Harold Holt Swimming Centre Building Automation System
Technical Specifcation APPENDIX A - BMS Point List
POINT AI AO DI DO HLI New? DESCRIPTION
Rooftop Heating System Boiler R-1 Rooftop Heating System Boiler Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Boiler 1 HLI 15 Y Modbus High Level Interface Boiler R-2 Rooftop Heating System Boiler Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Boiler 2 HLI 15 Y Modbus High Level Interface PHHWP-1 Rooftop Primary Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status PHHWP-2 Rooftop Primary Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status SHHWP-1 Rooftop Secondary Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status SHHWP-2 Rooftop Secondary Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status SAF/RAF Rooftop Heating System Supply/Return Air Fan SAF High Select 1 Supply Air Fan High Speed Select Command SAF High Status 1 Supply Air Fan High Speed Run Status SAF High Fault 1 Supply Air Fan High Speed Fault Status SAF Low Select 1 Supply Air Fan Low Speed Select Command SAF Low Status 1 Supply Air Fan Low Speed Run Status SAF Low Fault 1 Supply Air Fan Low Speed Fault Status RAF High Select 1 Supply Air Fan High Speed Select Command RAF High Status 1 Supply Air Fan High Speed Run Status RAF High Fault 1 Supply Air Fan High Speed Fault Status RAF Low Select 1 Supply Air Fan Low Speed Select Command RAF Low Status 1 Supply Air Fan Low Speed Run Status RAF Low Fault 1 Supply Air Fan Low Speed Fault Status HHW Valve 1 Heating Water Valve Control RAP Start/Stop 1 Run Around Heat Recovery Pump Start/Stop Command RAP Status 1 Run Around Heat Recovery Pump Run Status OA Damper 1 Outside Air Damper Control EA Damper 1 Exhaust Air Damper Control Pool Area Temp 1 Main Pool Area Temperature - return air grille Pool Area Humidity 1 1 Y Main Pool Area Humidity - return air grille Pool Area Temp 2 1 Y Main Pool Area Temperature 2 - far end of pool hall Pool Area Humidity 2 1 Y Main Pool Area Humidity 2 - far end of pool hall EA Temperature 1 Y Exhaust Air Temperature SA Temperature 1 Y Supply Air Temperature SA Humidity 1 Y Supply Air Humidity Indoor HHW System Rooftop Heating System Secondary Heating Water System Common Supply Water SHHW Com Supply Temp 1 Y Temperature Secondary Heating Water System Common Return Water SHHW Com Return Temp 1 1 Y Temperature - HEX 6 Secondary Heating Water System Common Return Water SHHW Com Return Temp 2 1 Y Temperature - SAF/RAF
Building Automation System Technical Specification 1/6
Harold Holt Swimming Centre Building Automation System Technical Specifcation APPENDIX A - BMS Point List
POINT AI AO DI DO HLI New? DESCRIPTION
HEX-6 Heat Exchanger Heat Valve 1 Heat Exchanger Heating Valve Control HHW Entering Temp 1 Y Heating Water Entering Temperature HHW Leaving Temp 1 Y Heating Water Leaving Temperature Pool Loop Entering Temp 1 Y Pool Loop Heating Water Entering Temperature Pool Loop Leaving Temp 1 Y Pool Loop Heating Water Leaving Temperature Pool Loop Pump Status 1 Y Pool Pump Run Status Outdoor Heating System Boiler G-1 Outdoor Heating System Boiler Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Boiler 3 HLI 15 Y Modus High Level Interface Boiler G-2 Outdoor Heating System Boiler Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Boiler 4 HLI 15 Y Modus High Level Interface HHWP-1 & VSD Outdoor Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Speed 1 VSD Speed Control HHWP-2 & VSD