Drafts - Concrete - May 25, 2023
Drafts - Concrete - May 25, 2023
88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Specifier's comments:
1 Anchor Design
1.1 Input data
Anchor type and diameter: HIT-RE 500 V4 + HAS-U 8.8 HDG M20
Return period (service life in years): 50
Item number: 2223914 HAS-U 8.8 HDG M20x260 (element) /
2287553 HIT-RE 500 V4 (adhesive)
Gap filling with Hilti Filling Set M20
Effective embedment depth: hef,act = 150.0 mm (hef,limit = - mm)
Material: 8.8
Evaluation Service Report: ETA 20/0541
Issued I Valid: 9/06/2023 | -
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 20.0 mm
Anchor plate
CBFEM
: lx x ly x t = 463.0 mm x 201.0 mm x 20.0 mm;
Profile: Advance UKC, 152 x 152 x 30; (L x W x T x FT) = 157.6 mm x 152.9 mm x 6.5 mm x 9.4 mm
Base material: 2
cracked concrete, C35/45, fc,cube = 45.00 N/mm ; h = 330.0 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to EOTA TR 029, 5.2.2.6 present.
CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Group anchor ID
3-8
Group anchor ID
3-8
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Group anchor ID
1-8
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
1.5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)
1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates as per current regulations (ETAG 001/Annex C, EOTA
TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor
plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above.
The proof if the rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The anchor resistances used for this design are ONLY valid if the Hilti Filling Set will be installed on the jobsite as per IFU when the Seismic
washer was selected.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!
• The anchor design methods in PROFIS Engineering require rigid anchor plates, as per current regulations (AS 5216:2021, ETAG 001/Annex
C, EOTA TR029 etc.). This means that the anchor plate should be sufficiently rigid to prevent load re-distribution to the anchors due to
elastic/plastic displacements. The user accepts that the anchor plate is considered close to rigid by engineering judgment."
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 150 mm embedment h_ef, M20, Hot dip galvanized, Hammer drilled
installation per ETA 20/0541, with annular gaps filled with Hilti Filling set or any suitable gap solutions
86.5
y
231.5 231.5
4.5 50.5
100.5
3 7
5
1.0
6.0
1
0.5
93.0
x
100.5
4
5.0
2 6
1.0
30.5 9.5
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
2.2 Summary
Description Profile Stiffeners Anchor plate Welds [%]
sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] Hole bearing
[%]
1 ULS ENV 50.27 0.00 42.39 0.00 37.24 0.00 1 16
2.3 Anchor plate classification
Results below are displayed for the decisive load combinations: ULS ENV
Anchor tension forces Equivalent rigid anchor plate (CBFEM) Component-based Finite Element Method
(CBFEM) anchor plate design
Anchor 1 1.594 kN 0.000 kN
Anchor 2 0.000 kN 0.000 kN
Anchor 3 12.569 kN 11.599 kN
Anchor 4 7.683 kN 8.930 kN
Anchor 5 15.904 kN 18.666 kN
Anchor 6 14.082 kN 14.454 kN
Anchor 7 17.795 kN 18.519 kN
Anchor 8 15.879 kN 13.743 kN
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
User accepted to consider the selected anchor plate as rigid by his/her engineering judgement. This means the anchor design guidelines can
be applied.
2.4 Profile/Stiffeners/Plate
Profile and stiffeners are verified at the level of the steel to concrete connection. The connection design does not replace the steel design for
critical cross sections, which should be performed outside of PROFIS Engineering.
