Professional Documents
Culture Documents
1
Announcements
• No class on Sept 24 because of NAPS; HW1 due 9/12
• Some of the material from this lecture is in T.J.
Overbye, “Power System Simulation: Understanding
Small and Large-System Operation,” IEEE Power and
Energy Magazine, 2004; also in M. Crow, G. Gross,
P.W. Sauer, “Power System Basics for Business
Professionals in Our Industry,” IEEE Power and Energy
Magazine, 2003
• Additional information about the power system design
problem is in T.J. Overbye, “Fostering Intuitive Minds
for Power System Design,” IEEE Power and Energy
Magazine, 2003 2
Two Bus Newton-Raphson
Example
For the two bus power system shown below, use the
Newton-Raphson power flow to determine the
voltage magnitude and angle at bus two. Assume
that bus one is the slack and SBase = 100 MVA.
Line Z = 0.1j
0 MW 200 MW
0 MVR 100 MVR
2 j10 j10
x Ybus
V2 j10 j10
3
Two Bus Example, cont’d
General power balance equations
n
Pi Vi Vk (Gik cosik Bik sin ik ) PGi PDi
k 1
n
Qi Vi Vk (Gik sin ik Bik cosik ) QGi QDi
k 1
Bus two power balance equations
V2 V1 (10sin 2 ) 2.0 0
2
V2 V1 (10cos 2 ) V2 (10) 1.0 0
4
Two Bus Example, cont’d
P2 (x) V2 (10sin 2 ) 2.0 0
2
Q2 (x) V2 (10cos 2 ) V2 (10) 1.0 0
Now calculate the power flow Jacobian
P2 (x) P2 (x)
V 2
2
J ( x)
Q 2 (x) Q 2 (x)
V 2
2
(0)
V2 (10sin 2 ) 2.0 2.0
f(x ) 2 1.0
V2 (10cos 2 ) V2 (10) 1.0
(0) 10 V2 cos 2 10sin 2 10 0
J (x ) 0 10
10 V2 sin 2 10cos 2 20 V2
1
(1) 0 10 0 2.0 0.2
Solve x 1.0
1
0 10 0.9
6
Two Bus Example, Next Iterations
(1) 0.9(10sin( 0.2)) 2.0 0.212
f(x ) 2
0.9( 10cos( 0.2)) 0.9 10 1.0 0.279
(1) 8.82 1.986
J (x )
1.788 8.199
1
(2) 0.2 8.82 1.986 0.212 0.233
x
0.9 1.788 8.199 0.279 0.8586
(2) 0.0145 (3) 0.236
f(x ) x
0.0190 0.8554
(3) 0.0000906
f(x ) Done! V2 0.8554 13.52
0.0001175
7
Two Bus Solved Values
Once the voltage angle and magnitude at bus 2 are
known we can calculate all the other system values,
such as the line flows and the generator reactive
power output
200.0 MW -200.0 MW
168.3 MVR Line Z = 0.1j -100.0 MVR
200.0 MW 2 00 MW
168.3 MVR 1 00 MVR
(0)
V2 (10sin 2 ) 2.0 2
f(x ) 2 0.875
V2 (10 cos 2 ) V2 (10) 1.0
(0) 10 V2 cos 2 10sin 2 2.5 0
J (x ) 0 5
10 V2 sin 2 10 cos 2 20 V2
9
Low Voltage Solution, cont'd
1
0 2.5 0 2
(1) 0.8
Solve x
0.25 0 5 0.875 0.075
(2) 1.462 (2) 1.42 (3) 0.921
f (x ) x x
0.534 0.2336 0.220
Low voltage solution
200.0 MW -200.0 MW
831.7 MVR Line Z = 0.1j -100.0 MVR
200.0 MW 200 MW
831.7 MV R 100 MV R
10
Practical Power Flow Software Note
• Most commercial software packages have built in
defaults to prevent convergence to low voltage
solutions.
– One approach is to automatically change the load model from
constant power to constant current or constant impedance
when the load bus voltage gets too low
– In PowerWorld these defaults can be modified on the Tools,
Simulator Options, Advanced Options page; note you also
need to disable the “Initialize from Flat Start Values” option
– The PowerWorld case Bus2_Intro_Low is set solved to the
low voltage solution
– Initial bus voltages can be set using the Bus Information
Dialog
11
Two Bus Region of Convergence
Slide shows the region of convergence for different initial
guesses of bus 2 angle (x-axis) and magnitude (y-axis)
Red region
converges
to the high
voltage
solution,
while the
yellow region
converges
to the low
voltage
solution
12
Power Flow Fractal Region of
Convergence
• Earliest paper showing fractal power flow regions of
convergence is by C.L DeMarco and T.J. Overbye,
“Low Voltage Power Flow Solutions and Their Role in
Exit Time Bases Security Measures for Voltage
Collapse,” Proc. 27th IEEE CDC, December 1988
• A more widely known paper is J.S. Thorp, S.A. Naqavi,
“Load-Flow Fractals Draw Clues to Erratic Behavior,”
IEEE Computer Applications in Power, January 1997
13
An Unexpected Low Voltage Solution
The 8/14/03
MISO day
ahead
model had
65
energized
115,138,
or 230 kV
buses
with
voltages
below
0.90 pu
The lowest 138 kV voltage was 0.836 pu; lowest 34.5 kV was 0.621 pu;
case contained 42,766 buses; case had been used daily all summer. This
was a low voltage solution!