Outdoor Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Speed 1 VSD Speed Control HHWP-3 & VSD Outdoor Heating Water Pump Start/Stop 1 Start/Stop Command Status 1 Run Status Fault 1 Fault Status Speed 1 VSD Speed Control Outdoor HHW System Outdoor Heating System HHW System DP 1 Heating Water System Differential Pressure HHW Bypass Valve 1 Heating Water System Bypass Valve HHW Supply Temp 1 Y Heating Water System Supply Water Temperature HHW Return Temp 1 Y Heating Water System Return Water Temperature HHW System DP 1 Y Heating Water System Differential Pressure - field side HEX-1 Heat Exchanger Heat Valve 1 Heat Exchanger Heating Valve Control Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature HEX-2 Heat Exchanger Heat Valve 1 Heat Exchanger Heating Valve Control Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature HEX-3 Heat Exchanger Heat Valve 1 Heat Exchanger Heating Valve Control Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature HEX-4 Heat Exchanger Heat Valve 1 Heat Exchanger Heating Valve Control Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature
Building Automation System Technical Specification 2/6
Harold Holt Swimming Centre Building Automation System Technical Specifcation APPENDIX A - BMS Point List
POINT AI AO DI DO HLI New? DESCRIPTION
HEX-5 Heat Exchanger Heat Valve 1 Heat Exchanger Heating Valve Control Primary Leaving Temp 1 Y Primary Heating Water Leaving Temperature Secondary Entering Temp 1 Y Secondary Heating Water Entering Temperature Secondary Leaving Temp 1 Y Secondary Heating Water Leaving Temperature R-G-1 Room Temp 1 Ground Floor First Aid Room Temperature Radiator Valve 1 Radiator Valve Control R-G-2 Room Temp 1 Ground Floor Change Room Temperature Radiator Valve 1 Radiator Valve Control Roof Top Packaged Heat Recovery AC AC-R-1 Pool Hall Temp 1 1 Y Combined Pool Zone Temperature 1 Pool Hall Humidity 1 1 Y Combined Pool Zone Humidity 1 Pool Hall Temp 2 1 Y Combined Pool Zone Temperature 2 Pool Hall Humidity 2 1 Y Combined Pool Zone Humidity 2 Supply Air Temp 1 Packaged Heat Recovery AC Supply Air Temperature Return Air Temp 1 Packaged Heat Recovery AC Return Air Temperature Status 1 Packaged Heat Recovery AC Run Status Fault 1 Packaged Heat Recovery AC Fault Status Start/Stop 1 Packaged Heat Recovery AC Start/Stop Command Comp1 1 Packaged Heat Recovery AC Compressor 1 Command Comp2 1 Packaged Heat Recovery AC Compressor 2 Command Reversing Valve 1 Packaged Heat Recovery AC Reversing Valve Command Roof Top Packaged Units AC-R-2 Zone Temp 1 Programme Zone Temperature Status 1 Packaged Unit Run Status Fault 1 Packaged Unit Fault Status Start/Stop 1 Packaged Unit Start/Stop Command Comp 1 Packaged Unit Compressor Command Reversing Valve 1 Packaged Unit Reversing Valve Command AC-R-3 Zone Temp 1 Spinning Zone Temperature Status 1 Packaged Unit Run Status Fault 1 Packaged Unit Fault Status Start/Stop 1 Packaged Unit Start/Stop Command Comp 1 Packaged Unit Compressor Command Reversing Valve 1 Packaged Unit Reversing Valve Command AC-R-4 Zone Temp 1 First Floor Gymnasium Zone Temperature Status 1 Packaged Unit Run Status Fault 1 Packaged Unit Fault Status Start/Stop 1 Packaged Unit Start/Stop Command Comp1 1 Packaged Unit Compressor 1 Command Comp2 1 Packaged Unit Compressor 2 Command Reversing Valve 1 Packaged Unit Reversing Valve Command AC-R-5 Zone Temp 1 Lobby Zone Temperature Status 1 Packaged Unit Run Status Fault 1 Packaged Unit Fault Status Start/Stop 1 Packaged Unit Start/Stop Command Comp 1 Packaged Unit Compressor Command Reversing Valve 1 Packaged Unit Reversing Valve Command AC-R-6 Zone Temp 1 Creche Zone Temperature Status 1 Packaged Unit Run Status Fault 1 Packaged Unit Fault Status