Results
Part Load Material sEd [N/mm²] ePl [%] fy [N/mm²] gM0 fy/gM0 elim [%] Status
combination [N/mm²]
Plate ULS ENV S 355 37.24 0.00 355.00 1.00 355.00 5.00 OK
Profile ULS ENV S 355 50.27 0.00 355.00 1.00 355.00 5.00 OK
Profile ULS ENV S 355 31.68 0.00 355.00 1.00 355.00 5.00 OK
Profile ULS ENV S 355 35.06 0.00 355.00 1.00 355.00 5.00 OK
Stiffener0 ULS ENV S 355 42.39 0.00 355.00 1.00 355.00 5.00 OK
Stiffener1 ULS ENV S 355 20.31 0.00 355.00 1.00 355.00 5.00 OK
355.00 N/mm²
0.00 N/mm²
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
5.00%
0.00%
2.4.2 Hole bearing
Decisive load combination: 1 - ULS ENV
Plate hole bearing resistance, EN1993-1 - 8 section 3.6.1:
Equations
k1 ab fu d t
Fb,Rd =
gM2
VEd
Utilization =
Fb,Rd
Variables
k1 ab fu [N/mm²] d [mm] t [mm] gM2
Anchor 1 2.50 0.61 490.00 20.0 20.0 1.25
Anchor 2 2.50 0.56 490.00 20.0 20.0 1.25
Anchor 3 2.50 1.00 490.00 20.0 20.0 1.25
Anchor 4 2.50 1.00 490.00 20.0 20.0 1.25
Anchor 5 2.50 1.00 490.00 20.0 20.0 1.25
Anchor 6 2.50 0.82 490.00 20.0 20.0 1.25
Anchor 7 2.50 0.71 490.00 20.0 20.0 1.25
Anchor 8 2.50 0.53 490.00 20.0 20.0 1.25
Results
VEd [kN] Fb,Rd [kN] Utilization [%] Status
Anchor 1 0.088 238.917 1 OK
Anchor 2 0.099 220.817 1 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
2.5 Welds
Profiles are modeled without taking the corner radius into account. Special rules for welding (e.g. for cold-formed profiles ...) are not taken into
account by the software.
Equations
Results
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilization [%] Utilizationc [%] Status
Member 1-bfl 1 67.98 435.56 352.80 16 6 OK
Member 1-bfl 69.50 435.56 352.80 16 7 OK
Member 1-tfl 1 29.57 435.56 352.80 7 3 OK
Member 1-tfl 35.13 435.56 352.80 9 4 OK
Member 1-w 1 31.03 435.56 352.80 8 4 OK
Member 1-w 28.59 435.56 352.80 7 4 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Equations
Results
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilization [%] Utilizationc [%] Status
Stiffener0 (Anchor 29.83 435.56 352.80 7 5 OK
plate)
Stiffener0 (Anchor 23.36 435.56 352.80 6 4 OK
plate) 1
Stiffener1 (Anchor 17.57 435.56 352.80 5 3 OK
plate)
Stiffener1 (Anchor 19.99 435.56 352.80 5 4 OK
plate) 1
Stiffener0 (Member 55.02 435.56 352.80 13 4 OK
1-tfl 1)
Stiffener0 (Member 55.84 435.56 352.80 13 4 OK
1-tfl 1) 1
Stiffener1 (Member 27.54 435.56 352.80 7 2 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilization [%] Utilizationc [%] Status
1-bfl 1)
Stiffener1 (Member 27.56 435.56 352.80 7 2 OK
1-bfl 1) 1
2.6 Concrete
Decisive load combination: 1 - ULS ENV
According to EN1992-1-1 section 6.7(4), the concrete should have sufficient reinforcement to take into account the tensile forces that develop
due to the fixture attachment. The definition of the reinforcement in the concrete is out of scope of PROFIS Engineering.
0.00 N/mm²
2.6.2 Note: In case no external compression loads are applied to the anchor plate, compressions in concrete under the plate, per
EN1993-1-8 section 6.7 and EN1992-1, are not performed.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
2.8 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
anchor plate may not behave rigid. Please, validate the results with a professional designer and/or structural engineer to ensure suitability
and adequacy for your specific jurisdiction and project requirements.
● The anchor is modeled considering stiffness values determined from load displacement curves tested in an independent laboratory.
Please note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution
results.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
13
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
3 Summary of results
Design of the anchor plate, anchor, welds and other elements are based on CBFEM (component based finite element method) and Eurocode
regulations.
Load combination Max. utilization Status
Anchors ULS ENV 100% OK
Anchor plate ULS ENV 11% OK
Welds ULS ENV 16% OK
Stiffeners ULS ENV 12% OK
Profile ULS ENV 15% OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
14
Hilti PROFIS Engineering 3.0.88
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 25, 2023 (2) (1) Date: 25/10/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
15