Harold Holt Swimming Centre Building Automation System

Technical Specifcation APPENDIX A - BMS Point List

POINT AI AO DI DO HLI New? DESCRIPTION


Rooftop Heating System
Boiler R-1 Rooftop Heating System Boiler
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Boiler 1 HLI 15 Y Modbus High Level Interface
Boiler R-2 Rooftop Heating System Boiler
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Boiler 2 HLI 15 Y Modbus High Level Interface
PHHWP-1 Rooftop Primary Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
PHHWP-2 Rooftop Primary Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
SHHWP-1 Rooftop Secondary Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
SHHWP-2 Rooftop Secondary Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
SAF/RAF Rooftop Heating System Supply/Return Air Fan
SAF High Select 1 Supply Air Fan High Speed Select Command
SAF High Status 1 Supply Air Fan High Speed Run Status
SAF High Fault 1 Supply Air Fan High Speed Fault Status
SAF Low Select 1 Supply Air Fan Low Speed Select Command
SAF Low Status 1 Supply Air Fan Low Speed Run Status
SAF Low Fault 1 Supply Air Fan Low Speed Fault Status
RAF High Select 1 Supply Air Fan High Speed Select Command
RAF High Status 1 Supply Air Fan High Speed Run Status
RAF High Fault 1 Supply Air Fan High Speed Fault Status
RAF Low Select 1 Supply Air Fan Low Speed Select Command
RAF Low Status 1 Supply Air Fan Low Speed Run Status
RAF Low Fault 1 Supply Air Fan Low Speed Fault Status
HHW Valve 1 Heating Water Valve Control
RAP Start/Stop 1 Run Around Heat Recovery Pump Start/Stop Command
RAP Status 1 Run Around Heat Recovery Pump Run Status
OA Damper 1 Outside Air Damper Control
EA Damper 1 Exhaust Air Damper Control
Pool Area Temp 1 Main Pool Area Temperature - return air grille
Pool Area Humidity 1 1 Y Main Pool Area Humidity - return air grille
Pool Area Temp 2 1 Y Main Pool Area Temperature 2 - far end of pool hall
Pool Area Humidity 2 1 Y Main Pool Area Humidity 2 - far end of pool hall
EA Temperature 1 Y Exhaust Air Temperature
SA Temperature 1 Y Supply Air Temperature
SA Humidity 1 Y Supply Air Humidity
Indoor HHW System Rooftop Heating System
Secondary Heating Water System Common Supply Water
SHHW Com Supply Temp 1 Y
Temperature
Secondary Heating Water System Common Return Water
SHHW Com Return Temp 1 1 Y
Temperature - HEX 6
Secondary Heating Water System Common Return Water
SHHW Com Return Temp 2 1 Y
Temperature - SAF/RAF

Building Automation System Technical Specification 1/6


Harold Holt Swimming Centre Building Automation System
Technical Specifcation APPENDIX A - BMS Point List

POINT AI AO DI DO HLI New? DESCRIPTION


HEX-6 Heat Exchanger
Heat Valve 1 Heat Exchanger Heating Valve Control
HHW Entering Temp 1 Y Heating Water Entering Temperature
HHW Leaving Temp 1 Y Heating Water Leaving Temperature
Pool Loop Entering Temp 1 Y Pool Loop Heating Water Entering Temperature
Pool Loop Leaving Temp 1 Y Pool Loop Heating Water Leaving Temperature
Pool Loop Pump Status 1 Y Pool Pump Run Status
Outdoor Heating System
Boiler G-1 Outdoor Heating System Boiler
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Boiler 3 HLI 15 Y Modus High Level Interface
Boiler G-2 Outdoor Heating System Boiler
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Boiler 4 HLI 15 Y Modus High Level Interface
HHWP-1 & VSD Outdoor Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Speed 1 VSD Speed Control
HHWP-2 & VSD Outdoor Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Speed 1 VSD Speed Control
HHWP-3 & VSD Outdoor Heating Water Pump
Start/Stop 1 Start/Stop Command
Status 1 Run Status
Fault 1 Fault Status
Speed 1 VSD Speed Control
Outdoor HHW System Outdoor Heating System
HHW System DP 1 Heating Water System Differential Pressure
HHW Bypass Valve 1 Heating Water System Bypass Valve
HHW Supply Temp 1 Y Heating Water System Supply Water Temperature
HHW Return Temp 1 Y Heating Water System Return Water Temperature
HHW System DP 1 Y Heating Water System Differential Pressure - field side
HEX-1 Heat Exchanger
Heat Valve 1 Heat Exchanger Heating Valve Control
Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature
Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature
Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature
HEX-2 Heat Exchanger
Heat Valve 1 Heat Exchanger Heating Valve Control
Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature
Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature
Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature
HEX-3 Heat Exchanger
Heat Valve 1 Heat Exchanger Heating Valve Control
Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature
Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature
Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature
HEX-4 Heat Exchanger
Heat Valve 1 Heat Exchanger Heating Valve Control
Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature
Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature
Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature

