Professional Documents
Culture Documents
Types of Violation
Remedial Actions
5
Introduction
• In the past many wide spread blackouts have occurred in interconnected power
systems therefore it is necessary to insure that power system should be operated
most economically such that power is delivered reliably.
• Contingency analysis is abnormal condition in electrical network. It put whole
system or a part of the system under stress.
Introduction
• It occurs due to
• Sudden opening of a transmission line,
• Generator tripping,
• Sudden change in generation,
• Sudden change in load value,
Introduction
• The Line Outage Distribution Factor (LODF) is one of the important linear
sensitivity factors which play a key role in finding the effect of the critical
contingencies and hence suggesting possible preventive and corrective actions to
solve the violations in the system.
LODF
• LODFs are used to approximate the change in the flow on one line caused by the
outage of a second line.
• Typically they are only used to determine the change in the MW flow compared to
the pre-contingency flow
• LODFs are approximately independent of flows but do depend on the assumed
network topology.
Types of Violations
This type of violation occurs at the buses. This suggests that the voltage at the
bus is less than the specified value.
The operating range of voltage at any bus is generally 0.95-1.05 p.u.
Thus if the voltage falls below 0.95 p.u then the bus is said to have low voltage,
If the voltage rises above the 1.05 p.u then the bus is said to have a high voltage
problem. .
Types of Violations
Optimal Dispatch
Available to contingency
Optimal With respect to Economic operation
States of Security Analysis
Post Contingency
State after contingency
This Condition has a security Violation
States of Security Analysis
Secure Dispatch
System with no contingency
Account for security violations
States of Security Analysis
Secure Post-Contingency
Contingency at base condition after corrections
Remedial Actions
Contingency (Outage)
G1
Substation
Substation
FAULT
G2
05/26/2020 20
source[7]
States of Security Analysis
6
States of Security Analysis
• Normal State: In normal state, the power balance between generation and load
is satisfied and no equipment is overloaded. All the voltages are within limits. In
addition, the system has sufficient security margin to withstand any of the
credible contingencies.
States of Security Analysis
• Alert state: Under this state, the power balance between generation and load is
still met. No equipment is overloaded. No voltage is out of its limits. However,
when a severe contingency occurs, the system will either have overloaded
equipments or have voltage violations.
States of Security Analysis
• Emergency state: The power balance between generation and load is still
satisfied. However, either overloaded or voltage violations happen in emergency
state. If suitable corrective control actions are taken, the state can still be
restored to normal state or at least alert state.
States of Security Analysis
• In Extremis State: Under this state, the power balance between generation
and load is lost. Voltage violation may happen and some equipment is
overloaded. There are cascading outages. Load shedding may be taken, to
save as much of the system as possible.
6
States of Security Analysis
• Restorative State: Under this state, the operator performs control actions
to restore all system loads. Depending on different cases, the system can
reach either normal or alert state.
6
Load Flow
Image source[3]
4
IEEE 14 Bus General Layout
Image source[2]
28
IEEE 14 Bus Data-1
REACTIVE POWER
BUS VOLTAGE GENERATION LOAD
LIMITS
BUS
NUMBER MAGNITUDE Real Reactive Real Reactive
Phase Angle QMIN QMAX
Power Power Power Power
(p.u.) (degree) (MVAR) (MVAR)
(MW) (MVAR) (MW) (MVAR)
1 1.06 0 114.17 -16.9 0 0 0 10
2 1.045 0 40 0 21.7 12.7 -42 50
3 1.01 0 0 0 94.2 19.1 23.4 40
4 1 0 0 0 47.8 -3.9 -- --
5 1 0 0 0 7.6 1.6 -- --
6 1 0 0 0 11.2 7.5 -- --
7 1 0 0 0 0 0 -- --
8 1 0 0 0 0 0 -- --
9 1 0 0 0 29.5 16.6 -- --
10 1 0 0 0 9 5.8 -- --
11 1 0 0 0 3.5 1.8 -- --
12 1 0 0 0 6.1 1.6 -- --
13 1 0 0 0 13.8 5.8 -- --
14 1 0 0 0 14.9 5 -- -- source[1]
29
IEEE 14 Line Data-2
LINE IMPEDANCE (p.u.)
LINE FROM TO HALF LINE CHARGING MVA
NUMBER BUS BUS SUSCEPTANCE (p.u.) RATING
RESISTANCE REACTANCE
OUR DATA STD DATA OUR DATA STD DATA OUR DATA STD DATA OUR DATA STD DATA OUR DATA STD DATA OUR DATA STD DATA OUR DATA STD DATA OUR DATA STD DATA
Name Node kV V % v ° Angle U MW P Load MVar Q Load MW P Gen MVar Q Gen
Node Nam e V kV v % Angle U ° P Load MW Q Load MVar P Gen MW Q Gen MVar
B-1 BUS_1 69.0 69 73.14 100 106 0 0 0 0 7.959 14.88 234.742 232.597 0 0
B-2 BUS_2 69.0 67.785 72.105 98.24 104.5 -5.7 -5 21.7 21.7 12.7 12.7 40 40 50 49.157
B-3 BUS_3 69.0 65.8 69.69 95.36 101 -14.7 -12.8 94.2 94.2 19 19 0 0 40 27.578
B-4 BUS_4 69.0 65.055 69.803 94.28 101.16 -11.6 -10.2 47.8 47.8 4 4 0 0 0 0
B-5 BUS_5 69.0 65.396 70.09 94.78 101.58 -9.9 -8.7 7.6 7.6 1.6 1.6 0 0 0 0
B-6 BUS_6 13.8 13.716 14.766 99.39 107 -16.5 -14.4 11.2 11.2 7.5 7.5 0 0 24 22.979
B-7 BUS_7 13.8 13.298 14.46 96.36 104.78 -15 -13.2 0 0 0 0 0 0 0 0
B-8 BUS_8 18.0 4.737 19.561 26.32 108.67 -15 -13.2 0 0 0 0 0 0 24 24
B-9 BUS_9 13.8 13.097 14.238 94.91 103.17 -16.9 -14.8 29.5 29.5 16.6 16.6 0 0 0 0
B-10 BUS_10 13.8 13.093 14.226 94.88 103.09 -17.2 -15 9 9 5.8 5.8 0 0 0 0
B-11 BUS_11 13.8 13.347 14.444 96.72 104.66 -17 -14.8 3.5 3.5 1.8 1.8 0 0 0 0
B-12 BUS_12 13.8 13.463 14.536 97.56 105.33 -17.5 -15.3 6.1 6.1 1.6 1.6 0 0 0 0
B-13 BUS_13 13.8 13.362 14.446 96.83 104.68 -17.5 -15.3 13.5 13.5 5.8 5.8 0 0 0 0
B-14 BUS_14 13.8 12.938 14.076 93.75 102 -18.4 -16.1 14.9 14.9 5 5 0 0 0 0
ZOOM
OPEN ENTIRE
RESUTS
31
RESULTS COMPARISION
32
RESULTS COMPARISION
33
RESULTS COMPARISION
34
14-BUS SYSTEM LAYOUT (NEPLAN)
35
Necessity of Contingency Analysis
36
Different mathematical techniques
37
Fast decoupled Load Flow
38
Fast decoupled Load Flow
39
Contingency Analysis Flow Chart
40
Contingency Analysis Results
Generator 2 removed
41
Contingency Analysis Results
Generator 2 removed
42
Contingency Analysis Results
43
Contingency Analysis Results
44
Contingency Analysis Results
Transformer 3 removed
45
TO KNOW THE ROAD AHEAD, ASK THOSE COMING BACK.
Refrences
30