEVER AND INSERT
00AEA01 MECHANICAL
INTERLOCKING
DEVICE

40. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 1 EARTHING SWITCH MECHANICAL
LINE 1 INCOMER BAY 00AEA01GS601 INTERLOCKING
00AEA01 DEVICE IN PLACE

41. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV CLOSE EARTHING
MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH SWITCH LOCALLY
LINE 2 INCOMER BAY 00AEA02GS601 AND SELECT TO
00AEA02 OFF POSITION

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 5 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

42. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV CONFIRM


MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH EARTHING SWITCH
LINE 2 INCOMER BAY 00AEA02GS601 IS CLOSED
00AEA02

43. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH INTERLOCKING
LINE 2 INCOMER BAY 00AEA02GS601 LEVER AND INSERT
00AEA02 MECHANICAL
INTERLOCKING
DEVICE

44. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 2 EARTHING SWITCH MECHANICAL
LINE 2 INCOMER BAY 00AEA02GS601 INTERLOCKING
00AEA02 DEVICE IN PLACE

45. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV CLOSE


MOUNT ISA OVER HEAD OHL 1 LINE DISCONNECTOR DISCONNECTOR
LINE 1 INCOMER BAY 00AEA01GS203 LOCALLY AND
00AEA01 SELECT TO OFF
POSITION
46. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV CONFIRM
MOUNT ISA OVER HEAD OHL 1 LINE DISCONNECTOR DISCONNECTOR IS
LINE 1 INCOMER BAY 00AEA01GS203 CLOSED
00AEA01

47. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 1 LINE DISCONNECTOR INTERLOCKING
LINE 1 INCOMER BAY 00AEA01GS203 LEVER AND INSERT
00AEA01 MECHANICAL
INTERLOCKING
DEVICE

48. DPS HV SWITCH YARD INCOMER BAY 00AEA01 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 1 LINE DISCONNECTOR MECHANICAL
LINE 1 INCOMER BAY 00AEA01GS203 INTERLOCKING
00AEA01 DEVICE IN PLACE

49. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV CLOSE


MOUNT ISA OVER HEAD OHL 2 LINE DISCONNECTOR DISCONNECTOR
LINE 2 INCOMER BAY 00AEA02GS203 LOCALLY AND
00AEA02 SELECT TO OFF
POSITION
50. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV CONFIRM
MOUNT ISA OVER HEAD OHL 2 LINE DISCONNECTOR DISCONNECTOR IS
LINE 2 INCOMER BAY 00AEA02GS203 CLOSED
00AEA02

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 6 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

51. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV PULL MECHANICAL
MOUNT ISA OVER HEAD OHL 2 LINE DISCONNECTOR INTERLOCKING
LINE 2 INCOMER BAY 00AEA02GS203 LEVER AND INSERT
00AEA02 MECHANICAL
INTERLOCKING
DEVICE

52. DPS HV SWITCH YARD INCOMER BAY 00AEA02 132KV LOCK AND TAG
MOUNT ISA OVER HEAD OHL 2 LINE DISCONNECTOR MECHANICAL
LINE 2 INCOMER BAY 00AEA02GS203 INTERLOCKING
00AEA02 DEVICE IN PLACE

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 7 of 8


SWITCHING SHEET
DARWIN INTERNATIONAL AIRPORT

Switching Sheet Number 001

Single Line Diagram:

GENSRV-ENG-1000-FRM-113 Rev1: 13.06.2013 Page 8 of 8