You are on page 1of 1

AIR COOLER SERVICE: LIQUID COOLER: GAS OR VAPOR COOLER: NON-STM CONDENSER: STEAM CONDENSER: MIXED SERVICE

LIQUID COOLER
SELECT
A TYPE OF SERVICE

ITEM NO.:
FOR A COST ESTIMATE, ENTER THE REQUIRED INFORMATION BELOW:

E-1803

(OPTIONAL) CE INDEX FOR EQUIPMENT (1978's = 243) DESIGN PRESSURE, PSIG METALLURGY CODE

BARETUBE COEFFICIENT, 'U' HEAT DUTY, MMBTU/HR HOT FLUID INLET TEMP, F HOT FLUID OUT TEMP, F INLET AIR TEMPERATURE, F DO YOU WISH TO SPECIFY TUBE ROWS AND LENGTH? TUBE ROWS (3-10) = LENGTH (50' MAX) = ESTIMATED DIMENSIONS: WITH -

70.00 4.550 222.60 115.00 95.00 YES 6 24.0

243 85 316

'

ESTIMATED COST OF SPECIFIED UNIT WITH SPECIFIED METALLURGY: $59,044 TOTAL OPERATING FAN HP 15 CALCULATED TUBE ROWS 6 BARE TUBE AREA, FT 1,460 9'

24.0 ' TUBES (SPECIFIED), MINIMUM WIDTH IS:

Recommended air cooler specifications for preliminary estimate are: 24.0' Tube Length X 9' Total Width, 6 Tube Rows, 1 Bay With 2 - 20 HP Motor Fans

Source for ISO 9000 Considerations: YUBA Bulletin 21 - Air Cooled Exchangers, 1980

(YUBA no longer offers air cooled exchangers or this bulletin. Metallurgy cost factors are courtesy of Hudson Engineering, Inc., Houston, Texas.)
Z:\225_Process\Calculations\Equipment\Exchangers\Air Coolers\[E-1803 air cooler_vv.xls]Fast AC Method, Ver. 2.2

DATE:

04/12/06 CLIENT: Marathon Ashland Petroleum

CONTRACT NO.: UNIT/AREA:

214 - Kerosesne Hydrotreater GARYVILLE MAJOR EXPANSION PROJECT

PROJECT NAME: LOCATION: BY: ARB PURPOSE:

GARYVILLE, LA CHK'D.: SHEET NO.: 1 OF 1

ESTIMATE SIZE OF HOT SEPARATOR OVHD. CONDENSER