Building Automation System Technical Specification 3/6
Harold Holt Swimming Centre Building Automation System Technical Specifcation APPENDIX A - BMS Point List
POINT AI AO DI DO HLI New? DESCRIPTION
Start/Stop 1 Packaged Unit Start/Stop Command Comp 1 Packaged Unit Compressor Command Reversing Valve 1 Packaged Unit Reversing Valve Command Fan Coil Units FCU-G-1 Room Temp 1 Ground Floor Change Rooms Temperature Start/Stop 1 Fan Coil Unit Start/Stop Command Status 1 Fan Coil Unit Run Status Fault 1 Fan Coil Unit Fault Status HHW Valve 1 Fan Coil Unit Heating Water Valve Control FCU-G-2 Room Temp 1 Ground Floor Change Rooms Temperature Start/Stop 1 Fan Coil Unit Start/Stop Command Status 1 Fan Coil Unit Run Status Fault 1 Fan Coil Unit Fault Status HHW Valve 1 Fan Coil Unit Heating Water Valve Control FCU-G-3 Room Temp 1 Ground Floor SPA Room Temperature Start/Stop 1 Fan Coil Unit Start/Stop Command Status 1 Fan Coil Unit Run Status Fault 1 Fan Coil Unit Fault Status HHW Valve 1 Fan Coil Unit Heating Water Valve Control FCU-1-1 Room Temp 1 First Floor Change Room Temperature Start/Stop 1 Fan Coil Unit Start/Stop Command Status 1 Fan Coil Unit Run Status Fault 1 Fan Coil Unit Fault Status HHW Valve 1 Fan Coil Unit Heating Water Valve Control Exhaust & Ventilation Air Systems F-G-1 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-G-2 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-G-3 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-G-4 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-G-5 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-1-1 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-1-2 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-1-3 Start/Stop 1 Fan Start/Stop Command
Building Automation System Technical Specification 4/6
Harold Holt Swimming Centre Building Automation System Technical Specifcation APPENDIX A - BMS Point List
POINT AI AO DI DO HLI New? DESCRIPTION
Status 1 Fan Run Status Fault 1 Fan Fault Status F-1-4 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-1-5 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status F-1-6 Start/Stop 1 Fan Start/Stop Command Status 1 Fan Run Status Fault 1 Fan Fault Status Outdoor Pool Pump Station (new) Pool circulating Pump 1 Y HLI points included in 'Pool Service Board FSB-3' Pool circulating Pump 2 Y HLI points included in 'Pool Service Board FSB-3' Balance Tank Y HLI points included in 'Pool Service Board FSB-3' Pool Circulation System Y HLI points included in 'Pool Service Board FSB-3' Main pipe pressure Y HLI points included in 'Pool Service Board FSB-3' Lighting (DB-1-1) PE Cell Sensor PE Cell 1 1 Y PE Cell Sensor for Circuit 1 PE Cell 2 1 Y PE Cell Sensor for Circuit 2 PE Cell 3 1 Y PE Cell Sensor for Circuit 3 PE Cell 4 1 Y PE Cell Sensor for Circuit 4 PE Cell 5 1 Y PE Cell Sensor for Circuit 5 PE Cell 6 1 Y PE Cell Sensor for Circuit 6 PE Cell 7 1 Y PE Cell Sensor for Circuit 7 PE Cell 8 1 Y PE Cell Sensor for Circuit 8 PE Cell 9 1 Y PE Cell Sensor for Circuit 9 PE Cell 10 1 Y PE Cell Sensor for Circuit 10 PE Cell 11 1 Y PE Cell Sensor for Circuit 11 PE Cell 12 1 Y PE Cell Sensor for Circuit 12 PE Cell 13 1 Y PE Cell Sensor