14
PV Buses
|Vi | – Vi setpoint = 0 15
Three Bus PV Case Example
For this three bus case we have
2 P2 (x) PG 2 PD 2
x 3 f (x) P3 (x) PG 3 PD 3 0
V2 Q2 (x) QD 2
Line Z = 0.1j
0.941 pu
One 1.000 pu Two -7.469 Deg
170.0 MW 200 MW
68.2 MVR 100 MVR
Line Z = 0.1j Line Z = 0.1j
Three 1.000 pu
30 MW
63 MVR
16
Modeling Voltage Dependent Load
So far we've assumed that the load is independent of
the bus voltage (i.e., constant power). However, the
power flow can be easily extended to include voltage
depedence with both the real and reactive load. This
is done by making PDi and Q Di a function of Vi :
n
Vi Vk (Gik cosik Bik sin ik ) PGi PDi ( Vi ) 0
k 1
n
Vi Vk (Gik sin ik Bik cosik ) QGi QDi ( Vi ) 0
k 1
17
Voltage Dependent Load Example
In previous two bus example now assume the load is
constant impedance, so
2
P2 (x) V2 (10sin 2 ) 2.0 V2 0
2 2
Q2 (x) V2 (10cos 2 ) V2 (10) 1.0 V2 0
Now calculate the power flow Jacobian
10 V2 cos 2 10sin 2 4.0 V2
J ( x)
10 V2 sin 2 10cos 2 20 V2 2.0 V2
18
Voltage Dependent Load, cont'd
(0) 0
Again set v 0, guess x
1
Calculate
2
(0) V2 (10sin 2 ) 2.0 V2 2.0
f(x )
V2 (10cos 2 ) V2 2 (10) 1.0 V2 2 1.0
(0) 10 4
J (x )
0 12
1
(1) 0 10 4 2.0 0.1667
Solve x 1.0
1
0 12 0.9167
19
Voltage Dependent Load, cont'd
With constant impedance load the MW/Mvar load at
bus 2 varies with the square of the bus 2 voltage
magnitude. This if the voltage level is less than 1.0,
the load is lower than 200/100 MW/Mvar
160.0 MW -160.0 MW
120.0 MVR Line Z = 0.1j -80.0 MVR
0.894 pu
One 1.000 pu Two -10.304 Deg
160.0 MW 160 MW
120.0 MV R 80 MV R
20
Generator Reactive Power Limits
Line 2
Line 1
345 kV
15/345 kV 100 mi 200 mi
2
280 Mvar 800 MW
Single-line diagram
2 P2 = PG2-PL2 = -8 V2, 2
Table 4. Input data Q2 = QG2-QL2 = -2.8
and unknowns
3 V3 = 1.05 Q3, 3
P3 = PG3-PL3 = 4.4
4 P4 = 0, Q4 = 0 V4, 4
5 P5 = 0, Q5 = 0 V5, 5 25
Five Bus Case Ybus
1 1
Y25 ' '
1.78552 j19.83932 per unit
R25 jX 25 0.0045 j 0.05
' '
1 1 B24 B25
Y22 ' '
' '
j j
R24 jX 24 R25 jX 25 2 2
1.72 0.88
(0.89276 j 9.91964) (1.78552 j19.83932) j j
2 2
2.67828 j 28.4590 28.5847 84.624 per unit
27
Here are the Initial Bus Mismatches
28
And the Initial Power Flow Jacobian
29
And the Hand Calculation Details
MVA MVA
395 MW A
520 MW
MVA
1.000 pu 0.974 pu A A
1.019 pu 80 MW
0.000 Deg -4.548 Deg MVA MVA
-2.834 Deg 40 Mvar
1.050 pu
-0.597 Deg
0.834 pu Two
-22.406 Deg
800 MW
280 Mvar
31
Power System Operations Overview
32
Power System Basics
34
Small PowerWorld Simulator Case
Load with
green Bus 2
-20 MW
4 MVR
20 MW
-4 MVR Bus 1
arrows 204 MW
1.00 PU
to control
output of Direction of arrow is used to indicate
generator direction of real power (MW) flow
PowerWorld Case: B3NewSlow 35
Basic Power Control
• Opening a circuit breaker causes the power flow to
instantaneously (nearly) change.
• No other way to directly control power flow in a
transmission line.
• By changing generation we can indirectly change this
flow.
• Power flow in transmission line is limited by heating
considerations
• Losses (I^2 R) can heat up the line, causing it to sag.
36
Overloaded Transmission Line
37
Interconnected Operation
39
Area Control Error (ACE)
41
Three Bus Case on AGC
-40 MW 40 MW
Bus 2 8 MVR -8 MVR Bus 1
1.00 PU
266 MW
133 MVR
1.00 PU
101 MW
5 MVR
-77 MW -39 MW
150 MW AGC ON
25 MVR 12 MVR 100 MW
166 MVR AVR ON
78 MW 39 MW
-21 MVR -11 MVR
Bus 3 1.00 PU
Home Area
133 MW
Generation 67 MVR
250 MW AGC ON
is automatically 34 MVR AVR ON