Building Automation System Technical Specification 2/6


Harold Holt Swimming Centre Building Automation System
Technical Specifcation APPENDIX A - BMS Point List

POINT AI AO DI DO HLI New? DESCRIPTION


HEX-5 Heat Exchanger
Heat Valve 1 Heat Exchanger Heating Valve Control
Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature
Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature
Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature
R-G-1
Room Temp 1 Ground Floor First Aid Room Temperature
Radiator Valve 1 Radiator Valve Control
R-G-2
Room Temp 1 Ground Floor Change Room Temperature
Radiator Valve 1 Radiator Valve Control
Roof Top Packaged Heat Recovery AC
AC-R-1
Pool Hall Temp 1 1 Y Combined Pool Zone Temperature 1
Pool Hall Humidity 1 1 Y Combined Pool Zone Humidity 1
Pool Hall Temp 2 1 Y Combined Pool Zone Temperature 2
Pool Hall Humidity 2 1 Y Combined Pool Zone Humidity 2
Supply Air Temp 1 Packaged Heat Recovery AC Supply Air Temperature
Return Air Temp 1 Packaged Heat Recovery AC Return Air Temperature
Status 1 Packaged Heat Recovery AC Run Status
Fault 1 Packaged Heat Recovery AC Fault Status
Start/Stop 1 Packaged Heat Recovery AC Start/Stop Command
Comp1 1 Packaged Heat Recovery AC Compressor 1 Command
Comp2 1 Packaged Heat Recovery AC Compressor 2 Command
Reversing Valve 1 Packaged Heat Recovery AC Reversing Valve Command
Roof Top Packaged Units
AC-R-2
Zone Temp 1 Programme Zone Temperature
Status 1 Packaged Unit Run Status
Fault 1 Packaged Unit Fault Status
Start/Stop 1 Packaged Unit Start/Stop Command
Comp 1 Packaged Unit Compressor Command
Reversing Valve 1 Packaged Unit Reversing Valve Command
AC-R-3
Zone Temp 1 Spinning Zone Temperature
Status 1 Packaged Unit Run Status
Fault 1 Packaged Unit Fault Status
Start/Stop 1 Packaged Unit Start/Stop Command
Comp 1 Packaged Unit Compressor Command
Reversing Valve 1 Packaged Unit Reversing Valve Command
AC-R-4
Zone Temp 1 First Floor Gymnasium Zone Temperature
Status 1 Packaged Unit Run Status
Fault 1 Packaged Unit Fault Status
Start/Stop 1 Packaged Unit Start/Stop Command
Comp1 1 Packaged Unit Compressor 1 Command
Comp2 1 Packaged Unit Compressor 2 Command
Reversing Valve 1 Packaged Unit Reversing Valve Command
AC-R-5
Zone Temp 1 Lobby Zone Temperature
Status 1 Packaged Unit Run Status
Fault 1 Packaged Unit Fault Status
Start/Stop 1 Packaged Unit Start/Stop Command
Comp 1 Packaged Unit Compressor Command
Reversing Valve 1 Packaged Unit Reversing Valve Command
AC-R-6
Zone Temp 1 Creche Zone Temperature
Status 1 Packaged Unit Run Status
Fault 1 Packaged Unit Fault Status