for Circuit 13 PE Cell 14 1 Y PE Cell Sensor for Circuit 14 PE Cell 15 1 Y PE Cell Sensor for Circuit 15 Light Circuit 1 Enable 1 Y Enable Command for Circuit 1 Light Circuit 2 Enable 1 Y Enable Command for Circuit 2 Light Circuit 3 Enable 1 Y Enable Command for Circuit 3 Light Circuit 4 Enable 1 Y Enable Command for Circuit 4 Light Circuit 5 Enable 1 Y Enable Command for Circuit 5 Light Circuit 6 Enable 1 Y Enable Command for Circuit 6 Light Circuit 7 Enable 1 Y Enable Command for Circuit 7 Light Circuit 8 Enable 1 Y Enable Command for Circuit 8 Light Circuit 9 Enable 1 Y Enable Command for Circuit 9 Light Circuit 10 Enable 1 Y Enable Command for Circuit 10 Light Circuit 11 Enable 1 Y Enable Command for Circuit 11 Light Circuit 12 Enable 1 Y Enable Command for Circuit 12 Light Circuit 13 Enable 1 Y Enable Command for Circuit 13 Light Circuit 14 Enable 1 Y Enable Command for Circuit 14 Light Circuit 15 Enable 1 Y Enable Command for Circuit 15 Miscellaneous Power Meter Typical Points (x 5) Ph1 Voltage 5 Y Phase 1 to Neutral Voltage Ph2 Voltage 5 Y Phase 2 to Neutral Voltage Ph3 Voltage 5 Y Phase 3 to Neutral Voltage Ph12 Voltage 5 Y Phase 1 to Phase 2 Voltage Ph13 Voltage 5 Y Phase 1 to Phase 3 Voltage
Building Automation System Technical Specification 5/6
Harold Holt Swimming Centre Building Automation System Technical Specifcation APPENDIX A - BMS Point List
POINT AI AO DI DO HLI New? DESCRIPTION
Ph23 Voltage 5 Y Phase 2 to Phase 3 Voltage Ph1 Current 5 Y Phase 1 Current Ph2 Current 5 Y Phase 2 Current Ph3 Current 5 Y Phase 3 Current Frequency 5 Y Frequency PF 5 Y Power Factor Active Power 5 Y Active Power Reactive Power 5 Y Reactive Power Apparent Power 5 Y Apparent Power Active Energy 5 Y Active Energy Reactive Energy 5 Y Reactive Energy Apparent Energy 5 Y Apparent Energy IoT Submetering System Gas meter - Roof boiler 1 1 Y Gas meter - Roof boiler 2 1 Y Gas Meter - Outdoor boiler 3 & 4 1 Y Gas Meter - Rooftop DHW 1 Y Gas Meter - Outdoor DHW 1 Y Water meter - Site Main 1 Y Water meter - Hydrotherapy pool 1 Y Water meter - Leisure pool 1 Y Water meter - Outdoor 50m pool 1 Y Pool Service Control System (x 3) Pool Service Board FSB-1 30 Y Pool Service Board FSB-2 30 Y Pool Service Board FSB-3 50 Y Including the new outdoor pool pumping station Room Temperatures Server Cupboard Temp 1 Server Cupboard Temperature Fitness Assessment Temp 1 Fitness Assessment Temperature Kitchenette Temp 1 Kitchenette Temperature Gym Office Temp 1 Gym Office Temperature Reception Temp 1 Reception Temperature Cafe Temp 1 Cafe Temperature Domestic Hot Water System - Rooftop Start/Stop 1 Y Pump Start/Stop Command Status 1 Y Pump Run Status Water Supply Temperature 1 Y Domestic Supply Temperature Water Return Temperature 1 Y Domestic Supply Temperature Domestic Hot Water System - Outdoor Start/Stop 1 Y Pump Start/Stop Command Status 1 Y Pump Run Status Water Supply Temperature 1 Y Domestic Supply Temperature Water Return Temperature 1 Y Domestic Supply Temperature Ambient Sensors Ambient Temperature 1 Y Ambient Temperature Ambient Humidity 1 Y Ambient Humidity TOTAL Points - existing 21 19 73 51 0 Existing sensors currently connected to the existing controllers New field sensoring & controlling devices, and wiring to be TOTAL Points - New 41 0 18 17 264 added TOTAL BY TYPE 62 19 91 68 264 TOTAL 240 264 Spare points to be added as per Technical Specification
Building Automation System Technical Specification 6/6