Building Automation System Technical Specification 3/6


Harold Holt Swimming Centre Building Automation System
Technical Specifcation APPENDIX A - BMS Point List

POINT AI AO DI DO HLI New? DESCRIPTION


Start/Stop 1 Packaged Unit Start/Stop Command
Comp 1 Packaged Unit Compressor Command
Reversing Valve 1 Packaged Unit Reversing Valve Command
Fan Coil Units
FCU-G-1
Room Temp 1 Ground Floor Change Rooms Temperature
Start/Stop 1 Fan Coil Unit Start/Stop Command
Status 1 Fan Coil Unit Run Status
Fault 1 Fan Coil Unit Fault Status
HHW Valve 1 Fan Coil Unit Heating Water Valve Control
FCU-G-2
Room Temp 1 Ground Floor Change Rooms Temperature
Start/Stop 1 Fan Coil Unit Start/Stop Command
Status 1 Fan Coil Unit Run Status
Fault 1 Fan Coil Unit Fault Status
HHW Valve 1 Fan Coil Unit Heating Water Valve Control
FCU-G-3
Room Temp 1 Ground Floor SPA Room Temperature
Start/Stop 1 Fan Coil Unit Start/Stop Command
Status 1 Fan Coil Unit Run Status
Fault 1 Fan Coil Unit Fault Status
HHW Valve 1 Fan Coil Unit Heating Water Valve Control
FCU-1-1
Room Temp 1 First Floor Change Room Temperature
Start/Stop 1 Fan Coil Unit Start/Stop Command
Status 1 Fan Coil Unit Run Status
Fault 1 Fan Coil Unit Fault Status
HHW Valve 1 Fan Coil Unit Heating Water Valve Control
Exhaust & Ventilation Air Systems
F-G-1
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-G-2
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-G-3
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-G-4
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-G-5
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-1-1
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-1-2
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-1-3
Start/Stop 1 Fan Start/Stop Command

Building Automation System Technical Specification 4/6


Harold Holt Swimming Centre Building Automation System
Technical Specifcation APPENDIX A - BMS Point List

POINT AI AO DI DO HLI New? DESCRIPTION


Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-1-4
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-1-5
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
F-1-6
Start/Stop 1 Fan Start/Stop Command
Status 1 Fan Run Status
Fault 1 Fan Fault Status
Outdoor Pool Pump Station (new)
Pool circulating Pump 1 Y HLI points included in 'Pool Service Board FSB-3'
Pool circulating Pump 2 Y HLI points included in 'Pool Service Board FSB-3'
Balance Tank Y HLI points included in 'Pool Service Board FSB-3'
Pool Circulation System Y HLI points included in 'Pool Service Board FSB-3'
Main pipe pressure Y HLI points included in 'Pool Service Board FSB-3'
Lighting (DB-1-1)
PE Cell Sensor
PE Cell 1 1 Y PE Cell Sensor for Circuit 1
PE Cell 2 1 Y PE Cell Sensor for Circuit 2
PE Cell 3 1 Y PE Cell Sensor for Circuit 3
PE Cell 4 1 Y PE Cell Sensor for Circuit 4
PE Cell 5 1 Y PE Cell Sensor for Circuit 5
PE Cell 6 1 Y PE Cell Sensor for Circuit 6
PE Cell 7 1 Y PE Cell Sensor for Circuit 7
PE Cell 8 1 Y PE Cell Sensor for Circuit 8
PE Cell 9 1 Y PE Cell Sensor for Circuit 9
PE Cell 10 1 Y PE Cell Sensor for Circuit 10
PE Cell 11 1 Y PE Cell Sensor for Circuit 11
PE Cell 12 1 Y PE Cell Sensor for Circuit 12
PE Cell 13 1 Y PE Cell Sensor for Circuit 13
PE Cell 14 1 Y PE Cell Sensor for Circuit 14
PE Cell 15 1 Y PE Cell Sensor for Circuit 15
Light Circuit 1 Enable 1 Y Enable Command for Circuit 1
Light Circuit 2 Enable 1 Y Enable Command for Circuit 2
Light Circuit 3 Enable 1 Y Enable Command for Circuit 3
Light Circuit 4 Enable 1 Y Enable Command for Circuit 4
Light Circuit 5 Enable 1 Y Enable Command for Circuit 5
Light Circuit 6 Enable 1 Y Enable Command for Circuit 6
Light Circuit 7 Enable 1 Y Enable Command for Circuit 7
Light Circuit 8 Enable 1 Y Enable Command for Circuit 8
Light Circuit 9 Enable 1 Y Enable Command for Circuit 9
Light Circuit 10 Enable 1 Y Enable Command for Circuit 10
Light Circuit 11 Enable 1 Y Enable Command for Circuit 11
Light Circuit 12 Enable 1 Y Enable Command for Circuit 12
Light Circuit 13 Enable 1 Y Enable Command for Circuit 13
Light Circuit 14 Enable 1 Y Enable Command for Circuit 14
Light Circuit 15 Enable 1 Y Enable Command for Circuit 15
Miscellaneous
Power Meter Typical Points (x 5)
Ph1 Voltage 5 Y Phase 1 to Neutral Voltage
Ph2 Voltage 5 Y Phase 2 to Neutral Voltage
Ph3 Voltage 5 Y Phase 3 to Neutral Voltage
Ph12 Voltage 5 Y Phase 1 to Phase 2 Voltage
Ph13 Voltage 5 Y Phase 1 to Phase 3 Voltage

Building Automation System Technical Specification 5/6


Harold Holt Swimming Centre Building Automation System
Technical Specifcation APPENDIX A - BMS Point List

POINT AI AO DI DO HLI New? DESCRIPTION


Ph23 Voltage 5 Y Phase 2 to Phase 3 Voltage
Ph1 Current 5 Y Phase 1 Current
Ph2 Current 5 Y Phase 2 Current
Ph3 Current 5 Y Phase 3 Current
Frequency 5 Y Frequency
PF 5 Y Power Factor
Active Power 5 Y Active Power
Reactive Power 5 Y Reactive Power
Apparent Power 5 Y Apparent Power
Active Energy 5 Y Active Energy
Reactive Energy 5 Y Reactive Energy
Apparent Energy 5 Y Apparent Energy
IoT Submetering System
Gas meter - Roof boiler 1 1 Y
Gas meter - Roof boiler 2 1 Y
Gas Meter - Outdoor boiler 3 & 4 1 Y
Gas Meter - Rooftop DHW 1 Y
Gas Meter - Outdoor DHW 1 Y
Water meter - Site Main 1 Y
Water meter - Hydrotherapy pool 1 Y
Water meter - Leisure pool 1 Y
Water meter - Outdoor 50m pool 1 Y
Pool Service Control System (x 3)
Pool Service Board FSB-1 30 Y
Pool Service Board FSB-2 30 Y
Pool Service Board FSB-3 50 Y Including the new outdoor pool pumping station
Room Temperatures
Server Cupboard Temp 1 Server Cupboard Temperature
Fitness Assessment Temp 1 Fitness Assessment Temperature
Kitchenette Temp 1 Kitchenette Temperature
Gym Office Temp 1 Gym Office Temperature
Reception Temp 1 Reception Temperature
Cafe Temp 1 Cafe Temperature
Domestic Hot Water System - Rooftop
Start/Stop 1 Y Pump Start/Stop Command
Status 1 Y Pump Run Status
Water Supply Temperature 1 Y Domestic Supply Temperature
Water Return Temperature 1 Y Domestic Supply Temperature
Domestic Hot Water System - Outdoor
Start/Stop 1 Y Pump Start/Stop Command
Status 1 Y Pump Run Status
Water Supply Temperature 1 Y Domestic Supply Temperature
Water Return Temperature 1 Y Domestic Supply Temperature
Ambient Sensors
Ambient Temperature 1 Y Ambient Temperature
Ambient Humidity 1 Y Ambient Humidity
TOTAL Points - existing 21 19 73 51 0 Existing sensors currently connected to the existing controllers
New field sensoring & controlling devices, and wiring to be
TOTAL Points - New 41 0 18 17 264
added
TOTAL BY TYPE 62 19 91 68 264
TOTAL 240 264 Spare points to be added as per Technical Specification

Building Automation System Technical Specification 6/6